OBC Detection, Lighting & Power study materials
OBC Detection, Lighting & Power study resources

OBC Detection, Lighting & Power cheat sheet

OBC Detection, Lighting & Power · Keep the key ideas within reach.

Quick reference

Outboard Detection Systems: Sensors and Coverage

  • Passive infrared (PIR) sensors detect changes in infrared radiation (heat) from moving objects; they do not emit energy and are immune to radio-frequency interference but can be blinded by heat sources or sunlight.

  • Microwave motion sensors emit and receive radio waves (typically 2.4 GHz or 10.525 GHz); they can detect through non-metallic materials but may cause false alarms from moving water or fluorescent lights.

  • Dual-technology sensors require both PIR and microwave detection to trigger an alarm, reducing false alarms; the logic is AND, not OR.

  • Photoelectric beam detectors use an infrared beam between a transmitter and receiver; a break in the beam triggers an alarm; alignment is critical and fog or dirt can attenuate the beam.

  • Ultrasonic sensors use high-frequency sound waves (typically 25–40 kHz) and detect motion by Doppler shift; they are sensitive to air currents and temperature changes.

  • Coverage pattern for a PIR sensor is typically 90° or 110° horizontal and about 60° vertical; rated detection range is specified for a standard human target (70 kg, 1.7 m tall) walking at 1 m/s.

  • Detection range is reduced by high ambient temperature (approaching body temperature), by barriers, and by mounting height above the recommended maximum.

  • Glass-break detectors use acoustic sensors tuned to the frequency of breaking glass (typically 3–5 kHz) and may include a shock sensor; they should be mounted within 7.6 m (25 ft) of the protected glass.

  • Perimeter detection using active infrared beams: beam stacking (multiple beams) reduces false alarms from small animals; beam height and spacing determine the detection zone.

Quick reference

Outboard Lighting Circuits and Luminaire Types

  • Incandescent lamp efficacy is about 10–17 lumens per watt; halogen is about 15–25 lm/W; compact fluorescent (CFL) is about 50–70 lm/W; LED is about 80–150 lm/W.

  • Luminous flux (lumens) is total light output; illuminance (lux) is lumens per square meter; 1 footcandle = 10.76 lux.

  • Color temperature is measured in kelvin (K): warm white ≈ 2700–3000 K, neutral ≈ 3500–4100 K, cool white ≈ 5000–6500 K.

  • Color rendering index (CRI) ranges from 0 to 100; a CRI of 80+ is generally acceptable for indoor lighting, 90+ for critical color tasks.

  • A luminaire's ingress protection (IP) rating: first digit (0–6) for solids, second digit (0–8) for liquids; IP65 is dust-tight and protected against water jets.

  • LED drivers may be constant-current or constant-voltage; constant-current drivers specify output current (e.g., 350 mA, 700 mA) and a voltage range.

  • Dimming: forward-phase (leading-edge) dimmers are for incandescent/halogen; reverse-phase (trailing-edge) are for electronic transformers and some LEDs; 0–10 V dimming uses a low-voltage control signal.

  • Class 2 circuits for lighting are limited to 100 VA and 30 V RMS or 60 V DC; they require separation from Class 1 circuits.

  • Luminaire spacing for uniform illumination: spacing-to-mounting-height ratio (S/MH) is typically 0.8–1.5 depending on the luminaire's beam distribution.

Quick reference

Outboard Power Distribution and Circuit Protection

  • Ohm's law: V = I × R; power: P = V × I = I²R = V²/R.

  • A circuit breaker trips on overcurrent (overload or short circuit); a fuse melts; both are overcurrent protective devices (OCPDs).

  • The interrupting rating (AIC) of a circuit breaker must be equal to or greater than the available fault current at its terminals.

  • Time-current curves show trip time versus current; the curve's shape determines coordination with upstream devices.

  • Ground-fault circuit interrupter (GFCI) trips at 4–6 mA of ground-fault current within a specified time; it protects people from electric shock.

  • Arc-fault circuit interrupter (AFCI) detects signature of parallel or series arcing and trips; required by NEC for many branch circuits.

  • Voltage drop formula for single-phase: VD = 2 × K × I × L / CM, where K = 12.9 for copper, 21.2 for aluminum, I in amperes, L in feet, CM = circular mils.

  • Ampacity of conductors is affected by ambient temperature and number of current-carrying conductors in a raceway; apply correction and adjustment factors from NEC Table 310.15(B)(2)(a) and (B)(3)(a).

  • Selective coordination: the upstream OCPD should have a higher threshold and longer time delay than the downstream OCPD so that only the downstream device trips for a fault in its zone.

Quick reference

Wiring Methods, Conductors, and Terminations

  • American Wire Gauge (AWG): smaller number = larger conductor; area doubles approximately every 3 gauge steps (e.g., 10 AWG has about twice the area of 13 AWG; 12 AWG is about twice 15 AWG).

  • Ampacity examples for copper conductors at 30°C ambient, 60°C insulation: 14 AWG = 15 A, 12 AWG = 20 A, 10 AWG = 30 A; at 75°C: 14 AWG = 20 A, 12 AWG = 25 A, 10 AWG = 35 A.

  • Stranded conductors are more flexible and resistant to vibration than solid; use stranded in areas subject to movement.

  • Terminations must be made with listed connectors (wire nuts, push-in connectors, terminal blocks) and tightened to the manufacturer's specified torque.

  • Aluminum conductors require CO/ALR or AL-CU rated devices and antioxidant compound; aluminum-to-copper connections are prone to galvanic corrosion and thermal creep.

  • Conductor color code (US NEC): black/red/blue = ungrounded (hot) phases; white or gray = grounded (neutral); green, green/yellow, or bare = equipment grounding conductor.

  • Cable tray fill, conduit fill (NEC Chapter 9 Table 1): 1 conductor = 53%, 2 = 31%, 3 or more = 40% of conduit internal cross-sectional area.

  • Bend radius for non-shielded conductors: at least 8 times the overall cable diameter for fixed installations; for single conductors, 8× the conductor diameter.

  • Soldered connections are not permitted as the sole means of termination; mechanical connectors must be used.

Quick reference

Grounding, Bonding, and Electrical Safety

  • Grounding connects equipment to earth; bonding connects metallic parts together to ensure equal potential. Both are required to clear faults and protect people.

  • The equipment grounding conductor (EGC) provides a low-impedance path for fault current, allowing the overcurrent device to trip quickly.

  • Ground-fault current path impedance must be low enough that the OCPD trips within the time specified by the time-current curve; NEC 250.4(A)(5) requires effective ground-fault current path.

  • Bonding jumpers around water meters, gas piping, and structural steel ensure electrical continuity; use listed bonding clamps and conductors sized per NEC Table 250.122.

  • The minimum size of the EGC is based on the rating of the overcurrent device protecting the circuit, not on the conductor ampacity alone.

  • Ground resistance testing: fall-of-potential (three-point) method is the standard; a ground resistance of 25 ohms or less is often specified for a single electrode, otherwise a second electrode is required.

  • Touch potential is the voltage between a person's hand and feet; step potential is between two feet; both are reduced by equipotential bonding and low ground resistance.

  • Lockout/tagout (LOTO) procedures require de-energizing, testing for absence of voltage, and locking the disconnect before work; verify with a known-good tester.

  • Personal protective equipment (PPE) for electrical work is selected by incident energy analysis (arc flash study); arc-rated clothing and face protection are required for higher hazard levels.

Quick reference

Inspection, Testing, and Fault Diagnosis

  • Continuity testing: use a low-resistance ohmmeter; a reading near 0 Ω indicates a good connection; a high reading indicates corrosion or loose termination.

  • Insulation resistance testing (megohmmeter): apply 500 V DC for 600 V rated equipment; minimum acceptable value is typically 1 MΩ per kV of rated voltage plus 1 MΩ (IEEE 43).

  • Polarity test: verify that the ungrounded (hot) conductor is connected to the correct terminal; reversed polarity is a common fault.

  • Voltage drop measurement: measure voltage at the source and at the load while the load is energized; a drop greater than 3% for branch circuits or 5% overall indicates a problem.

  • Thermal imaging: use an infrared camera to detect hot spots at terminations, breakers, and conductors; compare similar phases under load.

  • Ground fault location: use a clamp-on ammeter to measure current on the grounding conductor; any significant current indicates a ground fault or leakage.

  • Short-circuit vs. overload: a short circuit causes immediate high current and trips magnetic element; an overload causes gradual heating and trips thermal element.

  • Motor circuit testing: measure winding resistance (should be balanced within 5%), insulation resistance to ground, and running current compared to nameplate FLA.

  • Documentation: record test results, compare to previous readings, and follow NFPA 70B recommended maintenance intervals for electrical equipment.