EPA 608 Type II study materials
EPA 608 Type II study resources

EPA 608 Type II cheat sheet

EPA 608 Type II · Keep the key ideas within reach.

Quick reference

Leak Detection

  • Leak-repair thresholds apply to appliances holding 50 lb or more of refrigerant: 10% of charge per 12 months for comfort cooling, 20% for commercial refrigeration, 30% for industrial process refrigeration.

  • A chronically leaking appliance is one that leaks 125% or more of its applicable threshold within 12 months; it must be retrofitted or retired under a dated plan.

  • Normal repair deadline is 30 days after leak discovery; it extends to 120 days only when industrial process refrigeration must be shut down to make the repair.

  • After a repair: initial verification test within 30 days of the repair, and a follow-up verification test within 30 days after the repair is completed or the appliance returns to normal operating conditions.

  • Before use, confirm the electronic detector responds to the target refrigerant and is calibrated; some sensors respond poorly to HFOs and to specific blend components.

  • Refrigerant vapor is heavier than air: probe low points, flare nuts, Schrader ports, brazed joints, and coil headers, moving the probe tip slowly (about 1 in. per second).

  • UV dye plus a UV lamp locates slow leaks, but only dye approved by the compressor or component manufacturer may be added to the system.

  • Dry nitrogen is the only acceptable pressurizing gas for leak testing; oxygen or compressed air can explode when combined with refrigerant oil, and test pressure must stay below the component design limit.

  • Trace gas used to help locate a leak must be recovered after testing; it may not be vented to atmosphere.

Quick reference

Recovery Techniques

  • Type II certification covers high-pressure and very high-pressure appliances (R-12, R-22, R-134a, R-410A, R-502, R-13, R-503) but not small appliances or low-pressure chillers.

  • EPA recovery vacuum levels for high-pressure appliances: 0 psig for charges under 200 lb; 4 in. Hg (built before Nov 15, 1993) or 10 in. Hg (built after) at 200 lb or more; 15 in. Hg when a 200 lb or larger appliance is being disposed of.

  • Recovery cylinders must be DOT-approved, evacuated before first use, labeled with the refrigerant they contain, and filled to no more than 80% of capacity by weight.

  • R-410A must go into a cylinder with a 400 psig service rating (DOT 4BA400 / 4BW400) and through equipment rated for R-410A; R-22 service cylinders are not acceptable.

  • Push-pull liquid transfer is fastest for large charges; vapor recovery then finishes the job, and recovery stops when the recovery machine's rated vacuum is reached.

  • Self-contained recovery units have their own compressor; system-dependent (passive) devices rely on the appliance's compressor and internal pressure to move refrigerant.

  • Recovery equipment must never be used as an evacuation pump: it cannot reach a deep vacuum and can be damaged by running at its limit.

  • Recovered refrigerant may not be vented and may not be recharged into equipment until it has been recycled or reclaimed.

  • Short hoses with core depressors, low ambient temperature, or an ice/water bath on the recovery cylinder all speed up vapor recovery and reduce residual loss.

Quick reference

Recycling and Reclaiming

  • Recycling is on-site cleanup of recovered refrigerant (oil separation, filtering, moisture removal) for reuse; it does not restore refrigerant to AHRI 700 purity.

  • Reclaiming reprocesses refrigerant to AHRI Standard 700 purity and must be verified by laboratory analysis; only EPA-certified reclaimers may perform it.

  • Recycled refrigerant may be charged only into equipment owned by the same owner; reclaimed refrigerant may be used in any appliance.

  • Refrigerant of unknown identity or a mixture of refrigerants must not be blended with a known refrigerant; it can only be sent for reclamation or destruction.

  • Recovery and recycling equipment must be certified by an EPA-approved testing organization to meet 40 CFR 82.158 before it may be sold or used for 608 work.

  • Refrigerant failing purity tests (excess moisture, acid, particulates, non-condensables) is off-spec and must be reclaimed or destroyed, never installed in a system.

  • Single-use (disposable) refrigerant cylinders may not be refilled with recovered refrigerant; only DOT-approved refillable recovery cylinders are legal for that purpose.

Quick reference

Evacuation and Charging

  • Deep-vacuum target is 500 microns or lower; the micron gauge belongs at the system, not at the pump, because manifold gauges cannot resolve deep vacuum.

  • Standing (decay) vacuum test: isolate the pump at the target vacuum; a reading that keeps climbing indicates a leak or moisture still in the system.

  • Triple evacuation: pull a vacuum, break it with dry nitrogen to 0 psig, and repeat three times to sweep moisture and non-condensables out of the circuit.

  • Zeotropic blends such as R-410A are charged as liquid from the cylinder to prevent fractionation; charging by weight is the most accurate method for any blend.

  • TXV systems are verified by subcooling at the condenser outlet; fixed-orifice (piston) systems are verified by superheat against the manufacturer's target-superheat chart.

  • Liquid refrigerant is charged into the high side with the system off, or through a throttling device; liquid must never be slugged into a running compressor's suction line.

  • The system compressor is never used as a vacuum pump; it cannot reach deep vacuum, can overheat, and can pull air in through leak points.

  • Non-condensables raise discharge pressure and must be removed by recovery or reclamation, not by venting refrigerant from the system.

Quick reference

Safety and Regulatory Compliance

  • Section 608 of the Clean Air Act prohibits knowingly venting CFC and HCFC refrigerants during service, maintenance, or disposal; HFC venting is likewise restricted under the AIM Act.

  • Technicians must be certified for the appliance type they service (Type I, II, III, or Universal) before opening the refrigerant circuit or handling regulated refrigerant.

  • Owners of appliances with 50 lb or more of charge must keep records of refrigerant added, leak inspections, repairs, and verification tests for at least three years.

  • Refrigerant exposed to an open flame decomposes into toxic and corrosive gases including hydrogen fluoride, hydrogen chloride, and phosgene; the circuit must be recovered and purged before brazing.

  • Liquid refrigerant boils at very low temperature and causes frostbite and eye injury; gloves and safety glasses are required whenever breaking into a circuit.

  • Refrigerant vapor is heavier than air and displaces oxygen in pits, basements, and machine rooms; ventilation or a refrigerant monitor is required in occupied or confined spaces.

  • Cylinders are never heated above 125°F; warm water is acceptable, open flame or uncontrolled heaters are not, and cylinders are stored upright, secured, and valve-capped for transport.

  • Civil penalties for 608 violations can exceed $40,000 per day per violation, and venting violations may also trigger federal enforcement action.