- Sol-air temperature
- An equivalent outdoor air temperature combining real air temperature and absorbed solar radiation, used to compute wall and roof heat gain with a single conduction equation.
- Sensible heat ratio
- The ratio of sensible cooling load to total cooling load. It determines whether the coil can hold room humidity and sets the required apparatus dew point.
- Apparatus dew point
- The coil surface temperature at which the air process line intersects saturation. It sets the coil leaving-air condition and the bypass factor.
- Design outdoor heating temperature
- The winter dry-bulb value with 50 percent cumulative frequency, not the extreme minimum. It balances installed capacity against hours of unmet load.
- Reverse-return piping
- A two-pipe layout where supply and return paths are equal length for every terminal, so flows stay near design without balancing valves on near terminals.
- Condensing boiler efficiency
- Efficiency above 95 percent on higher heating value is possible only when return water is below the flue-gas dew point, recovering latent heat from water vapor.
- Stairwell pressurization
- A smoke control method maintaining 25 to 30 pascals in the stairwell with doors closed, keeping smoke out of the egress path during evacuation.
- Capture velocity
- The air velocity at the contaminant source needed to draw emissions into an exhaust hood. Values depend on hood type and contaminant toxicity.
- Make-up air ratio
- The fraction of smoke exhaust volume supplied as replacement air, typically 50 percent for natural and 80 percent for mechanical supply.
- Equivalent duct diameter
- For a rectangular duct of sides a and b, the equal-friction equivalent diameter is 2ab divided by a plus b, used with friction charts.
- Chiller COP
- The ratio of refrigerating effect to compressor work. Real chillers reach 40 to 60 percent of the Carnot COP for the same evaporating and condensing temperatures.
- Bypass factor
- The fraction of air passing a coil without contacting the surface, computed from inlet, outlet and apparatus dew point temperatures. Fewer rows reduce it.
- Fan laws
- For a fixed fan, flow varies with speed, pressure with speed squared, and power with speed cubed. They justify variable-speed drives for part-load savings.
- Low delta-T syndrome
- A chilled-water temperature difference well below design, often under 3 kelvin, caused by coil or valve faults, forcing higher pump flow and energy.
- IPLV
- Integrated part-load value, a weighted efficiency metric combining chiller performance at 100, 75, 50 and 25 percent load. It reflects seasonal operation.
- Window-to-wall ratio
- The glazed area divided by gross facade area. Codes cap it by climate zone and orientation to limit solar gain and envelope heat loss.
- Economizer free cooling
- A control strategy using outdoor air for cooling when its temperature or enthalpy is below return air, reducing chiller operation in transitional seasons.
- Heat recovery effectiveness
- The ratio of actual heat transferred to the maximum possible between exhaust and supply air. Sensible cores reach 50 to 70 percent, enthalpy wheels 60 to 80.
- Specific fan power
- Fan electrical input power divided by airflow, expressed in watts per cubic meter per hour. Codes set maximum values to limit fan energy.
- Control valve authority
- The valve pressure drop divided by the total circuit pressure drop. Values of at least 0.3 to 0.5 give stable modulating control.
- Static pressure reset
- A control strategy lowering duct static pressure setpoint as terminal dampers open, keeping the critical zone damper mostly open and saving fan energy.
- Testing, adjusting, balancing
- The process of measuring and setting air and water flows to design values before functional performance testing. Supply airflow tolerance is typically plus or minus 10 percent.
- Condenser approach temperature
- The difference between condensing refrigerant temperature and leaving condenser water. A rising value signals fouling or poor heat transfer and reduced efficiency.
- Fire damper
- A closure installed where a duct penetrates a fire-rated wall or floor, closing on fire signal or fusible link to stop fire spread through the duct.
- Smoke exhaust rate
- The design volumetric exhaust for smoke control, commonly 60 cubic meters per hour per square meter of floor area for corridors and 120 for atria.
- Door-opening force limit
- In pressurized stairwells the force needed to open a door against the pressure differential must not exceed 110 newtons for safe evacuation.
- Design fire size
- The assumed heat release rate used to size smoke exhaust, typically 2.5 to 5 megawatts for atria and large spaces with steady burning.
- 280 degree fan rating
- Smoke exhaust fans and ducts must operate at 280 degrees Celsius for 30 minutes to remain functional during a fire and remove hot smoke.
- Professional seal
- The registered engineer's stamp on design documents certifying personal preparation or supervision. Sealing work not prepared by the engineer violates registration rules.
- Conflict of interest
- A financial or personal interest in a supplier or contractor that could bias design decisions. It must be disclosed and avoided in specifications.
- Continuing education requirement
- The minimum hours of approved professional training a registered engineer must complete each registration cycle to renew and maintain the license.
- Record retention
- The obligation to keep design calculations, load calculations, commissioning reports and as-built drawings for the regulated period to support audits and liability defense.