Electrical Power System Fundamentals

  • Three-phase real power P = √3 × V_LL × I_L × power factor; for single-phase P = V × I × PF.

  • Apparent power S (VA) = P + jQ; reactive power Q = √3 × V_LL × I_L × sin θ, positive for inductive loads.

  • Per-unit method: Z_pu = Z_actual / Z_base, where Z_base = V_base² / S_base; base change formula Z_pu,new = Z_pu,old × (S_new/S_old) × (V_old/V_new)².

  • Delta-connected load: phase voltage equals line voltage, line current = √3 × phase current. Wye-connected load: phase current equals line current, line voltage = √3 × phase voltage.

  • Transformer turns ratio a = N1/N2 = V1/V2; reflected impedance Z_primary = a² × Z_secondary.

  • Voltage drop on a feeder ≈ √3 × I × (R cos θ + X sin θ) for three-phase; keep drop within 3% (branch) and 5% total per NEC 210.19 informational notes.

  • Short-circuit current from a source: I_sc = V / Z_source; transformer I_sc,secondary ≈ I_FLA / Z_pu.

  • Power factor correction kVAR = P × (tan θ_initial − tan θ_target); capacitors do not reduce real power, only reactive demand.

  • Symmetrical components: any unbalanced three-phase set decomposes into positive, negative, and zero sequences; zero-sequence currents require a neutral or ground return path.

Quick reference

Motors

  • Synchronous speed N_s = 120 × f / P (rpm); slip s = (N_s − N_r)/N_s, typically 1–5% at full load for induction motors.

  • NEMA Design B is the general-purpose industrial motor: locked-rotor current ≈ 6× FLA, breakdown torque ≈ 200% rated, slip < 5%.

  • NEMA frame sizes encode face-to-face dimensions; frame number × 4 = shaft height in sixteenths of an inch (e.g., 184T → 4.5 in).

  • Motor FLA from NEC Table 430.250 is used for branch-circuit sizing; nameplate FLA is used for overload protection (NEC 430.32).

  • Insulation class B = 130 °C, F = 155 °C, H = 180 °C; Class F with 1.15 service factor is the common industrial combination.

  • Torque (lb-ft) = 5252 × HP / rpm; motor current is approximately proportional to load torque below breakdown.

  • DC motor speed ≈ (V − I_a R_a)/kΦ; shunt motor is nearly constant speed, series motor has high starting torque and must never run unloaded.

  • Inverter-duty motors require insulation rated for PWM voltage spikes and often a shaft grounding ring to prevent bearing currents.

Quick reference

Motor Controls and Variable Frequency Drives

  • NEMA contactor sizing uses AC-3 for squirrel-cage motor starting; IEC utilization categories: AC-1 resistive, AC-3 motor starting, AC-4 plugging/jogging.

  • Overload relay class number = trip time in seconds at 6× FLA from cold; Class 10 is standard, Class 20 for high-inertia loads.

  • VFD V/f control holds V/f constant to keep flux constant; below base speed torque is constant, above base speed power is constant (field weakening).

  • PWM carrier frequency: higher carrier reduces audible noise but increases switching loss, common-mode current, and motor heating.

  • VFD acceleration time must exceed the motor's accelerating torque capability; DC injection braking is limited (typically 3–5 s) to avoid overheating.

  • Line reactors (typically 3–5% impedance) reduce VFD input harmonics and protect the drive from transients; harmonic limits per IEEE 519.

  • VFD output cable: use shielded VFD cable, limit distance per manufacturer, and never install a contactor or disconnect between drive and motor while running.

  • Safe torque off (STO) removes gate pulses without contactor; it is not equivalent to a lockout/tagout isolation.

Quick reference

Instrumentation and Process Measurement

  • 4–20 mA loop: 4 mA = 0% and 20 mA = 100% of span; live zero at 4 mA allows detection of broken wires.

  • Ohm's law for loops: maximum loop resistance = (supply voltage − 12 V) / 0.020 A for a 4–20 mA transmitter.

  • RTD (Pt100): 100 Ω at 0 °C, ≈ 0.385 Ω/°C; 3-wire and 4-wire connections cancel lead resistance.

  • Thermocouple types: K (chromel-alumel) most common general purpose; J (iron-constantan) not for oxidizing atmospheres; use reference junction compensation.

  • Orifice plate flow: Q ∝ √ΔP; a 25% flow requires 6.25% of full-scale differential pressure.

  • Gauge vs absolute vs differential pressure: gauge reads relative to atmosphere, absolute relative to vacuum, differential is the difference between two ports.

  • Level by differential pressure: ΔP = ρ × g × h; interface and density changes shift zero and require compensation.

  • HART superimposes a ±0.5 mA FSK digital signal on the 4–20 mA analog current; loop must have ≥ 230 Ω for communication.

Quick reference

Programmable Logic Controllers and Automation Systems

  • PLC scan cycle: input scan → logic solve → output update → housekeeping; scan time is dominated by program size and instruction mix.

  • Ladder logic: XIC (examine if closed), XIO (examine if open), OTE (output energize), OTL/OTU (latch/unlatch), TON/TOF/RTO timers, CTU/CTD counters.

  • A TON timer's accumulated value resets when its rung goes false; an RTO retains accumulated value until a separate reset.

  • Analog input scaling: engineering units = ((raw − raw_min)/(raw_max − raw_min)) × (EU_max − EU_min) + EU_min.

  • Sinking vs sourcing: a sinking input module provides the common return; a sourcing output module supplies +24 V to the load.

  • PID equation: output = Kp·e + Ki·∫e dt + Kd·de/dt; derivative acts on error or PV (derivative-on-PV avoids derivative kick).

  • Safety PLCs and standard PLCs must be separate; safety functions require certified hardware and are rated by SIL (IEC 61508/61511) or PL (ISO 13849).

  • Industrial networks: EtherNet/IP and PROFINET are Ethernet-based; Modbus RTU is RS-485 serial; DeviceNet and Profibus DP are fieldbus.

Quick reference

Electrical Safety

  • NFPA 70E arc flash PPE categories: Category 1 (4 cal/cm²), 2 (8), 3 (25), 4 (40); use incident-energy analysis when available.

  • Arc flash boundary: distance at which incident energy equals 1.2 cal/cm² (the second-degree burn threshold).

  • Approach boundaries per NFPA 70E: limited (shock protection), restricted (qualified only), and arc flash boundary.

  • Lockout/tagout per OSHA 1910.147 requires energy isolation, verification of zero energy, and a lock per worker.

  • Body current thresholds: 1 mA perception, 10 mA let-go, 30 mA respiratory tetanus, 100–300 mA ventricular fibrillation.

  • Ground-fault circuit interrupters trip at 4–6 mA; equipment protective devices (GFPE) trip at 30 mA for personnel protection at higher settings.

  • Bonding and grounding: equipment grounding conductor carries fault current; earth ground is not a substitute for the EGC.

  • Test before touch: verify a meter on a known live source, test the circuit, then re-verify on the known source.

Quick reference

Codes and Standards

  • NEC Article 430 covers motors; 430.52 sets branch-circuit short-circuit and ground-fault protection at 250% of FLA for inverse-time breakers (up to 400% if needed).

  • NEC 430.32 overload protection: 125% of motor nameplate FLA for motors with 1.15 service factor, 115% otherwise.

  • NEC Table 310.16 ampacities apply to not more than three current-carrying conductors in a raceway at 30 °C ambient; apply correction factors for temperature and conduit fill.

  • NEC 250.122 equipment grounding conductor sizing is based on the overcurrent device rating, not the conductor ampacity.

  • NEC 210.8 requires GFCI protection for 125–250 V receptacles in bathrooms, kitchens, outdoors, garages, and similar locations.

  • NEC 500/505 hazardous locations: Class I gases/vapors, Class II dusts, Class III fibers; Division 1 vs 2, or Zones 0/1/2 (gas) and 20/21/22 (dust).

  • NEMA enclosure types: Type 1 indoor general, Type 4/4X watertight (X = corrosion resistant), Type 7/9 hazardous gas/dust.

  • IEEE 519 limits harmonic current distortion at the point of common coupling; IEEE 1584 provides arc flash incident-energy calculations.

Quick reference

Troubleshooting, Maintenance and Reliability

  • Half-splitting: measure at the midpoint of a signal chain to halve the search area; continue until the faulty component is isolated.

  • Motor insulation resistance: minimum acceptable ≈ 1 MΩ per kV of rated voltage plus 1 MΩ; Polarization Index (10 min / 1 min) > 2.0 is good.

  • Vibration analysis: 1× running speed = unbalance; 2× = misalignment; high-frequency broadband = bearing defect; bearing defect frequencies BPFO/BPFI/BSF/FTF.

  • Infrared thermography detects loose connections and overloaded conductors; compare phase-to-phase and ambient-referenced temperatures.

  • Thermography delta-T guides: 1–3 °C possible deficiency, 4–15 °C probable, >15 °C major, >40 °C critical.

  • Predictive maintenance uses condition monitoring (vibration, oil analysis, thermography, MCA) to schedule work before failure.

  • Reliability metrics: MTBF = total operating time / number of failures; availability = MTBF / (MTBF + MTTR).

  • Root cause analysis tools: 5 Whys, fishbone (Ishikawa), and fault tree analysis; always verify with physical evidence.