Power Eng 5th Class study materials
Power Eng 5th Class study resources

Power Eng 5th Class flashcards

Power Eng 5th Class · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

MAWP
Maximum allowable working pressure: the highest pressure at which a boiler or pressure vessel may operate under design conditions, based on wall thickness, material strength, and joint efficiency.
Boiler horsepower
A measure of boiler capacity equal to 33,475 BTU/h, equivalent to evaporating 34.5 lb of water per hour at 212°F and atmospheric pressure.
Joint efficiency
A factor (E) applied in pressure vessel design to account for the strength of welded seams relative to seamless plate; ranges from 0.6 to 1.0 depending on radiography.
Hydrostatic test
A pressure test using water to verify vessel integrity, typically at 1.5 times MAWP for new boilers; water is used because it stores little energy if rupture occurs.
Safety valve
A spring-loaded pressure relief device that opens automatically at set pressure to discharge steam and protect the boiler from overpressure; must be set at or below MAWP.
Stoichiometric combustion
The ideal air-fuel ratio where all fuel is burned with exactly the theoretical amount of oxygen, producing only CO2, H2O, and N2; excess air is added in practice.
Pre-purge
A forced-air period before ignition that removes combustible gases from the furnace and breeching, typically at least five air changes or 30–60 seconds.
Flame failure response
The safety action that shuts off fuel within a specified time (often 4 seconds for main flame) when the flame scanner loses the flame signal.
Low-water cutoff
A safety device that trips the burner when boiler water level falls below a safe point, preventing overheating and explosion; must be tested regularly.
Swell and shrink
Transient false level readings caused by steam bubble expansion (swell) on load increase or contraction (shrink) on load decrease, affecting drum level indication.
Excess air
Air supplied beyond the theoretical stoichiometric amount, typically 5–15% for gas and 10–20% for oil, to ensure complete combustion and reduce CO and smoke.
Balanced draft
A boiler arrangement where forced draft and induced draft fans maintain a slight negative pressure (about −0.05 to −0.1 in. w.c.) at the furnace outlet.
Boiler explosion
A catastrophic failure releasing stored energy from pressurized hot water flashing to steam, often caused by low water, overpressure, or scale-induced overheating.
Lockout/tagout
A safety procedure isolating all energy sources (fuel, steam, electrical, pneumatic) with locks and tags to prevent accidental startup during maintenance.
Confined space entry
Entry into a boiler or vessel requiring atmospheric testing (O2 19.5–23.5%, LEL <10%), a permit, an attendant, and a rescue plan.
Emergency shutdown
A procedure that trips fuel, closes the main fuel valve, keeps the forced draft fan running to purge unburned gases, then stops the fan.
Jurisdictional inspection
A legally required examination of a boiler by an authorized inspector, typically annual internal and periodic external, with a certificate posted in the boiler room.
Centrifugal pump affinity laws
Relationships stating flow varies with speed, head with speed squared, and power with speed cubed; also apply to impeller diameter changes.
NPSH
Net positive suction head: the margin between absolute suction pressure and vapor pressure, available at the pump inlet; must exceed the pump's required NPSH to avoid cavitation.
Cavitation
Formation and collapse of vapor bubbles in a pump due to low suction pressure, causing noise, vibration, and impeller pitting; prevented by increasing NPSH available.
Deaerator
A vessel that heats feedwater to saturation and vents dissolved oxygen and carbon dioxide, typically operating at 5–15 psig and 227–250°F.
Positive displacement pump
A pump that moves a fixed volume of fluid per cycle (gear, piston, diaphragm), delivering constant flow regardless of pressure and requiring a discharge relief valve.
Fan laws
Relationships for fans: airflow varies with speed, static pressure with speed squared, and horsepower with speed cubed.
Scale
Deposits of calcium and magnesium salts on boiler surfaces that reduce heat transfer, cause overheating, and are measured as hardness in ppm or grains per gallon.
Softener regeneration
The process of restoring a water softener resin by passing brine (NaCl) through it, exchanging sodium ions for accumulated calcium and magnesium ions.
Oxygen scavenger
A chemical such as sodium sulfite or hydrazine added to boiler water to remove residual dissolved oxygen and prevent pitting corrosion.
Blowdown
The removal of boiler water to control dissolved solids and sludge; continuous surface blowdown controls conductivity, while bottom blowdown removes sludge.
Caustic embrittlement
A cracking failure of boiler metal caused by high caustic alkalinity concentrating in seams and crevices, mitigated by pH and alkalinity control.
4–20 mA loop
An analog instrumentation standard where 4 mA represents zero and 20 mA full scale; the live zero allows detection of broken wires.
PID control
A control algorithm using proportional (gain), integral (reset), and derivative (rate) actions to minimize error and stabilize a process such as boiler steam pressure.
Thermocouple
A temperature sensor made of two dissimilar metals that generates a voltage proportional to temperature difference; common types are J, K, and T.
Refrigeration cycle
A sequence where refrigerant is compressed, condensed (rejecting heat), expanded (dropping pressure), and evaporated (absorbing heat) to provide cooling.