OBC Detection, Lighting & Power flashcards
OBC Detection, Lighting & Power · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- PIR sensor principle
- Passive infrared sensors detect changes in infrared radiation emitted by warm bodies moving across the field of view; they do not emit energy and are immune to radio interference but can be blinded by heat sources.
- Microwave motion sensor
- Emits and receives radio-frequency waves (e.g., 2.4 GHz) and detects motion by Doppler shift; can penetrate non-metallic materials but may false-alarm on moving water or fluorescent lights.
- Dual-technology sensor logic
- Requires both passive infrared and microwave detection to trigger an alarm (AND logic), reducing false alarms compared to either technology alone.
- Photoelectric beam detector
- Uses an infrared beam between transmitter and receiver; a break in the beam triggers an alarm; alignment is critical and fog or dirt can attenuate the beam.
- Glass-break detector
- Acoustic sensor tuned to the frequency of breaking glass (typically 3–5 kHz) and may include a shock sensor; mount within 7.6 m (25 ft) of protected glass.
- Lumens vs lux
- Luminous flux (lumens) is total light output; illuminance (lux) is lumens per square meter; 1 footcandle equals 10.76 lux.
- Lamp efficacy
- Ratio of light output to power input in lumens per watt; incandescent ≈10–17 lm/W, halogen ≈15–25, CFL ≈50–70, LED ≈80–150.
- Color temperature
- Measured in kelvin (K); warm white ≈2700–3000 K, neutral ≈3500–4100 K, cool white ≈5000–6500 K; indicates the light's apparent color.
- Color rendering index
- Scale from 0 to 100 indicating how accurately a light source renders colors compared to a reference; CRI 80+ is acceptable for indoor lighting, 90+ for critical color tasks.
- IP rating
- Ingress protection code: first digit (0–6) for solids, second digit (0–8) for liquids; IP65 means dust-tight and protected against water jets.
- LED driver types
- Constant-current drivers specify output current (e.g., 350 mA, 700 mA) and a voltage range; constant-voltage drivers provide a fixed voltage (e.g., 12 V, 24 V).
- Dimming methods
- Forward-phase (leading-edge) dimmers suit incandescent/halogen; reverse-phase (trailing-edge) suit electronic transformers and some LEDs; 0–10 V dimming uses a low-voltage control signal.
- Ohm's law and power
- V = I × R; P = V × I = I²R = V²/R; these formulas relate voltage, current, resistance, and power in DC and resistive AC circuits.
- Circuit breaker interrupting rating
- The maximum fault current a breaker can safely interrupt; it must be equal to or greater than the available fault current at its terminals.
- GFCI trip threshold
- Ground-fault circuit interrupter trips at 4–6 mA of ground-fault current within a specified time, protecting people from electric shock.
- Voltage drop formula
- Single-phase: VD = 2 × K × I × L / CM, where K = 12.9 for copper, 21.2 for aluminum; I in amperes, L in feet, CM = circular mils.
- Selective coordination
- Upstream overcurrent protective device has a higher threshold and longer time delay than the downstream device so that only the downstream device trips for a fault in its zone.
- AWG sizing rule
- Smaller AWG number means larger conductor; area doubles approximately every 3 gauge steps (e.g., 10 AWG has about twice the area of 13 AWG).
- Copper ampacity examples
- At 30°C ambient, 60°C insulation: 14 AWG = 15 A, 12 AWG = 20 A, 10 AWG = 30 A; at 75°C: 14 AWG = 20 A, 12 AWG = 25 A, 10 AWG = 35 A.
- Aluminum conductor termination
- Requires CO/ALR or AL-CU rated devices and antioxidant compound; aluminum-to-copper connections are prone to galvanic corrosion and thermal creep.
- Conductor color code
- US NEC: black/red/blue = ungrounded (hot) phases; white or gray = grounded (neutral); green, green/yellow, or bare = equipment grounding conductor.
- Conduit fill percentages
- NEC Chapter 9 Table 1: 1 conductor = 53%, 2 conductors = 31%, 3 or more = 40% of conduit internal cross-sectional area.
- Grounding vs bonding
- Grounding connects equipment to earth; bonding connects metallic parts together to ensure equal potential; both are required to clear faults and protect people.
- Equipment grounding conductor
- Provides a low-impedance path for fault current, allowing the overcurrent device to trip quickly; its minimum size is based on the OCPD rating per NEC Table 250.122.
- Ground resistance testing
- Fall-of-potential (three-point) method is standard; a ground resistance of 25 ohms or less is often specified for a single electrode, otherwise a second electrode is required.
- Touch and step potential
- Touch potential is voltage between a person's hand and feet; step potential is between two feet; both are reduced by equipotential bonding and low ground resistance.
- Lockout/tagout
- Procedure requiring de-energizing, testing for absence of voltage, and locking the disconnect before work; verify with a known-good tester.
- Insulation resistance testing
- Apply 500 V DC for 600 V rated equipment; minimum acceptable value is typically 1 MΩ per kV of rated voltage plus 1 MΩ (IEEE 43).
- Voltage drop measurement
- Measure voltage at source and at load while energized; a drop greater than 3% for branch circuits or 5% overall indicates a problem.
- Thermal imaging inspection
- Use an infrared camera to detect hot spots at terminations, breakers, and conductors; compare similar phases under load to identify anomalies.
- Short circuit vs overload
- A short circuit causes immediate high current and trips the magnetic element; an overload causes gradual heating and trips the thermal element.
- Motor circuit testing
- Measure winding resistance (should be balanced within 5%), insulation resistance to ground, and running current compared to nameplate FLA.