BTEB Refrigeration & AC Exam flashcards
BTEB Refrigeration & AC Exam · Build recall with a focused review session.
35 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Coefficient of Performance
- Ratio of refrigerating effect to compressor work input, COP = Q_evap / W. Higher COP means more cooling per unit of energy, and it falls as the temperature lift increases.
- Ton of Refrigeration
- Cooling rate equal to 3.517 kW, 12,000 Btu/h or 3024 kcal/h, defined as the heat needed to melt one short ton of ice in 24 hours.
- Sensible Heat
- Heat that changes the dry-bulb temperature of a substance without changing its moisture content, calculated as mass times specific heat times temperature difference.
- Latent Heat
- Heat absorbed or released during a phase change or moisture change without a dry-bulb temperature change, such as evaporation of water or condensation on a cooling coil.
- Superheat
- Difference between the actual suction line temperature and the saturation temperature at the same pressure, confirming that all liquid has boiled off before the compressor.
- Subcooling
- Difference between the condensing saturation temperature and the actual liquid line temperature, showing how far the liquid has been cooled below its condensing point.
- Absolute Pressure
- Pressure measured from a perfect vacuum, equal to gauge pressure plus atmospheric pressure of about 101.3 kPa; all refrigerant saturation tables use this value.
- Refrigerant Glide
- Temperature difference between bubble point and dew point in a zeotropic blend, which causes composition and temperature change during evaporation and condensation.
- Vapour Compression Cycle
- Continuous sequence of compression, condensation, expansion and evaporation in which a refrigerant absorbs heat at low pressure and rejects it at high pressure.
- Thermostatic Expansion Valve
- Modulating valve that maintains constant evaporator superheat by balancing bulb pressure against evaporator pressure plus an adjustable spring force.
- Capillary Tube
- Fixed restriction of small-bore tubing that meters refrigerant and equalises pressure at shutdown; performance depends critically on exact charge and tube length.
- Filter Drier
- Device in the liquid line containing a desiccant and screen that removes moisture and solid particles, protecting the expansion valve and compressor from damage.
- Suction Accumulator
- Vessel installed in the suction line that traps liquid refrigerant and oil, allowing controlled return to the compressor and preventing damaging liquid slugging.
- Flooded Evaporator
- Evaporator kept completely filled with liquid refrigerant, requiring a surge drum or low-side float and giving high heat transfer with careful liquid level control.
- Scroll Compressor
- Positive-displacement compressor using two interleaved spiral wraps, one orbiting, to compress gas continuously with few moving parts, low noise and no suction valves.
- Condenser Heat Rejection
- Total heat rejected by the condenser equals refrigerating effect plus compressor work, so the condenser load is always greater than the evaporator load.
- Sensible Heat Ratio
- Ratio of sensible load to total load; a low value indicates a large latent or moisture load that needs a lower apparatus dew point for dehumidification.
- Bypass Factor
- Fraction of air passing through a cooling coil without contacting the surface, calculated from leaving and entering dry-bulb temperatures and the apparatus dew point.
- Psychrometric Chart
- Graph plotting dry-bulb, wet-bulb, dew point, humidity ratio, relative humidity and enthalpy, used to find coil and room conditions and process lines.
- Apparatus Dew Point
- Effective coil surface temperature at which air leaving the coil would be saturated, found by extending the entering-to-leaving condition line to the saturation curve.
- Ventilation Load
- Heat and moisture introduced by outdoor air supplied for indoor air quality, calculated from airflow and the enthalpy or humidity difference between outdoor and room air.
- Solar Heat Gain
- Radiant heat entering through glazing and roof, depending on orientation, time of day, shading and glass properties, and a major component of peak cooling load.
- Energy Efficiency Ratio
- Ratio of cooling capacity in Btu/h to electrical power input in watts at rated conditions; a higher value indicates a more efficient unit.
- Air Handling Unit
- Factory or site-assembled casing containing filters, coils, fan and dampers that conditions and moves air through ductwork to the served spaces.
- Fan Laws
- Relations stating that airflow varies with speed, pressure with speed squared and power with speed cubed, used to predict performance at changed speed or size.
- Cooling Tower Approach
- Difference between the water leaving the cooling tower and the entering wet-bulb temperature; it cannot reach zero and typically ranges from three to five kelvin.
- Chilled Water System
- Arrangement in which a chiller cools water that is pumped to air handling or fan coil units, allowing central plant and refrigerant containment away from occupied spaces.
- Triple Evacuation
- Method of evacuating a system, breaking the vacuum with dry nitrogen, and repeating three times to remove moisture and non-condensable gases.
- Micron Vacuum
- Unit of vacuum equal to one thousandth of a millimetre of mercury; a standing vacuum of about 500 microns indicates an acceptable moisture-free, leak-free system.
- Weigh-In Charging
- Method of charging refrigerant by measuring the cylinder on a scale and adding the nameplate quantity, giving the most accurate charge for critically charged systems.
- Nitrogen Pressure Test
- Leak test using dry nitrogen at about one and a half times working pressure with soap solution or an electronic detector, never using oxygen or air.
- Liquid Slugging
- Condition in which liquid refrigerant reaches the compressor, causing noise, valve damage and oil dilution; prevented by correct superheat and an accumulator.
- High Discharge Pressure
- Abnormally high condensing pressure usually caused by a dirty condenser, non-condensable gases, overcharge, high ambient temperature or restricted cooling water.
- Refrigerant Recovery
- Process of removing refrigerant from a system into a recovery cylinder for reuse or disposal, required by law instead of venting to the atmosphere.
- Lockout Tagout
- Safety procedure of isolating electrical energy, applying a personal lock and tag, and verifying zero voltage before maintenance work begins.