Quick reference

Safety and Environmental Protection

  • EPA Section 608 prohibits knowingly venting ozone-depleting refrigerants and their non-exempt substitute refrigerants to the atmosphere during service, maintenance, or disposal.

  • Evacuation levels before opening a system: appliances built after Nov 15, 1993 require 10 in. Hg vacuum (4 in. Hg if the compressor is inoperative); small appliances may use 80% recovery or 4 in. Hg.

  • Recovery cylinders must never be filled beyond 80% of capacity by weight, because liquid refrigerant expands as it warms and a hydraulically full cylinder can rupture.

  • Never mix two different refrigerants in one recovery cylinder; a mixed cylinder cannot be reclaimed and must be destroyed.

  • A2L refrigerants are mildly flammable (burning velocity no greater than 10 cm/s); charge limits and ignition-source control follow ASHRAE 15 and UL 60335-2-40.

  • OSHA's permissible exposure limit for carbon monoxide is 50 ppm as an 8-hour time-weighted average; NIOSH recommends 35 ppm as the ceiling for worker exposure.

  • Refrigerant vapor is heavier than air and displaces oxygen in pits, basements, and low spaces; atmosphere must be tested before entry.

  • Liquid refrigerant at atmospheric pressure boils far below 0°F, so safety goggles and insulating gloves are required to prevent frostbite on contact.

  • Lockout/tagout plus capacitor discharge is required before electrical service; stored charge can remain in run and start capacitors after power is removed.

Quick reference

Tools, Instruments, and Measurement

  • Manifold gauge color code: blue hose and gauge = low side, red = high side, yellow = center port for recovery, evacuation, or charging.

  • Superheat (°F) = measured suction line temperature minus the saturation temperature at the measured suction pressure.

  • Subcooling (°F) = saturation temperature at the measured liquid-line pressure minus the measured liquid-line temperature.

  • Evacuation is confirmed with an electronic micron gauge, not a manifold gauge; a standing vacuum test holds below 500 microns for 10–15 minutes with the pump isolated.

  • 1 in. w.c. = 249 pascals = 0.0361 psi; duct static pressures are read with a manometer, Magnehelic gauge, or digital differential pressure instrument.

  • Cfm = velocity in fpm × free area in square feet; velocity comes from an anemometer, velometer, or pitot tube traverse.

  • Clamp meters must be true RMS to read inverter-driven compressor and ECM blower current accurately; averaging meters under-report distorted waveforms.

  • Infrared thermometers misread shiny or reflective surfaces because of low emissivity; contact probes or thermocouples are used for refrigerant line temperatures.

  • Electronic leak detectors are refrigerant-family specific; a nitrogen pressure test with soap bubbles confirms the exact leak location.

Quick reference

Refrigeration Fundamentals and the Refrigeration Cycle

  • The four core components are the compressor, condenser, metering device, and evaporator; the metering device separates the high side from the low side.

  • 1 ton of refrigeration = 12,000 Btu/h = 3.517 kW = 200 Btu/min.

  • Saturation means a refrigerant boils and condenses at a single temperature for a given pressure (ignoring glide in blends).

  • Compression ratio = absolute discharge pressure ÷ absolute suction pressure, both in psia; high ratios raise discharge temperature and reduce volumetric efficiency.

  • Superheat is added after the evaporator; subcooling is produced in the bottom of the condenser as liquid backs up behind the metering device.

  • Latent heat of vaporization of water at atmospheric pressure is about 970 Btu/lb; most evaporator capacity is latent in humid climates.

  • R-410A is a near-azeotropic blend with about 0.2°F glide and operates at roughly 50–60% higher pressures than R-22.

  • Zeotropic blends fractionate: a vapor leak leaves a liquid charge with a different composition, so blends are charged as liquid.

  • Flash gas at the evaporator inlet consumes coil surface without absorbing room heat, so the metering device must pass liquid only.

Quick reference

Electrical Fundamentals and Controls

  • Ohm's law: V = I × R; resistive power P = V × I; single-phase power P = V × I × power factor.

  • Balanced three-phase power: P = √3 × V × I × power factor.

  • Series circuits share one current and add voltages; parallel circuits share one voltage and add branch currents.

  • Capacitors must be discharged before testing; a capacitance reading more than about 10% below nameplate indicates a weak run capacitor.

  • Locked rotor amps are typically 5–6 times rated load amps; a compressor that stays at LRA without starting has a start-circuit or mechanical fault.

  • Residential 24 V control circuits are Class 2; R is 24 V hot, C is common, Y is cooling, W is heating, G is indoor fan.

  • ECM blowers are electronically commutated motors: line voltage powers them, a low-voltage signal sets speed, and airflow is programmed to stay constant.

  • A contactor coil is rated by voltage and VA; pitted or welded contacts cause continuous compressor operation or single-phasing.

  • Cooling-call sequence: thermostat closes Y and G, contactor coil energizes, compressor and condenser fan start, indoor blower starts.

Quick reference

Air Distribution, Ductwork, and Indoor Air Quality

  • Cfm = velocity (fpm) × duct cross-sectional area (sq ft); round duct area = π r².

  • Sensible Btu/h = 1.08 × cfm × dry-bulb temperature difference.

  • Total Btu/h = 4.5 × cfm × enthalpy difference; latent Btu/h = 0.68 × cfm × grains difference.

  • Residential blowers are rated at a total external static pressure, commonly 0.5 in. w.c.; readings above the fan table value indicate restrictive filters, coils, or ducts.

  • Equal-friction duct sizing commonly targets about 0.1 in. w.c. of friction loss per 100 ft of duct run.

  • Return grilles are sized for roughly 400–500 fpm face velocity and filters for about 300 fpm to limit pressure drop.

  • Duct leakage is measured with a duct blaster that pressurizes the system to 25 Pa and reports leakage in cfm25.

  • ASHRAE 62.2 residential ventilation rate: Qtot = 0.03 × conditioned floor area (ft²) + 7.5 × (number of bedrooms + 1), in cfm.

  • Indoor relative humidity should stay roughly 30–50%; sustained values above 60% support mold and dust mite growth.

Quick reference

Heating Systems and Components

  • Temperature rise = supply air temperature − return air temperature; it must fall inside the range printed on the rating plate at the correct airflow.

  • Natural gas manifold pressure is typically 3.5 in. w.c.; LP gas manifold pressure is typically 10–11 in. w.c.

  • Electric resistance heat delivers 3.413 Btu per watt-hour.

  • AFUE is annual fuel utilization efficiency; condensing furnaces exceed 90% AFUE by recovering latent heat in a secondary heat exchanger.

  • Condensing furnace flue pipe must slope back toward the furnace so acidic condensate drains to a trapped condensate line.

  • Flame rectification sensors typically read 2–6 microamps; the control module closes the gas valve when the signal falls near 1 microamp.

  • Natural-draft appliances depend on a draft hood and adequate combustion air; a spillage test at the draft hood verifies proper venting.

  • A heat pump balance point is the outdoor temperature where heat pump capacity equals building load; below it, auxiliary or emergency heat carries the load.

  • Defrost may terminate on coil temperature, pressure, or time, and the reversing valve shifts the system to cooling mode during defrost.

Quick reference

Cooling Systems and Components

  • Common compressor types are reciprocating, scroll, and rotary; scroll compressors dominate residential split systems.

  • Low evaporator airflow lowers suction pressure and can produce coil icing, low superheat, and liquid floodback to the compressor.

  • Dirty or blocked condenser coils raise discharge pressure and temperature, increasing compression ratio and compressor amp draw.

  • A TXV modulates to hold constant evaporator superheat; a fixed-orifice piston's superheat varies with load and ambient conditions.

  • Typical target subcooling on a TXV system is about 10–12°F, matched to the manufacturer's charging chart.

  • Target superheat on fixed-orifice systems is read from a charging chart using indoor wet-bulb and outdoor dry-bulb temperature.

  • Condensate drains on a negative-pressure coil must include a trap and continuous slope, or the pan will not drain.

  • A crankcase heater keeps oil warm during the off cycle to prevent refrigerant migration and oil dilution; it must be energized before restart after long shutdowns.

  • A filter drier removes moisture and particulates; a flashing liquid line on a sight glass indicates a restriction or undercharge in many systems.

Quick reference

System Performance, Commissioning, and Diagnostics

  • Commissioning order: verify airflow and static pressure first, confirm refrigerant charge second, then measure the air temperature split.

  • Cooling temperature split is typically 16–22°F; a low split suggests low load or excess airflow, a high split suggests low airflow.

  • New installations are charged by weight; field verification uses subcooling on TXV systems and superheat on fixed-orifice systems.

  • Compare measured compressor current to nameplate RLA; current well above RLA indicates high head pressure, low voltage, or a failing compressor.

  • Combustion analysis reports O2, CO, CO2, and stack temperature; air-free CO above about 100 ppm in flue gas indicates a combustion problem requiring correction.

  • High suction plus high head points to overcharge, excessive load, or poor condenser airflow; low suction plus low head points to undercharge or a restriction.

  • On a TXV system, high superheat with low subcooling indicates undercharge; low superheat with high subcooling indicates overcharge.

  • A blower door test pressurizes the house to 50 Pa and reports ACH50, quantifying envelope leakage for load and infiltration estimates.

  • Recording baseline pressures, temperatures, amps, and static pressures at start-up provides the reference for later diagnostics.