EPA 608 Type II flashcards
EPA 608 Type II · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Comfort cooling leak threshold
- For comfort-cooling appliances holding 50 lb or more of refrigerant, the leak rate that triggers mandatory repair is 10% of the charge per 12 months.
- Commercial refrigeration threshold
- Commercial refrigeration appliances holding 50 lb or more of charge must be repaired when the annualized leak rate exceeds 20% per 12 months.
- Industrial process threshold
- Industrial process refrigeration appliances holding 50 lb or more of charge have a 30% per 12 months leak-rate threshold before repair is required.
- Chronic leaker definition
- An appliance that leaks 125% or more of its applicable threshold within 12 months is chronically leaking and must be retrofitted or retired under a plan.
- Leak repair deadline
- Repairs must be completed within 30 days of leak discovery, extendable to 120 days only when industrial process refrigeration must be shut down to make the repair.
- Verification test timing
- After repair, an initial verification test is done within 30 days, and a follow-up verification test within 30 days after repair completion or return to normal operation.
- Nitrogen pressure testing rule
- Dry nitrogen is the only acceptable pressurizing gas for leak testing; oxygen or compressed air can explode when mixed with refrigerant oil, and pressure must stay within design limits.
- Recovery cylinder 80% rule
- A recovery cylinder must never be filled above 80% of its capacity by weight, because liquid expansion as temperature rises can otherwise rupture the cylinder.
- R-410A cylinder rating
- R-410A requires a recovery cylinder rated for at least 400 psig service pressure, such as DOT 4BA400 or 4BW400; standard R-22 cylinders are not acceptable.
- Push-pull recovery method
- Push-pull uses the pressure difference between the appliance and the recovery cylinder to move liquid refrigerant quickly from a large charge before vapor recovery finishes.
- System-dependent recovery device
- Recovery equipment with no compressor of its own that relies on the appliance's compressor and internal pressure to move refrigerant into the recovery cylinder.
- No recovery as vacuum pump
- Recovery machines are not built to pull a deep vacuum and can be damaged by doing so; a separate vacuum pump must be used for evacuation.
- Type II appliance scope
- Type II certification covers high-pressure and very high-pressure appliances using refrigerants such as R-22, R-134a, R-410A and R-502, but not small appliances or low-pressure chillers.
- Recycling versus reclaiming
- Recycling cleans recovered refrigerant on site with filters and oil separation for reuse; reclaiming reprocesses it to AHRI 700 purity and requires laboratory verification.
- AHRI 700 standard
- AHRI Standard 700 sets the purity specification for reclaimed refrigerant, which must be analyzed and certified to meet that specification before resale.
- Recycled refrigerant ownership limit
- Refrigerant that has only been recycled may be charged only into equipment owned by the same owner; reclaimed refrigerant may be used in any appliance.
- Mixed refrigerant handling
- Different refrigerants must never be combined in one recovery cylinder; an unknown mixture can only be sent for reclamation or destruction.
- Reclaimer certification
- Only EPA-certified reclaimers may reprocess used refrigerant, and recovery or recycling equipment must be certified by an approved organization to 40 CFR 82.158.
- Off-spec refrigerant
- Refrigerant containing excess moisture, acid, particulates, or non-condensables fails purity testing and must be reclaimed or destroyed rather than reused.
- Deep vacuum target
- A high-pressure system is evacuated to 500 microns or lower, with a micron gauge connected at the system rather than relying on manifold gauge readings.
- Standing vacuum test
- After evacuation the pump is isolated and the micron gauge watched; a vacuum that keeps rising indicates a leak or moisture still in the system.
- Triple evacuation
- Pull a vacuum, break it with dry nitrogen to 0 psig, and repeat three times to sweep moisture and non-condensables out of the refrigerant circuit.
- Liquid charging blends
- Zeotropic blends such as R-410A must be charged as liquid from the cylinder to prevent fractionation, and charging by weight is the most accurate method.
- Subcooling charging check
- On systems with a thermostatic expansion valve, charge is verified by measuring subcooling at the condenser outlet and comparing it with the manufacturer's target.
- Superheat charging check
- On fixed-orifice systems, charge is verified with superheat using the manufacturer's target-superheat chart based on indoor wet-bulb and outdoor dry-bulb temperature.
- Compressor not a vacuum pump
- A system compressor must never be used to evacuate; it cannot reach deep vacuum, may overheat, and can draw air in through leak points.
- Section 608 venting ban
- The Clean Air Act prohibits knowingly venting CFC and HCFC refrigerants during service, maintenance, or disposal, and HFC venting is similarly restricted under the AIM Act.
- Recordkeeping requirement
- Owners of appliances with 50 lb or more of charge must keep records of refrigerant added, leak inspections, repairs, and verification tests for at least three years.
- Refrigerant flame decomposition
- Refrigerant exposed to an open flame breaks down into toxic and corrosive gases such as hydrogen fluoride and hydrogen chloride, so circuits must be recovered before brazing.
- Cylinder heating limit
- Refrigerant cylinders must never be heated above 125°F; warm water is acceptable, but open flame or an uncontrolled heater that can overheat the shell is not.
- Liquid refrigerant frostbite hazard
- Liquid refrigerant boils at extremely low temperature and can cause frostbite and eye injury on contact, so gloves and eye protection are required.
- Asphyxiation risk
- Refrigerant vapor is heavier than air, collects in pits and basements, and displaces oxygen; confined spaces require ventilation or a refrigerant monitor before entry.