T&P Relief Drips After a PRV Was Installed

CO Plumber · Put your knowledge to work in context.

All case studies

T&P Relief Drips After a PRV Was Installed

A two-story house on a hill has 135 psi static pressure at the hose bibb. Last spring a plumber installed a 3/4-inch pressure-reducing valve set to 60 psi and a new 50-gallon gas water heater with a new T&P valve rated 150 psi / 210°F. Since then the T&P has dripped about a cup a day, mostly in the hours after a shower. The burner and pilot run normally, and there is no expansion tank anywhere on the system and no backflow device at the meter beyond the PRV itself. The discharge is 1/2-inch copper ending 3 ft above the floor with a threaded cap screwed on "to keep dust out." The homeowner's handyman suggests either tightening the cap or replacing the T&P with a higher-rated valve.

1. Diagnose the drip and describe how you would confirm it rather than guess.

Read the worked answer

The drip began after the PRV went in, and the timing - after hot water is drawn and the tank recovers - points to thermal expansion in a now-closed system.

Before the PRV, the house saw 135 psi, which is itself a problem, but the tank could push expanded water back out to the main. A PRV with a check seat makes the system closed: every heating cycle, 40–50 gallons of water expanding about 1% per 100°F has nowhere to go, pressure climbs from 60 psi toward the 150 psi valve setting, and the T&P relieves a little each time.

Confirm instead of assuming:

  • Gauge on the tank drain valve. Watch pressure through a full recovery cycle. A rise from about 60 psi to near 150 psi is diagnostic.
  • Rule out a bad PRV or a failed T&P. Check static pressure upstream and downstream to make sure the valve is holding and not passing; check the T&P for debris or a weak spring by observing whether it passes at low pressure with a hose bibb open.
  • Check for a missing or failed check/backflow device that would also create a closed system.

Do not accept the handyman's fixes. Tightening the cap blocks the safety device; installing a higher-rated valve defeats the listing and can turn a drip into a tank or piping failure.

2. What is the correct repair, and how is the device sized?

Read the worked answer

Install listed thermal-expansion control on the cold side of the water heater, between the heater and any check valve or PRV. Code requires expansion control where a closed system is created by a backflow preventer, check valve, or PRV.

Sizing is not guesswork:

  • Precharge the tank to the system's static pressure, i.e., the PRV setting of about 60 psi.
  • Size from system volume and temperature swing. For a typical 2-story home with a 50-gallon heater, total system volume is often 60–100 gallons; manufacturer sizing charts for that volume and a 60 psi precharge typically land in the 2- to 4.5-gallon acceptance-volume range. Use the chart, not floor space.
  • Verify the relief valve is the correct rating for the heater and is not damaged from repeated lifting; replace it if it has been relieving for a season.
  • Recheck the PRV setting - 50–60 psi is appropriate for a house with 135 psi main pressure.

Finally, confirm the meter configuration: if the utility's meter setter contains a check valve, that alone can close the system even without a PRV.

3. How must the discharge piping be corrected, and why does each detail matter?

Read the worked answer

The discharge piping is a safety device, not a drain line, and every requirement has a failure mode behind it:

  • Remove the cap. A cap or plug defeats the valve and can allow tank pressure to exceed the relief setting. The outlet must be unthreaded so nothing can be added to it.
  • Full size. The pipe must be the same nominal size as the valve outlet, or larger - reducing it restricts capacity.
  • No valves, no traps, no uphill runs. Gravity flow only, and no fittings that can trap water and freeze or corrode.
  • Terminate correctly. Not more than 6 inches above the floor, or to the exterior at a point that will not scald anyone standing near it. A discharge that ends 3 ft above the floor near the water heater can spray a person at close range.
  • Material rated for 210°F, listed for the temperature and pressure - copper, CPVC, or another listed material, per the code and the manufacturer.
  • Air gap if it discharges to a floor drain or receptor; never a direct connection into the drainage system.

Explain to the homeowner that the drip was the system's way of telling them the pressure was going somewhere - the repair is to give the expanded water a place to go, not to silence the valve.