32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Section 608 venting prohibition
Under EPA Section 608, knowingly venting ozone-depleting refrigerants and their non-exempt substitute refrigerants to the atmosphere during service, maintenance, or disposal is prohibited.
Recovery cylinder 80 percent rule
Recovery and refrigerant cylinders must never be filled beyond 80 percent of capacity by weight, because liquid refrigerant expands as it warms and can rupture a completely full cylinder.
A2L refrigerant flammability class
A2L refrigerants are mildly flammable, with a lower flammability limit and a burning velocity no greater than 10 cm/s; charge limits and ignition-source control follow ASHRAE 15 and UL 60335-2-40.
Nitrogen pressure testing rule
Pressure-test systems only with dry nitrogen and a pressure regulator; never use oxygen or compressed air, because oxygen combined with compressor oil can ignite or explode.
Micron gauge purpose
An electronic micron gauge reads absolute pressure during evacuation; it resolves levels far below what manifold gauges indicate, so it is required to confirm the system reached 500 microns.
Superheat calculation formula
Superheat equals the actual suction line temperature minus the saturation temperature corresponding to the measured suction pressure, expressed in degrees Fahrenheit.
Subcooling calculation formula
Subcooling equals the saturation temperature at the measured liquid-line pressure minus the actual liquid-line temperature; it confirms a solid liquid seal at the condenser outlet.
Manometer reading units
A manometer measures duct static pressure in inches of water column; one inch of water column equals about 249 pascals, or 0.036 psi.
One refrigeration ton
One ton of refrigeration equals 12,000 Btu per hour, or about 3.517 kilowatts, the rate of heat removal needed to freeze one ton of ice in 24 hours.
Latent versus sensible heat
Sensible heat changes a substance's temperature without changing its state, while latent heat changes state at constant temperature, as when refrigerant boils or condenses in a coil.
Compression ratio definition
Compression ratio is absolute discharge pressure divided by absolute suction pressure, both in psia; higher ratios raise discharge temperature and reduce volumetric efficiency.
Zeotropic blend temperature glide
A zeotropic refrigerant blend evaporates and condenses across a temperature range called glide, and it must be charged as a liquid to prevent fractionation of the mixture.
Ohm's law relationship
Voltage equals current multiplied by resistance (V = I × R); rearranged, current equals voltage divided by resistance and resistance equals voltage divided by current.
Thermostat terminals R Y W G
R supplies 24-volt control power, Y energizes the compressor contactor for cooling, W energizes the heating circuit, and G starts the indoor blower.
Run capacitor microfarad test
Discharge the capacitor, then measure microfarads with a capacitance meter; a reading more than about 10 percent below the nameplate rating indicates a weak capacitor.
Three-phase power formula
For a balanced three-phase load, true power in watts equals the square root of three multiplied by volts, amps, and power factor.
Airflow from velocity
Cubic feet per minute equals air velocity in feet per minute multiplied by the duct cross-sectional area in square feet at the measurement point.
Sensible heat airflow equation
Sensible Btu per hour equals 1.08 multiplied by cfm multiplied by the dry-bulb temperature difference across the coil or the furnace heat exchanger.
External static pressure limit
Residential blowers are typically rated at 0.5 inches of water column total external static pressure; readings above the fan table value mean restricted ducts, coils, or filters.
Duct leakage test pressure
A duct blaster pressurizes the duct system to 25 pascals and reports leakage in cfm at that pressure, allowing comparison against program or code thresholds.
Natural gas manifold pressure
Most natural gas furnaces are set to about 3.5 inches of water column manifold pressure, while propane appliances typically require 10 to 11 inches.
Furnace temperature rise
Temperature rise is supply air temperature minus return air temperature; it must fall within the range printed on the furnace rating plate at the correct airflow.
Flame sensor microamp reading
A flame sensor proves ignition by flame rectification; a healthy reading is roughly 2 to 6 microamps, and lower values indicate a dirty or failing sensor.
Condensing furnace secondary exchanger
A condensing furnace extracts additional heat in a secondary heat exchanger, cooling flue gas below its dew point; the acidic condensate must drain through a trap.
TXV superheat control
A thermostatic expansion valve modulates refrigerant flow to hold a set evaporator superheat, responding to the temperature and pressure sensed by its remote bulb.
Subcooling charging method
Systems with a thermostatic expansion valve are charged by the subcooling method, targeting the manufacturer's specified value, commonly around 10 to 12 degrees Fahrenheit.
Superheat charging method
Fixed-orifice systems are charged by superheat, using a chart based on indoor wet-bulb and outdoor dry-bulb temperature to determine the target superheat value.
Crankcase heater function
A crankcase heater warms compressor oil so refrigerant does not migrate and condense into the oil during the off cycle, which would dilute lubricant and damage bearings.
Cooling temperature split
The dry-bulb temperature difference between return and supply air in cooling is typically 16 to 22 degrees Fahrenheit when airflow and refrigerant charge are correct.
Commissioning airflow checked first
Airflow must be verified before refrigerant charge is evaluated, because incorrect evaporator airflow skews superheat and subcooling readings and misleads the technician.
High head high suction diagnosis
High discharge pressure together with high suction pressure usually indicates an overcharged system, excessive heat load, or insufficient condenser airflow.
Blower door ACH50 test
A blower door measures envelope airtightness by pressurizing the house to 50 pascals and reporting air changes per hour at that pressure, called ACH50.