Quick reference

Refrigeration Fundamentals

  • Cooling capacity: Q = m × Δh, where m is refrigerant mass flow (kg/s) and Δh is enthalpy change across the evaporator (kJ/kg); 1 TR = 3.517 kW = 12,000 Btu/h = 3024 kcal/h.

  • Carnot COP for cooling = T_L / (T_H − T_L) with absolute temperatures in kelvin; actual COP is always lower, and COP falls as the condensing temperature rises or the evaporating temperature falls.

  • Sensible heat changes dry-bulb temperature only (Q = m × c_p × ΔT); latent heat changes moisture content without changing dry-bulb temperature; total heat = sensible + latent.

  • Pressure–enthalpy diagram reading: evaporation is a horizontal line at low pressure, condensation a horizontal line at high pressure, compression a curve rising to the right, expansion a vertical line at constant enthalpy.

  • Standard vapour-compression cycle order: compression, condensation, expansion, evaporation; superheat is added after full evaporation and subcooling after full condensation.

  • Subcooling increases refrigerating effect by lowering the enthalpy entering the evaporator; superheat protects the compressor but adds no useful refrigerating effect.

  • Refrigerant glide is the temperature difference between bubble and dew points of a zeotropic blend; for blends, evaporating and condensing pressures must be read at dew point for superheat and bubble point for subcooling.

  • Absolute pressure = gauge pressure + atmospheric pressure (about 101.3 kPa or 14.7 psi); all refrigerant tables and saturation data use absolute pressure.

  • Dalton's law: total pressure of a mixture equals the sum of partial pressures, which is why air in a system raises head pressure and discharge temperature.

Quick reference

Refrigeration Systems and Components

  • The four essential components are compressor, condenser, expansion device and evaporator; a system missing any one cannot maintain a continuous refrigeration cycle.

  • Compressor types: reciprocating (positive displacement, high pressure ratio), scroll (fewer parts, quiet, common in small AC), screw and centrifugal (large capacities, centrifugal needs high evaporator pressure).

  • Thermostatic expansion valve controls superheat by balancing bulb pressure against evaporator pressure plus spring force; a starved evaporator gives high superheat, a flooded one gives low superheat.

  • Capillary tube systems are critically charged: charge quantity and tube length set the flow, so no adjustable superheat exists and any leak or overcharge seriously degrades performance.

  • Condenser types: air-cooled, water-cooled (shell-and-tube) and evaporative; heat rejected equals refrigerating effect plus compressor work, Q_cond = Q_evap + W_comp.

  • Evaporator types: flooded (filled with liquid, needs a surge drum or low-side float), direct-expansion (dry, fed by TXV) and forced-draft finned coils for air cooling.

  • Accessories: filter-drier removes moisture and particles from the liquid line, accumulator prevents liquid floodback on the suction line, oil separator returns lubricant to the compressor.

  • Liquid line sight glass shows bubbles when the charge is short or subcooling is inadequate; moisture-indicating crystals change colour when water is present.

  • Safety controls: high-pressure cut-out, low-pressure cut-out, oil-pressure switch with time delay, and motor overload/thermal protection.

Quick reference

Air Conditioning Fundamentals and Load Estimation

  • Sensible heat ratio SHR = sensible load / total load; a low SHR means high latent load, requiring lower apparatus dew point or greater dehumidification capacity.

  • Cooling coil bypass factor BF = (leaving air DB − apparatus dew point) / (entering air DB − apparatus dew point); contact factor = 1 − BF.

  • Room sensible heat equation: Q_s = 1.21 × m³/s × ΔT (kW) or 1.08 × cfm × ΔT (Btu/h); latent heat: Q_L = 3010 × m³/s × Δw (kW) or 4840 × cfm × Δgrains.

  • Psychrometric properties: dry-bulb, wet-bulb, dew point, relative humidity, humidity ratio, enthalpy and specific volume; wet-bulb equals dry-bulb only at saturation.

  • Outdoor design conditions are selected at a low exceedance percentile (commonly 0.4–1% for cooling), not at the absolute maximum recorded temperature.

  • Load components: conduction through walls, roof and glass; solar radiation through glazing; people (about 75 W sensible and 55 W latent per person at rest, more with activity); lighting; equipment; and outdoor air ventilation load.

  • Infiltration and ventilation: use air-change method or crack-length method for infiltration; ventilation air carries both sensible and latent load and is often the largest single component.

  • Diversity and safety factors: apply a modest margin (typically 5–10%) after summing loads; oversizing causes short cycling, poor dehumidification and higher energy use.

  • Latent load from people and infiltration must be met by coil dehumidification; if SHR is very high, sensible capacity dominates and humidity control may need reheat or dedicated outdoor air.

Quick reference

AC Equipment

  • Window and split units are direct-expansion, air-cooled, typically rated in tons or Btu/h; EER = capacity (Btu/h) / power input (W), and SEER is the seasonal rating.

  • Chilled water systems use a chiller (air-cooled or water-cooled), pumps, AHUs or FCUs; a water-cooled chiller with cooling tower achieves lower condensing temperature and higher efficiency than an air-cooled chiller.

  • Air handling unit sections: filter, cooling coil, heating coil, humidifier, fan and mixing box; a draw-through arrangement places the fan after the coil, a blow-through arrangement places it before.

  • Fan laws: flow varies with speed, pressure with speed squared, power with speed cubed; halving speed cuts power to one-eighth.

  • Fan total pressure = static pressure + velocity pressure; velocity pressure = 0.5 × ρ × v², and fan power = airflow × total pressure / efficiency.

  • Duct systems: equal-friction and static-regain methods size ducts; velocity limits (about 4–6 m/s in main ducts) control noise and pressure drop.

  • Air distribution devices: diffusers, grilles and registers; throw, drop and terminal velocity determine comfort, and a ceiling diffuser should be selected for the required NC (noise criteria) level.

  • Cooling tower approach = leaving water temperature − entering wet-bulb temperature; range = entering water − leaving water; approach cannot be zero and typically runs 3–5 K.

Quick reference

Installation and Commissioning

  • Refrigerant piping practice: use dry nitrogen purge while brazing to prevent oxidation, install a filter-drier, and keep suction line insulated with vapour barrier.

  • Evacuation: pull a vacuum to at least 500 microns (0.67 mbar) and hold it for 10–30 minutes; a rising vacuum indicates moisture or a leak.

  • Triple evacuation: evacuate, break with dry nitrogen, repeat three times to remove moisture and non-condensables; never use refrigerant to blow out a system.

  • Leak testing: pressure test with dry nitrogen (typically 1.5 times working pressure) then soap solution or electronic leak detector; never use oxygen or compressed air.

  • Charging: liquid charging into the liquid line for blends; vapour charging into the suction line only for pure refrigerants; weigh-in method is most accurate.

  • Superheat setting for a TXV: measure suction pressure, convert to saturation temperature, subtract from suction line temperature; typical target 5–8 K at the evaporator outlet.

  • Subcooling check: liquid line temperature subtracted from condensing saturation temperature; target commonly 5–10 K, and low subcooling with bubbles suggests undercharge.

  • Commissioning records: airflow (balancing hood), static pressures, voltages and currents, superheat, subcooling, compressor amps versus nameplate, and filter pressure drop.

  • Electrical: verify supply voltage within ±10% of nameplate, correct phase rotation on three-phase units, tight terminals and correct earthing before energising.

Quick reference

Maintenance, Troubleshooting and Safety

  • Routine maintenance: clean condenser and evaporator coils, replace or clean filters, check refrigerant charge, tighten electrical connections, lubricate bearings, and inspect drain pans and insulation.

  • High discharge pressure causes: dirty condenser, non-condensables, overcharge, high ambient or cooling-water temperature, restricted condenser water flow, or fan failure.

  • Low suction pressure causes: undercharge, restricted liquid line or filter-drier, faulty TXV, frosted or blocked evaporator, or low load; high suction pressure points to overcharge, weak compressor valves, or excessive load.

  • Liquid floodback shows as a cold, sweating suction line and low superheat; liquid slugging causes compressor noise and damage - use an accumulator or correct the charge.

  • Compressor short cycling causes: low-pressure control set too close, thermostat differential too narrow, overload trip, or control wiring fault.

  • Safety: recover refrigerant, never vent to atmosphere; use PPE (goggles, gloves), ventilate the work area, and beware of asphyxiation and frostbite from liquid refrigerant.

  • Refrigerant cylinders must be stored upright, secured, below 50 °C, and never filled above 80% liquid by volume; use a scale for charging.

  • Electrical safety: lock out and tag out before servicing, discharge capacitors, verify zero voltage with a tester, and never bypass safety controls permanently.

  • Combustion and confined spaces: test for leaks, ensure ventilation, and use a calibrated gas detector before entering a plant room or pit.