Mistake 1

Treating the design outdoor dry-bulb and wet-bulb temperatures as the same value, or using the extreme annual maximum rather than the statistical design condition when selecting chillers, cooling towers and air handlers.

Candidates memorize a single 'design temperature' for a city and forget that the cooling design condition is a coincident dry-bulb/wet-bulb pair chosen at a statistical exceedance level, while the heating design condition is a separate low dry-bulb value. The wet-bulb drives the tower and coil selection, so substituting the dry-bulb inflates or deflates capacity.

What to do instead

For every load problem, write down both the summer design dry-bulb and wet-bulb and the winter design dry-bulb before touching equipment. State the exceedance basis you are using, keep the two seasons' values in separate columns, and check that the wet-bulb you use for tower sizing is the summer coincident value, not the winter one.

Mistake 2

Computing envelope transmission loads with the steady-state U·A·ΔT formula for walls and roofs that have significant thermal mass, ignoring the decrement factor and time lag, and then summing all peak loads as if they occurred at the same hour.

The steady-state formula is the first one taught and is easy to apply, so candidates default to it. Thermal mass shifts and attenuates the peak, and solar gains through glass peak at a different hour from conduction through walls, so simple summation overstates the block load and can lead to oversizing.

What to do instead

Use the sol-air temperature or equivalent temperature difference method (or a transfer-function/radiant-time-series approach) for massive envelope elements, apply the correct decrement factor and time lag, and build an hour-by-hour or at least peak-shifted summation table. Report the block load at the coincident hour, not the arithmetic sum of individual peaks.

Mistake 3

Sizing expansion tanks, safety valves and circulation pumps using only the nominal design flow temperature, without accounting for the hydrostatic head, the actual system water volume, and the lowest pressure point in the circuit.

Candidates plug numbers into the expansion-tank formula but take the fill pressure as a guess and forget that the pump's suction side is the critical point for cavitation and for keeping the system above atmospheric pressure at the highest point. The result passes arithmetic but fails at the top of the building.

What to do instead

Establish the static height from the lowest pump suction to the highest point, set the minimum fill pressure to keep at least the required margin above saturation at the maximum water temperature, compute the expansion volume from the actual pipe and equipment water content, and verify the pump NPSH margin and the safety-valve set pressure against the weakest component rating. Show each of these checks explicitly.

Mistake 4

Selecting a boiler or heat exchanger on the basis of gross calorific value efficiency while the load calculation and fuel billing assume net calorific value, or mixing the two bases in one calculation.

Chinese and European practice often quotes efficiency on the lower heating value (net calorific value), while some manufacturers and fuel data quote the higher heating value (gross). Candidates pick whichever number is printed and never reconcile the basis, producing a boiler capacity that is off by several percent.

What to do instead

Declare the calorific basis at the top of every combustion and boiler calculation. Convert one basis to the other using the latent heat of the fuel's water vapour before comparing, and confirm that the boiler's rated efficiency, the fuel consumption and the flue-loss calculation all sit on the same basis.

Mistake 5

Designing a kitchen, garage or laboratory exhaust without balancing the make-up air, so the space is held at a large negative pressure and the specified exhaust flow cannot actually be achieved.

Candidates size the exhaust hood or fan from the capture-velocity or air-change criterion and stop there, treating make-up air as someone else's problem. In a tight envelope the fan curve shifts to a lower flow and the hood fails to capture contaminants.

What to do instead

For every exhaust system, compute the make-up air path and quantity, specify transfer grilles or dedicated make-up air units with the pressure drop included, and check the space pressure relative to adjacent spaces. Add the make-up air fan to the fan-energy and pressure-balance schedule so the exhaust and supply are designed as one system.

Mistake 6

Treating a pressurized stairwell or smoke-control system as a simple constant-flow fan selection, without checking the door-open condition, the leakage area, or the pressure differential across the door against the maximum allowable opening force.

Candidates compute the pressurization flow for the closed-door leakage case because it is the smaller, simpler number, and never verify that the system still holds the required pressure with doors open or that the door force stays within the limit. The system then fails either the containment test or the accessibility requirement.

What to do instead

Design for both the closed-door and the specified door-open condition, state the assumed leakage areas for walls, doors and windows, and check the pressure differential at the design doors against both the minimum containment value and the maximum door-opening force. Include the relief damper or variable-speed control that reconciles the two cases.

Mistake 7

Selecting a cooling coil or air-handling unit on the basis of sensible capacity alone, or ignoring the entering air wet-bulb and the bypass factor when checking whether the apparatus dew point can actually be reached.

Candidates read the total capacity from a catalogue at rating conditions and never verify that the coil can handle the actual entering wet-bulb, the latent load, and the required supply air temperature simultaneously. The unit meets the sensible load but cannot dehumidify.

What to do instead

Plot the coil process on a psychrometric chart: entering and leaving dry-bulb and wet-bulb, apparatus dew point, bypass factor and sensible heat ratio. Confirm the coil's rated conditions bracket the design entering wet-bulb, and check the supply air temperature against the apparatus dew point so latent capacity is adequate, not just sensible.

Mistake 8

Assigning fan and pump energy by nameplate power rather than by the actual operating point on the system curve, and ignoring part-load behaviour and the affinity laws when evaluating VFD savings.

Candidates multiply rated power by assumed hours, which overstates energy at part load and understates the benefit of variable-speed control. The system curve shifts with damper and valve position, so the operating point is not the design point.

What to do instead

Determine the actual operating point from the intersection of the fan or pump curve with the system curve, apply the affinity laws for the variable-speed case, and build a part-load profile weighted by operating hours. Report both the design-point power and the annual energy with the control strategy stated.

Mistake 9

Writing control sequences as vague prose such as 'modulate to maintain temperature' without specifying the sensor location, setpoint, proportional band, reset schedule, fail-safe position and interlock logic.

Candidates focus on equipment selection and treat the control narrative as boilerplate. A sequence that lacks the measured variable, the manipulated variable and the failure mode cannot be commissioned or checked, and the answer loses marks even when the equipment is right.

What to do instead

Write each sequence in a fixed format: controlled variable and sensor location, setpoint and deadband, output signal and final control element, reset or scheduling logic, interlocks and permissives, and the fail-safe position on power or signal loss. State the sequence for each mode (occupied, unoccupied, warm-up, alarm) explicitly.

Mistake 10

Answering a professional-practice or ethics scenario by citing only the technical code requirement, without identifying the responsible party, the reporting obligation, or the conflict-of-interest issue the scenario is testing.

Candidates treat the exam as purely technical and read scenario questions as code-recall items. The scenario usually hinges on a duty to the public, a signature or seal question, or a disclosure obligation, and a code citation alone does not answer it.

What to do instead

For every scenario, name the parties, the duty owed and to whom, the specific action required (report, refuse to certify, disclose, escalate), and the record to be kept. Where a code clause applies, cite it as supporting the duty rather than as the whole answer, and state the consequence of not acting.