Registered Electrical Engineer (G&T) key terms
Registered Electrical Engineer (G&T) · Get comfortable with the vocabulary.
- per-unit system
- Related: symmetrical components, short-circuit MVA
A method of expressing voltages, currents, impedances and powers as fractions of chosen base values, so transformers and machines of different ratings can be combined in one network calculation without ratio conversions.
- symmetrical components
- Related: per-unit system, zero-sequence impedance
A technique that resolves an unbalanced three-phase set of phasors into positive-, negative- and zero-sequence balanced sets, allowing unbalanced faults and load flows to be solved with per-phase impedance networks.
- zero-sequence impedance
- Related: symmetrical components, neutral earthing
The impedance offered to the zero-sequence component of current, which depends strongly on transformer winding connections and grounding, and which governs earth-fault current magnitude.
- short-circuit MVA
- Related: per-unit system, prospective fault current
The apparent power that a source or network can deliver into a bolted three-phase fault, calculated as fault current times prefault voltage times root three; used to size switchgear and compare source strength.
- prospective fault current
- Related: breaking capacity, short-circuit MVA
The current that would flow at a point in an installation if a short circuit of negligible impedance occurred there, including contributions from all parallel paths and rotating machines as required by the standard.
- breaking capacity
- Related: prospective fault current, protective device discrimination
The maximum prospective fault current a switching device can safely interrupt at a stated voltage without damage or danger, distinguishing it from making capacity and short-time withstand ratings.
- protective device discrimination
- Related: breaking capacity, earth-fault loop impedance
Coordination of protective devices so that the device nearest a fault operates first, limiting supply interruption to the smallest healthy section of the network.
- earth-fault loop impedance
- Related: neutral earthing, residual current device
The total impedance of the path taken by fault current from the point of fault back to the source through the protective earth conductor and the earthed neutral, used to verify automatic disconnection of supply.
- neutral earthing
- Related: zero-sequence impedance, earth-fault loop impedance
Deliberate connection of a system neutral to earth, either solidly, through resistance or reactance, or via a transformer, which fixes the earth-fault current level and insulation duty.
- residual current device
- Related: earth-fault loop impedance, equipotential bonding
A device that compares currents in live conductors and trips when their vector sum indicates earth leakage above a set threshold, giving protection additional to overcurrent devices.
- equipotential bonding
- Related: residual current device, step and touch voltage
Intentional electrical connection of exposed conductive parts and extraneous conductive parts to keep them at substantially the same potential, reducing touch voltage during faults.
- step and touch voltage
- Related: equipotential bonding, grid resistance
Potential differences appearing across a person's feet, or between hand and feet, near an earthed structure carrying fault current; substation earthing design must keep both within tolerable limits.
- grid resistance
- Related: step and touch voltage, neutral earthing
The resistance between a substation earthing grid and remote earth, measured by fall-of-potential or similar methods, determining how much the grid potential rises during an earth fault.
- transmission line surge impedance
- Related: surge impedance loading, travelling wave
The ratio of voltage to current for a wave travelling along a lossless line, equal to the square root of inductance per unit length divided by capacitance per unit length, typically 250 to 400 ohms for overhead lines.
- surge impedance loading
- Related: transmission line surge impedance, Ferranti effect
The power a lossless line delivers when its receiving-end load equals its surge impedance, a convenient reference for comparing line loading and reactive power behaviour.
- Ferranti effect
- Related: surge impedance loading, shunt reactor
Rise of receiving-end voltage above sending-end voltage on a lightly loaded or open-circuited line, caused by the line's shunt capacitance charging current flowing through its series inductance.
- shunt reactor
- Related: Ferranti effect, static var compensator
An inductive device connected from line or bus to earth to absorb capacitive reactive power, controlling voltage rise on long lightly loaded cables and lines and limiting switching overvoltages.
- static var compensator
- Related: shunt reactor, power system stability
A thyristor-controlled shunt device that continuously adjusts reactive power injection or absorption to regulate voltage and damp power oscillations on transmission networks.
- power system stability
- Related: critical clearing time, equal area criterion
The ability of synchronous machines in an interconnected system to remain in synchronism after a disturbance, classified by rotor-angle, frequency and voltage stability phenomena.
- critical clearing time
- Related: power system stability, equal area criterion
The longest fault clearing time for which a generator or system remains transiently stable after a disturbance, a key output of transient stability studies used to set protection speeds.
- equal area criterion
- Related: critical clearing time, power system stability
A graphical method for judging transient stability of a single machine against an infinite bus by comparing accelerating and decelerating areas on the power-angle curve.
- load flow study
- Related: per-unit system, economic dispatch
Numerical solution for steady-state bus voltages, line flows and losses in a network given generation, load and one slack bus, usually by Newton-Raphson or Gauss-Seidel iteration.
- economic dispatch
- Related: load flow study, spinning reserve
Allocation of real power output among committed generating units to meet demand at least cost, conventionally by equal incremental fuel cost subject to losses and limits.
- spinning reserve
- Related: economic dispatch, load frequency control
Unloaded generation capacity that is already synchronised and can pick up load within minutes, required to cover sudden loss of a unit or load forecast error.
- load frequency control
- Related: spinning reserve, droop characteristic
Automatic adjustment of generator setpoints in response to frequency deviation and tie-line power error, restoring balance between system generation and demand.
- droop characteristic
- Related: load frequency control, synchronising
The steady-state relationship between frequency and generator output, expressed as percent speed change for full load change, which determines how load is shared between parallel machines.
- synchronising
- Related: droop characteristic, power transformer vector group
The process of matching voltage magnitude, frequency, phase angle and phase sequence before closing a generator or tie breaker onto an energised bus to avoid damaging currents.
- power transformer vector group
- Related: synchronising, zero-sequence impedance
A designation of transformer winding connections and phase displacement between high- and low-voltage windings, which must be matched for parallel operation and affects earth-fault behaviour.
- current transformer saturation
- Related: differential protection, burden
The condition in which a current transformer core cannot maintain flux proportional to primary current, distorting secondary current and potentially causing protection maloperation or refusal.
- differential protection
- Related: current transformer saturation, distance protection
A scheme that trips when the vector difference between currents entering and leaving a protected zone exceeds a threshold, providing fast unit protection for transformers, generators and busbars.
- distance protection
- Related: differential protection, protective device discrimination
Line protection that measures the impedance from the relay location to a fault and trips within set reach zones, giving fast clearing for in-zone faults and time-graded backup beyond.
- travelling wave
- Related: transmission line surge impedance, surge arrester
A voltage and current disturbance propagating along a line at near light speed, reflected at discontinuities, which explains lightning and switching overvoltage behaviour and relay fault location methods.
- surge arrester
- Related: travelling wave, basic impulse level
A protective device that becomes conducting above a specified voltage and diverts surge energy to earth, then reseals, limiting overvoltage on equipment insulation.
- basic impulse level
- Related: surge arrester, insulation coordination
The standard lightning impulse withstand voltage a piece of equipment insulation is designed to tolerate, used to coordinate insulation strength with protective device levels.
- insulation coordination
- Related: basic impulse level, surge arrester
Selection of insulation withstand strengths and protective device characteristics so that protective levels lie below equipment withstand levels with adequate margin across the system.
- code of ethics
- Related: conflict of interest, seal and signature
The written standards of conduct binding a licensed engineer, covering competence, honesty in reports, avoidance of conflicts of interest, confidentiality and duty to public safety.
- conflict of interest
- Related: code of ethics, seal and signature
A situation where an engineer's personal, financial or other interest could improperly influence professional judgement; it must be disclosed and avoided or managed.
- seal and signature
- Related: code of ethics, professional negligence
The licensed engineer's formal authentication of drawings and documents, accepting professional responsibility for their technical content and compliance with regulations.
- professional negligence
- Related: seal and signature, code of ethics
Failure to exercise the degree of care and skill ordinarily expected of a competent engineer in similar circumstances, giving rise to liability for resulting loss.
- variation order
- Related: critical path method, earned value management
A documented instruction changing the scope, schedule or price of contracted works, issued under the contract's variation clause and forming part of the agreed record.
- critical path method
- Related: variation order, earned value management
Schedule technique identifying the longest chain of dependent activities, whose delay directly delays project completion and which therefore receives the tightest management attention.
- earned value management
- Related: critical path method, variation order
Project control method comparing budgeted cost of work performed against actual cost and planned value to forecast cost and schedule performance objectively.