EPA 608 Universal study materials
EPA 608 Universal study resources

EPA 608 Universal cheat sheet

EPA 608 Universal · Keep the key ideas within reach.

Quick reference

Type I - Small Appliances

  • Type I covers appliances charged at the factory with 5 lb or less of refrigerant: household refrigerators and freezers, window air conditioners, dehumidifiers, water coolers, vending machines. MVACs are excluded.

  • Recovery target when the appliance compressor is operational: at least 90% of the refrigerant charge.

  • Recovery target when the appliance compressor is not operational: at least 80% of the refrigerant charge.

  • A system-dependent (passive) recovery device may be used only on a small appliance whose own compressor runs; it uses that compressor, applied heat, or gravity to move refrigerant.

  • If the compressor will not run, a self-contained (active) recovery machine must be used to meet the 80% standard.

  • Leak-repair obligations (30-day repair, verification tests, chronic-leak reporting) apply to appliances holding 50 lb or more and therefore do not apply to small appliances.

  • Refrigerant recovered from a small appliance may be recycled on site and reused in equipment owned by the same owner; refrigerant changing ownership must be reclaimed to AHRI 700 purity.

  • Recovery equipment used on small appliances must be certified to the EPA-referenced standard (ARI/AHRI 740) for Type I equipment.

  • Sealed small systems without service ports are accessed with a line-piercing valve; the access point must be leak-checked before charging.

Quick reference

Type II - High- and Very-High-Pressure Appliances

  • Type II covers high-pressure and very-high-pressure equipment other than small appliances and MVACs, e.g. R-22, R-134a, R-404A, R-407C, R-410A, R-502 systems.

  • Evacuation level for appliances built after November 15, 1993: 10 inches of mercury vacuum.

  • Evacuation level for pre-November 15, 1993 appliances using HCFC-22: 0 inches of mercury vacuum (atmospheric).

  • Evacuation level for pre-November 15, 1993 appliances using other high-pressure refrigerants: 4 inches of mercury vacuum.

  • R-410A is a near-azeotropic R-32/R-125 blend running roughly 50–70% above R-22 pressures; only R-410A-rated gauges, hoses, and recovery equipment may be used, and it is charged as a liquid.

  • A recovery cylinder must never be filled above 80% of its capacity by weight; liquid expansion at higher temperature can rupture the cylinder.

  • Leak testing uses dry nitrogen, soap bubbles, or an electronic detector on the system charge; oxygen, compressed air, and acetylene are prohibited because of fire and explosion risk.

  • Appliances holding 50 lb or more must have leaks repaired within 30 days of discovery, then pass an initial verification test and a follow-up verification test.

  • Opened systems are dehydrated with a vacuum pump and micron gauge (about 500 microns, held stable); the system compressor is never used as a vacuum pump.

Quick reference

Type III - Low-Pressure Appliances

  • Type III covers low-pressure appliances such as centrifugal chillers using CFC-11 or HCFC-123, refrigerants that boil below atmospheric pressure.

  • Required evacuation level is 25 mm of mercury absolute (about 29.6 inches of mercury vacuum), the same for pre-1993 and post-1993 equipment.

  • Because the machine runs in a vacuum, every leak or opened line draws air and moisture inward; air raises condensing (head) pressure and moisture forms acids.

  • Low-pressure chillers are protected by a rupture disc, typically set near 15 psig, rather than a reseating relief valve; never pressurize above the disc rating, and replace a burst disc before charging.

  • A purge unit removes air and other non-condensables from the condenser; excessive purging wastes refrigerant and usually indicates a leak on the low side.

  • Moisture entering a low-pressure chiller can freeze at the evaporator and block flow; keep the system closed, use filter-driers, and leak-test with dry nitrogen plus trace refrigerant, soap bubbles, or an electronic detector.

  • Recovery is done liquid-first, then vapor, using a machine capable of pulling from a vacuum; cooling the recovery cylinder speeds transfer of low-pressure vapor.

  • CFC-11 has an ODP of 1.0 while HCFC-123 is a lower-ODP replacement refrigerant; both are low-pressure and both must be recovered, never vented.

Quick reference

Universal - All Equipment Types

  • Section 608 certifications: Type I small appliances, Type II high-pressure, Type III low-pressure, Universal (all three).

  • Venting refrigerant to the atmosphere during service, maintenance, repair, or disposal has been prohibited since July 1, 1992; recovered refrigerant must be recycled, reclaimed, or destroyed.

  • Ozone depletion potential: CFC-11 and CFC-12 = 1.0, HCFC-22 = 0.05, HFCs such as R-134a and R-410A = 0.

  • Refrigerant must be recovered before an appliance is scrapped; the last person in the disposal chain verifies recovery and keeps the documentation for three years.

  • Motor vehicle air conditioners fall under Section 609 and require separate certification; Section 608 covers stationary refrigeration and air-conditioning.

  • Never braze or torch a line that still holds refrigerant: decomposition produces toxic, corrosive gas. Recover the charge and purge with dry nitrogen first.

  • Never mix refrigerants in a recovery cylinder; mixed refrigerant cannot be reclaimed to specification and cylinders must be labeled with the refrigerant they contain.

  • Recovery cylinders must be DOT-approved, requalified on schedule, and free of damage or corrosion; do not fill an out-of-test cylinder.

  • Releases that occur during good-faith recovery attempts (for example residual hose vapor) are de minimis and are not venting violations.