- U-factor
- The overall heat transfer coefficient of an assembly, equal to the reciprocal of its total thermal resistance R; expressed in Btu/h·ft²·°F or W/m²·K.
- Sensible heat equation
- Q = 1.08 × CFM × ΔT for air in English units, since 1.08 = 60 × 0.075 lb/ft³ × 0.24 Btu/lb·°F; the SI form is Q = 1.21 × L/s × ΔT.
- Degree-day method
- Estimates annual heating or cooling energy as UA × HDD × 24 divided by system efficiency. Accuracy depends on using a balance point near the building's actual balance temperature.
- Thermal mass effect
- Mass in the envelope or interior stores and releases heat, shifting and dampening peak loads. Effects are largest with wide daily temperature swings and night ventilation.
- COP versus EER
- COP is dimensionless cooling output divided by energy input at a rating condition. EER equals COP × 3.412 in Btu/Wh, while SEER is a seasonal rather than steady-state rating.
- Fan affinity laws
- For a fixed system, airflow varies with fan speed, pressure with speed squared, and shaft power with speed cubed, so VFD savings scale roughly with the cube of flow.
- Solar heat gain coefficient
- The fraction of incident solar radiation admitted through a fenestration, including directly transmitted solar plus absorbed solar that flows inward; lower SHGC reduces cooling loads.
- Unmet load hours
- Hours in which a zone's HVAC system cannot hold the setpoint. ASHRAE Standard 90.1 Appendix G limits the annual total to 300 hours for both baseline and proposed models.
- Thermal zone definition
- A building volume served by one HVAC control zone or sharing a single thermostat. Splitting zones more finely than the HVAC system increases run time without improving accuracy.
- Typical meteorological year
- A weather file built from 12 representative months selected from multi-year records, preserving typical rather than extreme conditions; used for annual energy, not equipment sizing.
- Fractional schedule and design level
- Hourly schedule values between 0 and 1 multiply a design level, such as W/ft² or cfm/ft², to produce the actual load in each hour of the simulated year.
- Biquadratic performance curve
- An equation fitted to manufacturer data that expresses equipment capacity or power as a function of two variables, typically entering water temperature and entering air wet-bulb temperature.
- Baseline model per Appendix G
- A budget building derived from the proposed design but with envelope, lighting, and HVAC replaced by prescriptive baseline values, simulated with identical weather and schedules.
- Economizer high-limit control
- Free cooling that allows up to 100% outdoor air when conditions permit, then disables above a dry-bulb, enthalpy, or dew-point high limit set by climate zone.
- Night setback and setup
- Unoccupied thermostat setpoints that reduce heating or cooling during off-hours. Realized savings depend on building mass, reset schedule, and system recovery time.
- CV(RMSE)
- The coefficient of variation of the root mean square error, used to judge calibration under ASHRAE Guideline 14; thresholds are 15% for monthly data and 30% for hourly data.
- Energy use intensity
- Annual site energy divided by conditioned floor area, usually reported in kBtu/ft²·yr, used to benchmark a model against CBECS or ENERGY STAR targets.
- Site versus source energy
- Site energy is measured at the building meter. Source energy adds upstream generation and delivery losses using national or regional conversion factors.
- 300 unmet load hour limit
- The Appendix G cap on hours per year when HVAC cannot meet zone setpoints. Exceeding it requires correcting the model before compliance or savings results are reported.
- PMV and PPD
- ASHRAE Standard 55 comfort indices: predicted mean vote on a −3 to +3 scale, and predicted percentage of dissatisfied. Acceptable comfort is PMV within ±0.5 and PPD ≤10%.
- Weather normalization
- Adjusting measured or modeled energy to a common climate using regression against heating and cooling degree days, so periods with different weather can be compared fairly.
- Peak demand versus annual energy
- Measures such as demand-controlled ventilation can reduce peak load while barely changing annual consumption, or the reverse; both metrics must be reported and analyzed separately.
- End-use breakdown
- Allocation of annual consumption among heating, cooling, fans, pumps, lighting, plug loads, and service hot water; used to confirm the model behaves plausibly before comparing designs.
- Life-cycle cost analysis
- Present value of capital, energy, maintenance, and replacement costs over a study period, discounted at an assumed rate; Appendix G uses a 30-year study period.
- Basis of design
- The document stating owner program, design assumptions, weather location, code version, and modeling scope; it defines what the model is required to represent.
- ASHRAE Standard 209
- A framework for simulation-aided design that defines numbered modeling cycles, from simple box through compliance, whose rigor increases as design decisions are finalized.
- Quality assurance checks
- Verification of geometry, zoning, schedules, and equipment inputs, plus mass and energy balance and comparison of EUI with benchmark ranges before results are released.
- Model version control
- Named, dated, archived copies of the input file plus a change log for every simulation run, so any reported number traces back to its exact model.
- Archiving deliverables
- Retaining input and output reports, the weather file, software name and version, and the assumptions memo so results can be reproduced years later by another modeler.
- Independent model review
- A second qualified modeler checks inputs against drawings and specifications, reruns at least one key parametric case, and signs off on assumptions before submission.
- ASHRAE Guideline 14
- Provides methods for determining measured energy savings, including calibrated simulation and whole-building metering, along with statistical thresholds for declaring a model calibrated.
- Modeling scope statement
- A written agreement listing which systems, spaces, and end uses are represented, which are excluded, and the intended use of results, preventing later disputes over expectations.