Coefficient of Performance
Ratio of refrigerating effect to compressor work input, COP = Q_evap / W. Higher COP means more cooling per unit of energy, and it falls as the temperature lift increases.
Ton of Refrigeration
Cooling rate equal to 3.517 kW, 12,000 Btu/h or 3024 kcal/h, defined as the heat needed to melt one short ton of ice in 24 hours.
Sensible Heat
Heat that changes the dry-bulb temperature of a substance without changing its moisture content, calculated as mass times specific heat times temperature difference.
Latent Heat
Heat absorbed or released during a phase change or moisture change without a dry-bulb temperature change, such as evaporation of water or condensation on a cooling coil.
Superheat
Difference between the actual suction line temperature and the saturation temperature at the same pressure, confirming that all liquid has boiled off before the compressor.
Subcooling
Difference between the condensing saturation temperature and the actual liquid line temperature, showing how far the liquid has been cooled below its condensing point.
Absolute Pressure
Pressure measured from a perfect vacuum, equal to gauge pressure plus atmospheric pressure of about 101.3 kPa; all refrigerant saturation tables use this value.
Refrigerant Glide
Temperature difference between bubble point and dew point in a zeotropic blend, which causes composition and temperature change during evaporation and condensation.
Vapour Compression Cycle
Continuous sequence of compression, condensation, expansion and evaporation in which a refrigerant absorbs heat at low pressure and rejects it at high pressure.
Thermostatic Expansion Valve
Modulating valve that maintains constant evaporator superheat by balancing bulb pressure against evaporator pressure plus an adjustable spring force.
Capillary Tube
Fixed restriction of small-bore tubing that meters refrigerant and equalises pressure at shutdown; performance depends critically on exact charge and tube length.
Filter Drier
Device in the liquid line containing a desiccant and screen that removes moisture and solid particles, protecting the expansion valve and compressor from damage.
Suction Accumulator
Vessel installed in the suction line that traps liquid refrigerant and oil, allowing controlled return to the compressor and preventing damaging liquid slugging.
Flooded Evaporator
Evaporator kept completely filled with liquid refrigerant, requiring a surge drum or low-side float and giving high heat transfer with careful liquid level control.
Scroll Compressor
Positive-displacement compressor using two interleaved spiral wraps, one orbiting, to compress gas continuously with few moving parts, low noise and no suction valves.
Condenser Heat Rejection
Total heat rejected by the condenser equals refrigerating effect plus compressor work, so the condenser load is always greater than the evaporator load.
Sensible Heat Ratio
Ratio of sensible load to total load; a low value indicates a large latent or moisture load that needs a lower apparatus dew point for dehumidification.
Bypass Factor
Fraction of air passing through a cooling coil without contacting the surface, calculated from leaving and entering dry-bulb temperatures and the apparatus dew point.
Psychrometric Chart
Graph plotting dry-bulb, wet-bulb, dew point, humidity ratio, relative humidity and enthalpy, used to find coil and room conditions and process lines.
Apparatus Dew Point
Effective coil surface temperature at which air leaving the coil would be saturated, found by extending the entering-to-leaving condition line to the saturation curve.
Ventilation Load
Heat and moisture introduced by outdoor air supplied for indoor air quality, calculated from airflow and the enthalpy or humidity difference between outdoor and room air.
Solar Heat Gain
Radiant heat entering through glazing and roof, depending on orientation, time of day, shading and glass properties, and a major component of peak cooling load.
Energy Efficiency Ratio
Ratio of cooling capacity in Btu/h to electrical power input in watts at rated conditions; a higher value indicates a more efficient unit.
Air Handling Unit
Factory or site-assembled casing containing filters, coils, fan and dampers that conditions and moves air through ductwork to the served spaces.
Fan Laws
Relations stating that airflow varies with speed, pressure with speed squared and power with speed cubed, used to predict performance at changed speed or size.
Cooling Tower Approach
Difference between the water leaving the cooling tower and the entering wet-bulb temperature; it cannot reach zero and typically ranges from three to five kelvin.
Chilled Water System
Arrangement in which a chiller cools water that is pumped to air handling or fan coil units, allowing central plant and refrigerant containment away from occupied spaces.
Triple Evacuation
Method of evacuating a system, breaking the vacuum with dry nitrogen, and repeating three times to remove moisture and non-condensable gases.
Micron Vacuum
Unit of vacuum equal to one thousandth of a millimetre of mercury; a standing vacuum of about 500 microns indicates an acceptable moisture-free, leak-free system.
Weigh-In Charging
Method of charging refrigerant by measuring the cylinder on a scale and adding the nameplate quantity, giving the most accurate charge for critically charged systems.
Nitrogen Pressure Test
Leak test using dry nitrogen at about one and a half times working pressure with soap solution or an electronic detector, never using oxygen or air.
Liquid Slugging
Condition in which liquid refrigerant reaches the compressor, causing noise, valve damage and oil dilution; prevented by correct superheat and an accumulator.
High Discharge Pressure
Abnormally high condensing pressure usually caused by a dirty condenser, non-condensable gases, overcharge, high ambient temperature or restricted cooling water.
Refrigerant Recovery
Process of removing refrigerant from a system into a recovery cylinder for reuse or disposal, required by law instead of venting to the atmosphere.
Lockout Tagout
Safety procedure of isolating electrical energy, applying a personal lock and tag, and verifying zero voltage before maintenance work begins.