Building Science Fundamentals

  • Heat moves by conduction (solid contact), convection (fluid/air movement), and radiation (electromagnetic); a building assembly rarely resists all three equally.

  • R-value measures conductive resistance only; it does not account for air leakage, thermal bridging, or radiant gains.

  • The stack effect drives warm air up and out of the top of a building in winter; neutral pressure plane is where indoor and outdoor pressure are equal.

  • Water vapor moves by diffusion (through materials, driven by vapor pressure difference) and by air transport (with bulk air leakage); air transport typically moves far more moisture.

  • Dew point is the temperature at which air reaches saturation; condensation forms on surfaces at or below dew point.

  • Thermal bridge is a path of higher conductance through an assembly; it lowers effective R-value below the nominal cavity R-value.

  • Pressure, temperature, and moisture are coupled: a wall that is airtight on both sides can still trap moisture if the wrong side is vapor retardant for the climate.

  • Latent heat is energy absorbed or released during phase change without temperature change; sensible heat changes dry-bulb temperature.

  • Whole-building performance depends on the interaction of envelope, air barrier, vapor control, and mechanical systems; fixing one layer can shift the failure point to another.

Quick reference

Energy Assessment and Diagnostic Testing

  • Blower door test measures envelope air leakage; report CFM50 and normalize to ACH50 = (CFM50 x 60) / conditioned volume in cubic feet.

  • CFM50 to natural infiltration conversion uses the LBL/n-factor method: natural CFM approx CFM50 / N, where N typically ranges about 15-20 for average climates and shielding.

  • Duct leakage testing (e.g., duct blaster) measures leakage to outdoors or total duct leakage; total leakage includes leaks to conditioned space.

  • Pressure pan testing reads pressure difference across a register while the house is depressurized; higher readings indicate greater leakage connection to the zone.

  • Infrared thermography reveals surface temperature differences; it requires a steady delta-T (typically 10-18 F or more) and must be interpreted with air leakage and emissivity in mind.

  • Zonal pressure diagnostics compare pressure between zones to locate dominant leakage paths and estimate effective leakage area.

  • Combustion safety testing includes draft measurement, spillage check, and CO measurement in the flue and ambient air; spillage of flue gases is a fail condition.

  • Energy assessment reports prioritize by cost-effectiveness and safety; health and safety findings take precedence over efficiency upgrades.

  • Baseline data collection includes utility bills, building dimensions, insulation levels, window types, and appliance inventory before any modeling.

Quick reference

Building Envelope and Insulation

  • Nominal R-value is the labeled insulation value; installed or effective R-value is lower due to compression, gaps, thermal bridging, and convection within the cavity.

  • Insulation must be in substantial contact with an air barrier on at least one side and enclosed on all six sides to perform near its rated value.

  • Grade I, II, and III installation quality (RESNET) describes how completely the cavity is filled and how well the insulation contacts the air barrier; grading lowers effective R-value.

  • Vapor retarder class: Class I (<=0.1 perm, e.g., sheet polyethylene), Class II (0.1-1.0 perm, e.g., kraft-faced or some vapor-retarder paints), Class III (1.0-10 perm, e.g., latex paint).

  • In cold climates, the vapor retarder goes on the warm-in-winter (interior) side; in hot-humid climates, avoid interior vapor barriers and use exterior vapor-permeable assemblies.

  • Attic insulation should be installed over a continuous air barrier and maintain ventilation clearance at the eaves; baffles protect the ventilation channel.

  • Rim joists, band joists, and cantilevers are high-leakage, high-bridging locations that require air sealing plus insulation.

  • Windows: U-factor measures whole-window conductance (lower is better); SHGC measures solar heat gain fraction (lower reduces cooling load); air leakage and condensation resistance are separate ratings.

  • Roof and wall assemblies should dry in at least one direction; adding impermeable layers on both sides of a cavity creates a moisture trap.

Quick reference

HVAC and Mechanical Systems

  • Heating and cooling load calculations (Manual J or equivalent) must precede equipment selection; oversized equipment causes short cycling, poor dehumidification, and higher energy use.

  • Equipment sizing uses design conditions and the calculated load; do not size to nameplate of the old unit or to rule-of-thumb square footage.

  • Duct design: total external static pressure must be within the blower's rated range; excessive static pressure reduces airflow and can ice coils or trip limits.

  • Airflow target for typical residential cooling is roughly 350-400 CFM per ton of capacity; low airflow causes coil icing and high supply temperatures.

  • Refrigerant charge must be verified by superheat or subcooling per manufacturer method; undercharge and overcharge both reduce capacity and efficiency.

  • Combustion appliances need adequate combustion air; a confined space requires two permanent openings sized per code or a ducted outdoor air supply.

  • Heat pump balance point is the outdoor temperature at which heat pump capacity equals building load; below it, auxiliary heat runs.

  • Duct location matters: ducts in unconditioned attics lose or gain significant energy; sealing and insulating ducts or moving them inside the envelope improves efficiency.

  • Ventilation: ASHRAE 62.2 sets whole-house ventilation rates; exhaust-only, supply-only, and balanced (HRV/ERV) strategies differ in pressure effects and energy recovery.

Quick reference

Air Sealing and Moisture Management

  • The air barrier must be continuous, durable, and in contact with insulation; the vapor retarder is separate and its location depends on climate.

  • Air sealing priority order: attic plane (top of house), rim joists and band joists, penetrations through the envelope, then windows and doors.

  • Chimney chases, dropped soffits, and balloon-frame cavities are major hidden leakage paths that connect conditioned space to attic or exterior.

  • Can lights, bath fans, and dryer vents must be sealed and, where penetrating the envelope, must not create a moisture path into the cavity.

  • Bulk water control is the first defense: roof, flashing, drainage, and grading; vapor control and air sealing come after bulk water is managed.

  • Wet basements: manage exterior water first (grading, downspouts, footing drains); interior vapor barriers on the wrong side can trap moisture in the slab or wall.

  • Crawlspace encapsulation converts a vented crawlspace to a conditioned, sealed space; it requires a ground vapor barrier, sealed vents, and often a supply or dehumidifier.

  • Bath and kitchen exhaust must terminate outdoors, not into attic or crawlspace; backdraft dampers and short, smooth duct runs reduce moisture and pressure problems.

  • In hot-humid climates, interior air leaking into wall cavities can condense on cool surfaces; air sealing the interior side reduces this risk.

Quick reference

Health and Safety: Combustion and Indoor Air Quality

  • Carbon monoxide (CO) is a colorless, odorless gas from incomplete combustion; symptoms include headache, nausea, dizziness, and fatigue; it is a life-safety hazard.

  • Combustion safety order of operations: verify draft, check for spillage, measure CO in flue and ambient air, and confirm combustion air before any tightening of the envelope.

  • Atmospheric (natural draft) appliances are the most vulnerable to depressurization from exhaust fans, dryers, and blower door testing; induced-draft and sealed-combustion units are safer.

  • Depressurization limits: combustion appliance zone (CAZ) testing checks whether exhaust fans can depressurize the zone enough to backdraft appliances.

  • Radon is a radioactive soil gas that enters through foundation cracks and openings; test before and after air sealing; mitigation uses sub-slab depressurization.

  • Moisture and mold: indoor relative humidity should generally be kept below about 50-60% in cooling season to limit mold growth; fix the water source first.

  • Ventilation with filtration (MERV-rated filters) reduces particulates; high-MERV filters increase static pressure and may require blower adjustment.

  • Asbestos and lead paint are hazards in older homes; disturb them only with proper precautions and certified abatement where required.

  • CO alarms should be installed near sleeping areas and on each level; test and replace per manufacturer instructions.

Quick reference

Energy Modeling, Codes, and Program Standards

  • Energy models compare proposed upgrades against a baseline; savings estimates depend on accurate inputs for envelope, equipment, and occupancy schedules.

  • Model calibration compares predicted energy use to utility bills; a common target is within about 10% of annual consumption.

  • Degree-day method estimates heating or cooling energy from the difference between indoor and outdoor temperature integrated over the season.

  • RESNET HERS Index: 100 equals a reference new home of the same size and shape; lower is better; a HERS Index of 0 is a net-zero-energy home.

  • Energy Star for Homes requires third-party verification and a HERS Index threshold that tightens over program versions; check current version requirements.

  • Building codes (IECC) set prescriptive or performance paths; the performance path uses whole-building energy modeling to trade off measures.

  • Weatherization programs (e.g., WAP) prioritize cost-effective measures and require health and safety inspections before efficiency work.

  • Program standards define allowable measures, required documentation, and quality control; failing inspection can require rework and may affect payment.

  • Utility bill analysis: normalize for weather using heating and cooling degree days and separate base load from seasonal load.

Quick reference

Customer Communication and Scope Development

  • Scope of work should list each measure, quantity, location, and expected outcome, plus exclusions and assumptions.

  • Explain findings in plain language: describe the problem, the evidence (test results), the recommended fix, and the expected benefit.

  • Cost-effectiveness is presented as savings versus installed cost; simple payback = installed cost / annual savings.

  • Informed consent: customers should understand health and safety findings, limitations of testing, and that savings are estimates, not guarantees.

  • Prioritize safety and durability measures before comfort and efficiency measures in the written scope.

  • Document baseline conditions and pre-work test results so post-work verification can demonstrate improvement.

  • Set expectations on timelines, access, dust and disruption, and inspection requirements; confirm who is responsible for permits.

  • Avoid technical jargon in customer-facing reports; define terms like ACH50, R-value, and HERS Index in one sentence each.

  • Change orders should be written and signed when scope changes during the job; verbal changes create disputes.