Red Seal Powerline Technician · Get comfortable with the vocabulary.

Approach distance

The minimum distance a worker or conductive object must stay from exposed energized parts, set by system voltage and whether the work is categorized as live-line or de-energized.

Related: Minimum approach distance, Limits of approach
Minimum approach distance (MAD)

The calculated safe working distance from energized conductors that accounts for voltage, switching surges, and inadvertent movement, used to set barricades and rubber glove boundaries.

Related: Approach distance, Rubber glove work
Limits of approach

Boundary zones around exposed energized equipment that restrict access by unqualified persons and define where qualified workers need shock protection measures.

Related: Approach distance, Arc flash boundary
Arc flash boundary

The distance from an arc source at which incident energy equals the threshold for a second-degree burn, used to select personal protective equipment and barricade placement.

Related: Incident energy, Limits of approach
Incident energy

The amount of thermal energy reaching a surface during an arcing fault, usually expressed in calories per square centimetre and used to choose arc-rated clothing.

Related: Arc flash boundary, Arc-rated clothing
Step potential

A voltage difference between two points on the ground a stride apart, caused by fault current spreading through earth, which can drive current through a person's legs.

Related: Touch potential, Equipotential grounding
Touch potential

A voltage difference between an energized object a person touches and the ground under their feet, a hazard at grounded structures during fault conditions.

Related: Step potential, Equipotential grounding
Equipotential grounding

Bonding all conductive parts and the worker's position to the same potential so no hazardous voltage difference can develop across the body during work.

Related: Protective ground, Step potential
Protective ground

A temporary ground set applied to de-energized conductors at the work site to drain induced or accidental voltage and to trip the circuit if it is re-energized.

Related: Equipotential grounding, Visible break
Visible break

A clearly observable open point in a circuit, such as an open disconnect or removed jumper, that confirms isolation before protective grounds are applied.

Related: Protective ground, Switching order
Switching order

A written or verbal sequence listing each device to be operated, its required position, and the confirming checks, used to prevent incorrect operations on the system.

Related: Tagout, Visible break
Tagout

Placing a durable warning tag on a lock or device to identify who is working and why the equipment must not be operated until the tag is removed by its owner.

Related: Switching order, Visible break
Recloser

A self-controlled switch that opens and recloses a circuit a set number of times to clear temporary faults before locking out on a permanent fault.

Related: Fuse saving, Lockout
Fuse saving

A coordination scheme in which a recloser trips quickly before a downstream fuse operates, allowing temporary faults to clear without blowing the fuse.

Related: Recloser, Sectionalizer
Sectionalizer

A fault-counting switch that opens during a recloser's open interval after sensing a set number of fault currents, isolating only the faulted section of line.

Related: Recloser, Fuse saving
Lockout

The condition in which a protective device has operated and will not reclose automatically, or the act of securing equipment so it cannot be energized.

Related: Recloser, Tagout
Voltage regulator

An autotransformer with tap-changing controls installed on a feeder to hold voltage within limits as load varies along the line.

Related: Tap changer, Voltage drop
Tap changer

A mechanism that selects different winding taps on a transformer or regulator to adjust the turns ratio and therefore the output voltage.

Related: Voltage regulator, Turns ratio
Turns ratio

The ratio of primary to secondary winding turns in a transformer, which determines the relationship between primary and secondary voltages.

Related: Tap changer, Wye connection
Wye connection

A three-phase transformer connection in which one end of each winding joins at a neutral point, giving a line-to-neutral voltage equal to line voltage divided by root three.

Related: Delta connection, Turns ratio
Delta connection

A three-phase connection in which windings form a closed loop, so line voltage equals winding voltage and no neutral point exists unless one is derived.

Related: Wye connection, Open delta
Open delta

A three-phase bank using only two transformers, providing reduced capacity and a usable three-phase supply when one unit of a full bank is unavailable.

Related: Delta connection, Bank paralleling
Bank paralleling

Connecting two transformer banks so they share load, which requires matching voltage, polarity, phase sequence, and impedance characteristics.

Related: Polarity, Open delta
Polarity

The relative instantaneous direction of induced voltages in transformer windings, marked by bushings, and critical for correct paralleling and bank connections.

Related: Bank paralleling, Turns ratio
Voltage drop

The reduction in voltage along a conductor caused by current flowing through its impedance, increasing with load, distance, and smaller conductor size.

Related: Voltage regulator, Ampacity
Ampacity

The maximum current a conductor can carry continuously without exceeding its temperature rating, affected by material, size, ambient temperature, and cooling conditions.

Related: Voltage drop, Conductor sag
Conductor sag

The downward curve of a suspended conductor between supports, set by tension, span length, weight, and temperature, and controlling ground clearance.

Related: Span, Ampacity
Span

The horizontal distance between two adjacent supporting structures on an overhead line, a key factor in sag, tension, and wind and ice loading.

Related: Conductor sag, Guy
Guy

A tensioned cable anchored to the ground or a structure that opposes unbalanced conductor pull and keeps a pole or crossarm in position.

Related: Span, Anchor
Anchor

A buried or driven device that transfers guy or structure loads into the earth, sized according to soil conditions and the applied pull.

Related: Guy, Load chart
Load chart

A manufacturer's table giving the rated capacity of a crane, digger derrick, or aerial device at each boom angle, radius, and configuration.

Related: Anchor, Dielectric test
Dielectric test

A periodic electrical test of insulating buckets, booms, blankets, and gloves that verifies they still withstand working voltage before being returned to service.

Related: Rubber glove work, Load chart
Rubber glove work

Live-line work in which a qualified worker wearing tested insulating gloves and sleeves contacts energized conductors directly within the minimum approach distance.

Related: Minimum approach distance (MAD), Dielectric test
Hot stick

An insulated tool with a tested dielectric rating used to manipulate energized conductors, ties, and switches from outside the minimum approach distance.

Related: Rubber glove work, Live-line tool
Live-line tool

Any insulated implement, such as a shotgun stick or wire tong, designed and maintained for contact with energized conductors at a stated voltage rating.

Related: Hot stick, Dielectric test
Fault indicator

A device on an overhead or underground circuit that senses fault current or voltage loss and displays a flag or signal to narrow the search area.

Related: Thumper, Sectionalizer
Thumper

A surge generator used on underground cable to apply high-voltage pulses that break down insulation at a fault and create an audible thump for locating it.

Related: Fault indicator, Time-domain reflectometer
Time-domain reflectometer (TDR)

An instrument that sends a pulse down a cable and times its reflection to measure distance to an open, short, or splice, aiding fault location.

Related: Thumper, Fault indicator
Pad-mounted transformer

A tamper-resistant transformer enclosure installed on a concrete pad at grade, serving underground residential distribution and requiring lock and barrier controls.

Related: Cable pulling tension, Termination
Cable pulling tension

The longitudinal force applied to a cable during installation, limited by the cable's rating to prevent conductor stretch or insulation damage.

Related: Pad-mounted transformer, Termination
Termination

The fitting and stress-control assembly that adapts an underground cable end for connection to equipment while managing the electric field.

Related: Cable pulling tension, Pad-mounted transformer
Ground gradient

The change in voltage per unit distance across the earth's surface near a grounded structure, which determines step and touch potential severity.

Related: Step potential, Equipotential grounding