ESAA Intermediate Level Exam flashcards
ESAA Intermediate Level Exam · Build recall with a focused review session.
33 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Three-phase real power
- P = √3 × V_line-line × I_line × power factor. This formula applies to balanced three-phase loads and gives the actual power consumed in watts.
- Per-unit impedance
- Z_pu = Z_actual / Z_base, where Z_base = V_base² / S_base. Per-unit values simplify transformer and fault calculations across voltage levels.
- Wye vs delta currents
- In a wye connection, line current equals phase current. In a delta connection, line current is √3 times phase current. Voltages follow the opposite rule.
- Power factor correction
- Capacitor kVAR = P × (tan θ_initial − tan θ_target). Capacitors supply reactive power locally and reduce line current without changing real power.
- Synchronous speed formula
- N_s = 120 × f / P, where f is frequency in Hz and P is the number of poles. A four-pole motor at 60 Hz runs at 1800 rpm synchronous.
- Motor slip
- Slip s = (N_s − N_r)/N_s, usually 1–5% at full load. Slip increases with load and determines the induced rotor current.
- NEMA Design B
- The general-purpose industrial induction motor: locked-rotor current about 6× FLA, breakdown torque about 200% rated, and slip under 5%.
- Motor torque equation
- Torque in lb-ft = 5252 × HP / rpm. This relationship links shaft horsepower, speed, and torque for any rotating machine.
- NEMA overload class
- The class number equals trip time in seconds at 6× FLA from a cold start. Class 10 is standard; Class 20 suits high-inertia loads.
- V/f control principle
- A VFD holds voltage proportional to frequency to keep motor flux constant. Below base speed torque is constant; above base speed power is constant.
- PWM carrier frequency
- Higher carrier frequency reduces audible motor noise but increases switching losses, common-mode current, and motor heating. Manufacturer limits apply.
- Line reactor purpose
- A 3–5% impedance reactor on the VFD input reduces harmonic current and absorbs transients. It also protects the drive's DC bus from surges.
- Safe torque off (STO)
- STO removes gate pulses to the drive output without a contactor. It is a safety function, not an isolation device, and does not de-energize the drive.
- 4–20 mA live zero
- 4 mA represents 0% and 20 mA represents 100% of span. The live zero at 4 mA allows detection of a broken wire or failed transmitter.
- Pt100 RTD resistance
- A Pt100 RTD reads 100 Ω at 0 °C and changes about 0.385 Ω/°C. Three- and four-wire connections cancel lead resistance errors.
- Orifice differential flow
- Flow is proportional to the square root of differential pressure. To get 25% flow, only 6.25% of full-scale ΔP is required.
- HART communication
- HART superimposes a ±0.5 mA frequency-shift digital signal on the 4–20 mA analog loop. The loop needs at least 230 Ω for communication.
- PLC scan cycle
- The PLC reads inputs, solves the program logic, updates outputs, then performs housekeeping. Scan time depends on program size and instruction mix.
- TON vs RTO timers
- A TON timer resets its accumulated value when the rung goes false. An RTO retains the accumulated value until a separate reset instruction.
- Analog input scaling
- Engineering units = ((raw − raw_min)/(raw_max − raw_min)) × (EU_max − EU_min) + EU_min. This maps raw counts into process units.
- PID derivative on PV
- Applying derivative to the process variable instead of the error avoids derivative kick when the setpoint changes suddenly.
- Arc flash boundary
- The distance at which incident energy equals 1.2 cal/cm², the threshold for a second-degree burn. PPE selection depends on incident energy.
- Let-go current
- About 10 mA for an average adult is the let-go threshold. Above this value, a worker cannot release the conductor without help.
- NFPA 70E PPE categories
- Category 1 = 4 cal/cm², Category 2 = 8, Category 3 = 25, Category 4 = 40. Use an incident-energy analysis when one is available.
- Test before touch
- Verify the meter on a known live source, test the target circuit, then re-verify on the known source. This confirms the meter works.
- NEC 430.32 overload rule
- Motor overload protection is set at 125% of nameplate FLA for motors with a 1.15 service factor, and 115% otherwise.
- NEC 250.122 EGC sizing
- The equipment grounding conductor is sized from the overcurrent device rating, not the conductor ampacity. Table 250.122 gives the values.
- Hazardous location classes
- Class I covers gases and vapors, Class II dusts, Class III fibers. Division 1 means normal presence; Division 2 means abnormal presence.
- NEMA enclosure types
- Type 1 is indoor general purpose; Type 4/4X is watertight with 4X corrosion resistant; Type 7/9 covers hazardous gas and dust.
- Polarization index
- The ratio of 10-minute to 1-minute insulation resistance. A value above 2.0 indicates good insulation; below 1.0 is suspect.
- Vibration fault signatures
- 1× running speed indicates unbalance; 2× indicates misalignment; high-frequency broadband energy indicates bearing defects. Phase analysis confirms the diagnosis.
- MTBF and availability
- MTBF = total operating time / number of failures. Availability = MTBF / (MTBF + MTTR), expressed as a fraction or percentage.
- Thermography delta-T
- A 1–3 °C rise suggests a possible deficiency, 4–15 °C a probable one, above 15 °C a major one, and above 40 °C a critical fault.