BEMP key terms
BEMP · Get comfortable with the vocabulary.
- Whole-Building Energy Simulation
- Related: Heat Balance Method, Simulation Timestep, Thermal Zone
A software-based method that predicts annual energy consumption by simultaneously solving envelope heat transfer, internal loads, and HVAC system performance for every zone at each timestep.
- Heat Balance Method
- Related: Radiant Time Series Method, Conduction Transfer Function
A rigorous load calculation technique that writes an energy balance on each interior and exterior surface and on the zone air, solving all equations simultaneously rather than sequentially.
- Radiant Time Series Method
- Related: Heat Balance Method, Thermal Mass
A simplified cooling load calculation that uses periodic response factors and radiant time factors to convert heat gains into loads, approximating heat balance results with far less computation.
- Conduction Transfer Function
- Related: Thermal Mass, Heat Balance Method
A set of coefficients relating heat flux at one face of a wall or roof to past fluxes and temperatures, capturing transient conduction without solving for internal layer temperatures.
- Thermal Mass
- Related: Conduction Transfer Function, Part-Load Performance Curve
The ability of building materials to absorb, store, and later release heat, which delays and reduces peak cooling loads and smooths indoor temperature swings.
- Thermal Zone
- Related: Whole-Building Energy Simulation, Unmet Load Hours
A space or group of spaces with a common setpoint and control, modeled by the simulation engine as a single well-mixed air volume at one temperature.
- Design Day
- Related: Autosizing, Sizing Run versus Annual Simulation
A synthetic 24-hour weather profile representing near-extreme conditions for a site, used to size equipment rather than to estimate annual energy use.
- Ideal Loads System
- Related: Zone Load versus System Load, Whole-Building Energy Simulation
A hypothetical HVAC system that supplies exactly the heating or cooling each zone requires with no efficiency or distribution losses, isolating zone loads from system effects.
- Infiltration
- Related: Outdoor Air Ventilation Rate, Schedule
Unintentional outdoor air leakage through cracks, joints, and openings in the envelope, driven by wind pressure and by indoor-outdoor temperature differences.
- Outdoor Air Ventilation Rate
- Related: Demand-Controlled Ventilation, Infiltration
The quantity of outdoor air intentionally supplied to a space for acceptable indoor air quality, usually set by code or standard based on occupancy and floor area.
- Diversity Factor
- Related: Schedule, Design Day
An assumption that connected loads or occupants are not all at full value at the same moment, so realistic peak demand is lower than the simple sum of components.
- Part-Load Performance Curve
- Related: Coefficient of Performance, Energy Use Intensity
A relationship describing how equipment capacity and efficiency change below rated capacity, essential because most equipment runs at part load for most of the year.
- Coefficient of Performance
- Related: Part-Load Performance Curve
The ratio of useful heating or cooling delivered to the energy consumed, evaluated at a specified rating condition for a chiller, heat pump, or packaged unit.
- Typical Meteorological Year Weather File
- Related: Sizing Run versus Annual Simulation, Design Day
An hourly, one-year weather dataset assembled from long-term site records to represent typical conditions, used as the driver for annual simulations.
- Simulation Timestep
- Related: Whole-Building Energy Simulation, Schedule
The interval at which the simulation solves its governing equations; shorter steps generally improve accuracy for fast-responding systems but increase run time.
- Schedule
- Related: Diversity Factor, Simulation Timestep
An hourly or sub-hourly profile defining occupancy, lighting, plug loads, or setpoints across the year, which strongly drives modeled loads and energy use.
- Autosizing
- Related: Design Day, Sizing Run versus Annual Simulation
The simulation engine's automatic calculation of equipment capacities, airflows, and water flows from design-day loads, replacing manual capacity assumptions.
- Sizing Run versus Annual Simulation
- Related: Autosizing, Typical Meteorological Year Weather File
A sizing run uses design-day conditions to fix equipment capacity, while the annual simulation applies those capacities across a full weather year to estimate energy.
- Parametric Run
- Related: Sensitivity Analysis, Version Control
A batch of simulations in which selected inputs are varied systematically, allowing results for alternative designs or control strategies to be compared directly.
- Air-Side Economizer
- Related: Demand-Controlled Ventilation, Part-Load Performance Curve
A control strategy that brings in cool outdoor air for free cooling when conditions allow, reducing or eliminating mechanical cooling energy.
- Demand-Controlled Ventilation
- Related: Outdoor Air Ventilation Rate, Air-Side Economizer
Modulating outdoor air intake in response to measured or estimated occupancy, such as carbon dioxide sensing, to avoid unnecessary fan and conditioning energy.
- Duct and Pipe Losses
- Related: Thermal Zone, Part-Load Performance Curve
Energy gained or lost by air or water distribution systems running through unconditioned space, which must be modeled to avoid overstating savings.
- Unmet Load Hours
- Related: Thermal Zone, Quality Assurance Review
The number of hours a zone drifts outside its allowed throttling range because the system cannot meet the load; a primary indicator of model and sizing quality.
- Energy Use Intensity
- Related: End-Use Breakdown, Utility Rate Structure
Annual energy consumption per unit of floor area, reported as site or source energy, used to benchmark a design against peers, targets, or code.
- End-Use Breakdown
- Related: Energy Use Intensity, Sensitivity Analysis
The allocation of total modeled energy among categories such as heating, cooling, fans, lighting, and plug loads, used to target efficiency measures.
- Calibration
- Related: Coefficient of Variation of RMSE, Mean Bias Error
Adjusting model inputs within justifiable ranges so that simulated energy use closely matches measured utility data for the same period.
- Coefficient of Variation of RMSE
- Related: Calibration, Mean Bias Error
The root-mean-square error between simulated and measured data divided by the mean measured value and expressed as a percentage; lower values mean a better fit.
- Mean Bias Error
- Related: Calibration, Coefficient of Variation of RMSE
The average difference between simulated and measured values over a period, expressed as a percentage of measured data, revealing systematic over- or under-prediction.
- Life-Cycle Cost Analysis
- Related: Utility Rate Structure, Parametric Run
Summing first cost, operating, maintenance, and replacement costs over a study period and discounting them to present value so alternatives can be compared.
- Utility Rate Structure
- Related: Life-Cycle Cost Analysis, Energy Use Intensity
The tariff that converts modeled consumption and demand into cost, including energy charges, demand charges, and time-of-use pricing periods.
- Sensitivity Analysis
- Related: Parametric Run, End-Use Breakdown
Systematically varying key inputs to see how much outputs change, revealing which assumptions dominate results and deserve the closest scrutiny.
- Scope of Work
- Related: Level of Model Detail, Simulation Documentation Report
A written agreement defining modeling objectives, deliverables, level of detail, schedule, software, and responsibilities before analysis begins.
- Level of Model Detail
- Related: Scope of Work, Thermal Zone
The chosen granularity of geometry, zoning, and system representation, matched to the purpose of the analysis and the available budget and data.
- Version Control
- Related: Simulation Documentation Report, Parametric Run
Tracking model file revisions, input changes, and software versions so that any reported result can be traced to a specific, reproducible model state.
- Quality Assurance Review
- Related: Unmet Load Hours, Simulation Documentation Report
A structured check of model inputs and outputs, covering geometry, schedules, loads, unmet hours, and energy balance, to catch errors before results are used.
- Simulation Documentation Report
- Related: Scope of Work, Version Control
A written record of modeling assumptions, input sources, software and version, and results, allowing a reviewer to understand and reproduce the analysis.
- Exceptional Calculation Method
- Related: Performance Rating Method, Quality Assurance Review
A documented alternative modeling approach approved by the rating authority when the simulation tool cannot represent a particular technology or system.
- Performance Rating Method
- Related: Exceptional Calculation Method, Simulation Documentation Report
A standardized procedure, such as the method in ASHRAE 90.1 Appendix G, prescribing how baseline and proposed models are built and compared to rate efficiency.