ESAA Intermediate Level Exam study plan
ESAA Intermediate Level Exam · Give each week a clear focus.
8 weeks · About 7 hours per week
Electrical Power System Fundamentals
Calculate apparent, active and reactive power for balanced three-phase loads and convert between them using the power triangle
Derive per-unit values for a simple radial system and explain why per-unit simplifies transformer and fault calculations
Sketch the single-line diagram of a typical industrial distribution system from utility service through MCC and label each voltage level
Compute voltage drop on a feeder given conductor impedance, current and power factor, and state whether it meets a 3 percent limit
Your checkpoint
A one-page worked calculation sheet solving five three-phase power, per-unit and voltage-drop problems with units shown at every step
Electrical Power System Fundamentals & Electrical Safety, Codes and Standards
Explain how transformer impedance and source strength set available fault current, and estimate fault current for a 1500 kVA transformer at 480 V
Identify the purpose of grounding, bonding and the equipment grounding conductor in a low-voltage industrial system
Locate and interpret the overcurrent protection, conductor sizing and ampacity tables used for feeder design
Distinguish between arc flash, arc blast and shock hazards and state the boundary concept behind each
Your checkpoint
A fault-current and conductor-sizing worksheet for one feeder, with the code table references cited for each value chosen
Motors, Motor Controls and Variable Frequency Drives
Describe the construction and torque-speed characteristic of an induction motor and identify slip at rated load from nameplate data
Explain how a VFD rectifies, filters and inverts to produce variable voltage and frequency, and what the DC bus does
Calculate motor full-load current, overload setting and short-circuit protection sizing from nameplate horsepower and voltage
Compare across-the-line, soft-start and VFD starting methods by inrush current and mechanical stress
Identify VFD-related issues including harmonics, reflected wave on long motor leads and carrier-frequency noise
Your checkpoint
A motor and drive specification sheet for one 50 hp application listing FLA, overload setting, protection size, starting method and justification
Motors, Motor Controls and Variable Frequency Drives & Troubleshooting, Maintenance and Reliability
Diagnose a motor that trips on overload using a structured sequence of current, insulation resistance and mechanical checks
Interpret VFD fault codes such as overcurrent, ground fault and DC bus undervoltage and state the likely root cause of each
Explain how to perform and read an insulation resistance test and what minimum values indicate acceptable winding condition
Describe vibration and thermography as predictive tools and what each detects early in a failing motor or drive
Your checkpoint
A motor troubleshooting decision tree covering overload trip, ground fault and VFD overcurrent, with the measurement that confirms each branch
Instrumentation and Process Measurement
Convert between 4-20 mA, voltage and engineering units for a linear transmitter and calculate the mA value at a given process reading
Explain the difference between two-wire, three-wire and four-wire transmitters and how loop power is supplied
Describe how RTDs and thermocouples work and select the appropriate sensor for a given temperature range and accuracy need
Identify sources of measurement error including lead resistance, cold-junction compensation and grounding-induced noise
Explain how a pressure transmitter measures level in a tank and what reference-leg compensation requires
Your checkpoint
A loop calculation and sensor selection table covering five process points with range, output at midscale and chosen sensor type
Instrumentation and Process Measurement & Programmable Logic Controllers and Automation Systems
Trace a 4-20 mA signal from field transmitter through input card to PLC scaling and show the resulting engineering value
Write and interpret ladder logic for start-stop sealing circuits, interlocks and a simple alarm with delay
Explain PLC scan cycle order and predict how input timing and program order affect an output
Describe how analog input modules scale raw counts and configure one for a 4-20 mA range
Distinguish discrete from analog I/O and identify wiring and isolation considerations for each
Your checkpoint
A documented ladder program for a motor start-stop with interlock and high-temperature alarm, plus the analog scaling math for the temperature input
Programmable Logic Controllers and Automation Systems & Troubleshooting, Maintenance and Reliability
Develop a systematic PLC troubleshooting approach that separates field device, wiring, I/O module and program faults
Use forcing, monitoring and cross-reference tools safely and explain the risk of leaving forces enabled
Describe preventive maintenance tasks for a control cabinet including thermal inspection, terminal torque checks and backup verification
Explain how to verify a program backup and restore it to a replacement processor
Identify reliability metrics such as MTBF and MTTR and how they guide maintenance prioritization
Your checkpoint
A control cabinet preventive maintenance checklist with ten tasks, each with acceptance criteria and a record field
Electrical Safety, Codes and Standards & Electrical Power System Fundamentals & Motors, Motor Controls and Variable Frequency Drives & Instrumentation and Process Measurement & Programmable Logic Controllers and Automation Systems & Troubleshooting, Maintenance and Reliability
Review lockout/tagout and energized-work principles and state the conditions under which each applies
Recite the key code requirements for conductor ampacity, overcurrent protection, grounding and motor circuits without notes
Complete a timed mixed-domain practice set and log every missed question by domain and cause
Re-derive the five calculations most often missed in weeks 1 through 6 from memory
Build a personal one-page formula and reference sheet covering power, motor current, loop scaling and fault current
Your checkpoint
A completed timed practice set with an error log and a final one-page reference sheet reviewed against the error log
Milestones
Week 2: Solve a three-phase power problem and a feeder voltage-drop problem cold, in under 15 minutes total, with correct units and no notes
Week 4: Explain a VFD's power conversion path and correctly size overload and short-circuit protection for a given motor nameplate without references
Week 6: Convert a process value to mA and back, and write a working start-stop interlock rung from scratch on a blank sheet
Week 8: Score at least 80 percent on the timed mixed-domain practice set and show every logged error mapped to a reviewed reference-sheet entry