Registered Public Utility Engineer - HVAC (China): Ventilation, Smoke Control and Industrial Exhaust

Registered Public Utility Engineer - HVAC (China) · Work through your exam, one topic at a time.

All guide sections

Ventilation, Smoke Control and Industrial Exhaust

Ventilation and smoke control are examined together because both concern moving air through defined paths at defined rates. Industrial ventilation asks for capture and transport; smoke control asks for tenability in escape routes and for a fan that survives 280 °C.

Industrial ventilation

  • Local exhaust beats dilution. Capture velocity at the hood face depends on the contaminant: about 0.25–0.5 m/s for fumes and gases, 1–2.5 m/s for grinding dust, higher for high-velocity particles.
  • Duct transport velocity must exceed the settling velocity: roughly 12–15 m/s for coarse dust and 18–23 m/s for heavy or moist dust. Too low causes silting; too high wastes fan power and erodes elbows.
  • Make-up air must be at least the exhaust volume minus permitted exfiltration, otherwise the fan stalls against negative pressure and doors become hard to open.

Smoke control under GB 51251

  • Stairwell pressurization about 50 Pa; lobby or refuge floor 25–30 Pa; the differential across a closed door must keep opening force within about 110 N.
  • Exhaust volumes follow space type (corridor, atrium, basement, warehouse), with make-up air at not less than 50% of the exhaust rate.
  • Smoke exhaust fans are rated 280 °C for 30 minutes; fire dampers in ordinary ducts close at 70 °C. Never interchange these.

Worked example

A stair door 1.0 m × 2.1 m must pass 0.7 m/s when open: flow = 2.1 × 0.7 = 1.47 m³/s = 5292 m³/h. Add closed-door leakage, Q = 0.827·A·√ΔP; with A = 0.06 m² and ΔP = 50 Pa, Q = 0.827 × 0.06 × 7.07 = 0.35 m³/s = 1263 m³/h. Total ≈ 6555 m³/h before a 1.1–1.2 safety factor, giving a fan selection near 7200–7900 m³/h.

Traps

Quoting a single pressurization value for both stair and lobby; sizing the pressurization fan on closed-door leakage only; omitting make-up air and then wondering why the exhaust rate is not achieved; using 70 °C dampers in a smoke exhaust duct; and forgetting that natural smoke exhaust needs an inlet area and a vent height, not just an outlet.