Quick reference

Occupational Health, Safety and Environment

  • Electric shock severity depends on current path, magnitude and duration: 30 mA across the heart can cause ventricular fibrillation; 50 mA is a commonly cited lethal threshold.

  • Body resistance falls from about 100 kΩ dry skin to roughly 1 kΩ when skin is wet, so touch voltage limits are set low: 50 V AC in dry, 25 V AC in wet or confined locations.

  • First aid for a shock victim: isolate supply, do not touch the casualty until proved dead, call for help, start CPR if breathing has stopped, place unconscious but breathing casualties in the recovery position.

  • Fire classes: A solid, B liquid, C gas, D metal, F cooking oil; use CO2 or dry powder on live electrical (Class C/E) fires, never water or foam.

  • Lockout/tagout sequence: identify all energy sources, isolate, lock and tag, prove dead with a tested voltage detector, discharge stored energy, then work.

  • A permit-to-work is required for live working, work in confined spaces, and work on high-voltage equipment; it records isolation points, limits and authorisation.

  • Personal protective equipment hierarchy: eliminate, substitute, engineer controls, administrate, then PPE last; PPE for electrical work includes insulating gloves, arc-rated clothing, face shield and safety footwear.

  • Environment: waste segregation (e-waste, lamps, batteries, solvents), spill kits for transformer oil, and no burning of PVC insulation because it releases hydrogen chloride.

Quick reference

Basic Electrical Principles and Calculations

  • Ohm's law V = I × R; power P = V × I = I²R = V²/R; for three-phase, P = √3 × V_L × I_L × cos φ.

  • Series: R_total = R1 + R2 + …; parallel: 1/R_total = 1/R1 + 1/R2 + …; two resistors in parallel give product over sum.

  • Kirchhoff's laws: current law, sum of currents at a node is zero; voltage law, algebraic sum of EMFs and drops around a loop is zero.

  • Energy in kWh = power in kW × time in hours; one unit of electricity = 1 kWh = 3.6 MJ.

  • AC: f = 1/T; ω = 2πf; X_L = 2πfL; X_C = 1/(2πfC); Z = √(R² + (X_L − X_C)²); cos φ = R/Z.

  • Star (Y) and delta (Δ) relations: in a balanced star, V_L = √3 V_ph and I_L = I_ph; in delta, V_L = V_ph and I_L = √3 I_ph.

  • RMS and peak: V_rms = V_peak/√2 ≈ 0.707 V_peak; V_peak = 1.414 V_rms; form factor 1.11, peak factor 1.414 for a sine wave.

  • Temperature coefficient: R2 = R1[1 + α(T2 − T1)]; conductor resistance rises with temperature, insulation resistance falls with temperature and moisture.

Quick reference

Electrical Materials

  • Copper: resistivity about 1.72 × 10⁻⁸ Ω·m, excellent conductor, used for conductors and busbars; annealed copper is soft, hard-drawn is stronger.

  • Aluminium: resistivity about 2.83 × 10⁻⁸ Ω·m, about 60% of copper conductivity by volume but far lighter; requires antioxidant paste and bimetallic joints to prevent electrolytic corrosion with copper.

  • Insulation classes and limiting temperatures: Y 90 °C, A 105 °C, E 120 °C, B 130 °C, F 155 °C, H 180 °C, C above 180 °C.

  • PVC insulation: good dielectric, flame-retardant, maximum conductor temperature 70 °C; XLPE: 90 °C continuous, higher current rating and better overload withstand.

  • Magnetic materials: soft iron and silicon steel (low hysteresis, high permeability) for cores; hard magnetic materials such as Alnico and ferrite for permanent magnets.

  • Contact materials: silver alloys for low contact resistance; tungsten for arc resistance in heavy contacts; brass and phosphor bronze for springs and terminals.

  • Solder: tin-lead 60/40 melts near 183–190 °C; lead-free SAC alloys melt near 217–227 °C and need higher iron temperatures.

  • Conduit and trunking: PVC for corrosive or damp areas, steel for mechanical protection and earth continuity; minimum conduit size is chosen so cable fill does not exceed about 40%.

Quick reference

Electrical Materials, Tools and Hand Skills

  • Insulated hand tools must be rated 1000 V and marked; check insulation for cuts before use and never use them as a substitute for isolation.

  • Wire stripping: set the stripper to the conductor gauge so strands are not nicked; a nicked strand reduces current capacity and creates a hot spot.

  • Crimping: match the lug to conductor size and use the correct die; a correct crimp shows no loose strands, passes a pull test and is insulated or heat-shrunk.

  • Bending conduit: minimum bend radius is commonly 6–10 times the conduit diameter; use a bending spring for PVC and a hickey or bender for rigid steel.

  • Terminal tightening: use a torque screwdriver where specified; loose terminals cause arcing and overheating, over-tightened terminals damage strands and threads.

  • Soldering a joint: clean and tin the iron, heat the joint and apply solder to the joint not the iron, aim for a shiny concave fillet, avoid a cold dull joint.

  • Measuring tools: vernier caliper for conductor and conduit diameter, micrometer for wire gauge, megger for insulation, multimeter for volts, amps and continuity.

  • Safe hand-tool practice: sharp-edged tools stored sheathed, chisels and files used away from the body, no loose clothing near rotating tools, eye protection for drilling and cutting.

Quick reference

Wiring Systems

  • Domestic lighting circuits are commonly wired in loop-in (loop at the ceiling rose) or loop-in at the switch; the three-plate rose carries permanent live, switched live and neutral.

  • Radial circuits serve one direction from the board; ring circuits return to the board, so a broken ring must be detected by continuity tests of all three conductors.

  • Two-way switching uses two strappers between the switches plus common and switched live; intermediate switches are inserted in the strappers for three or more control points.

  • Cable colour convention (IEC): line brown, neutral blue, protective earth green-yellow; old UK colours were red line, black neutral, green earth.

  • Cable sizing depends on design current, protective device rating, voltage drop (typically 3% lighting, 5% other loads) and correction factors for grouping and ambient temperature.

  • Voltage drop mV/A/m tables: drop = (mV/A/m × current × length)/1000; long runs often force a larger cable than current-carrying capacity alone.

  • Conduit and trunking systems: draw wires after conduit is erected, use inspection bends and boxes, and keep bends to a minimum to allow rewiring.

  • Segregation: extra-low-voltage and mains cables in the same enclosure require separate compartments or a barrier; data and power cables cross at right angles to limit interference.

Quick reference

Installation and Protection

  • MCB types: B trips at 3–5 × In, C at 5–10 × In, D at 10–20 × In; choose B for resistive loads, C for inductive motor loads, D for high inrush.

  • Fuse: rewirable and HRC types; HRC cartridge fuses have a high breaking capacity and current-limiting action; the fuse rating must not exceed the cable current capacity.

  • RCD residual current device: 30 mA for supplementary protection of socket outlets, 100–300 mA for fire protection; test button checks the trip mechanism, not the wiring.

  • Earthing systems: TN-S separate earth, TN-C-S combined neutral and earth (PME), TT local earth electrode; TT installations require an RCD because loop impedance is high.

  • Earth fault loop impedance Zs must satisfy Zs ≤ U0/Ia, where Ia is the current that trips the device within the required disconnection time.

  • Bonding: main protective bonding connects gas, water and structural metal to the main earth terminal; supplementary bonding is used in bathrooms and special locations.

  • Discrimination: the upstream device must not trip before the downstream device; check time-current curves and use a ratio of at least 1.6 for MCBs in series.

  • IP rating: first digit solid protection 0–6, second digit water protection 0–8; bathrooms require IPX4 in zones 1 and 2, and SELV (12 V AC) for luminaires in zone 0.

Quick reference

Electrical Machines and Transformers

  • DC machine EMF: E = (p × φ × Z × N)/(60 × a), where p poles, φ flux per pole, Z conductors, N rpm, a parallel paths; a = p for lap, a = 2 for wave.

  • DC motor torque T = 0.159 × φ × I_a × Z × p/a (N·m) or T ∝ φ I_a; shunt motor speed falls slightly with load, series motor must never start unloaded.

  • Three-phase induction motor synchronous speed Ns = 120f/p; slip s = (Ns − N)/Ns; rotor frequency = s × f.

  • Starting methods for induction motors: direct-on-line, star-delta (reduces starting current and torque to one third), autotransformer, soft starter, variable frequency drive.

  • Transformer EMF equation E = 4.44 × f × N × Φ_max; turns ratio V1/V2 = N1/N2 = I2/I1 for an ideal transformer.

  • Transformer losses: copper loss I²R varies with load squared, core loss (hysteresis plus eddy current) is nearly constant; maximum efficiency occurs when copper loss equals core loss.

  • Single-phase motors: capacitor-start, capacitor-run and split-phase types rely on a phase-split auxiliary winding; shaded-pole motors are low torque and low efficiency.

  • Machine cooling and rating: insulation class limits winding temperature rise; a motor rated for 40 °C ambient must be derated above that, and frequent starts raise winding heating.

Quick reference

Electrical Control and Motor Starting

  • DOL starter circuit: main contactor with overload relay, start push button in parallel with a holding (seal-in) auxiliary contact, stop button in series with the coil.

  • Forward-reverse control uses two contactors with electrical interlock (NC contacts in each other's coil circuit) and preferably a mechanical interlock.

  • Star-delta starter sequence: main and star contactors close, then after a timer the star opens and delta closes; never allow star and delta to close together (short circuit).

  • Overload relay: thermal type uses a bimetal strip and is set to motor full-load current; magnetic type responds to high current; it protects the motor, not the operator.

  • Contactor vs relay: a contactor switches high current motor loads and has arc-suppressing contacts and a strong magnetic blowout; a relay switches control circuits.

  • Limit switches, float switches, pressure switches and thermostats are pilot devices wired in the control circuit to start, stop or reverse the motor at a set condition.

  • VFD: rectifies AC to DC, then inverts to variable frequency and voltage; it reduces starting current and gives speed control, but needs shielded cable and an EMC earth.

  • Control panel protection: short-circuit protection by fuses or MCCB, overload by thermal relay, no-volt release by the contactor coil, and emergency stop hard-wired in series.

Quick reference

Testing, Fault Finding and Maintenance

  • Continuity test: prove the instrument on a known source, isolate the circuit, measure between the ends of the conductor and record the value; expected value is under 1 Ω for a healthy protective conductor.

  • Insulation resistance test: 500 V DC for 230/400 V circuits, minimum acceptable 1 MΩ; disconnect electronics and surge devices, and test line-neutral, line-earth, neutral-earth.

  • Polarity test: verify that the line conductor is at the centre contact of the lamp holder and the switch is in the line conductor, not the neutral.

  • Earth fault loop impedance: measured at the farthest point; compare with the maximum Zs for the protective device from the manufacturer's table.

  • RCD test: use an RCD tester to confirm trip current and time; a 30 mA device should trip within 300 ms at rated residual current, and a half-rated current test should not trip.

  • Fault finding sequence: gather symptoms, form a hypothesis, test in a logical order (supply, control, load), confirm the fault, repair, then retest and record.

  • Common faults: open circuit (no continuity), short circuit (low resistance, blown fuse), earth fault (insulation failure), high resistance joint (overheating, voltage drop).

  • Maintenance schedule: thermal imaging of joints, torque checks, cleaning of vents and filters, megger tests of motors, and inspection of contacts for pitting and wear.

Quick reference

Electrical Drawing, Estimation and Documentation

  • Standard symbols: a circle with a cross is a lamp, a rectangle with a diagonal is a resistor, an arrow through a contactor coil indicates a mechanical link, and dashed lines indicate an enclosure.

  • Single-line diagram shows the distribution path with one line per circuit; a schematic shows the electrical connections and control logic in detail.

  • Wiring diagram vs schematic: a wiring diagram shows physical terminal numbers and wire colours; a schematic shows functional relationships without physical layout.

  • Estimation: take off quantities from drawings, add for wastage (typically 5–10% for cable, 3–5% for accessories), then apply labour rates and overheads.

  • Load estimation: sum connected loads with diversity factor applied, then size the main switch, cable and meter to the maximum demand.

  • Bill of quantities lists items with description, unit, quantity and rate; a schedule of rates is used for variations and extra work.

  • As-built drawings record the installed arrangement and must be updated after any modification; cable schedules list circuit number, size, type, length and protective device.

  • Documentation set for a job: drawing register, test certificates, operation and maintenance manuals, risk assessments and the handover pack.

Quick reference

Electronics and Modern Electrical Applications

  • Diode: forward biased above about 0.7 V for silicon, 0.3 V for germanium; reverse bias blocks current until the reverse breakdown voltage.

  • Rectifiers: half-wave gives V_dc = 0.318 V_peak; full-wave and bridge give V_dc = 0.636 V_peak; a smoothing capacitor reduces ripple.

  • Transistor as a switch: base current I_B must exceed I_C/h_FE for saturation; the transistor then behaves like a closed switch between collector and emitter.

  • Thyristor (SCR) latches on when the gate is pulsed and the anode is positive; it turns off only when anode current falls below the holding current.

  • LED needs a series resistor R = (V_supply − V_LED)/I_LED; a typical LED drop is 2 V and a current of 10–20 mA.

  • PLC basics: inputs from sensors, outputs to contactors and valves; ladder logic uses normally open and normally closed contacts, coils, timers and counters.

  • Sensors: PIR detects infrared movement, LDR resistance falls with light, thermistor resistance changes with temperature, proximity sensors detect metal inductively or any object capacitively.

  • Solar PV: panels give DC, an inverter converts to AC, and a charge controller regulates battery charging; a blocking diode prevents night-time reverse current.

Quick reference

Trade Practice (Practical and Viva)

  • Before working: identify the circuit, isolate, lock off, prove dead with a tested voltage indicator, and place warning notices.

  • Cable preparation: strip only the length needed, keep the sheath inside the enclosure, and ensure the earth conductor is the last to be disconnected and the first to be reconnected.

  • Terminal connection: form a neat loop clockwise around the screw so tightening pulls the wire in, use ferrules on flexible conductors, and avoid mixing dissimilar metals without a bimetallic connector.

  • Board work: keep line and neutral separated, label circuits, maintain a wiring schedule, and leave sufficient slack for re-termination.

  • Viva topics: state Ohm's law, explain why the earth is needed, describe how an RCD works, name the insulation classes, and explain star-delta starting.

  • Safe testing: use the correct category (CAT III or IV) meter, check the meter on a known live source before and after the test, and never test alone on live equipment.

  • Handover: demonstrate the installation, explain the isolation points, hand over test certificates, and record any departures from the drawing.

  • Housekeeping: clear offcuts, coil and label spare cable, remove temporary supplies, and restore covers and enclosures before energising.