EPA 608 Universal flashcards
EPA 608 Universal · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Type I appliance threshold
- Type I certification covers small appliances containing 5 pounds or less of refrigerant, such as household refrigerators, window air conditioners, dehumidifiers, and vending machines, but not motor vehicle air conditioners.
- Small appliance recovery: 90 percent
- When the compressor of a small appliance is operating, the technician must recover at least 90 percent of the refrigerant charge before opening, servicing, or disposing of the appliance.
- Small appliance recovery: 80 percent
- If a small appliance's compressor is not functioning, at least 80 percent of the refrigerant charge must be recovered before the appliance is opened or discarded.
- System-dependent recovery device
- A recovery device that relies on the appliance's own compressor, gravity, or applied heat to move refrigerant; it may be used on small appliances only while the compressor operates.
- Leak repair rule scope
- The mandatory 30-day leak repair and verification requirements apply only to appliances containing 50 or more pounds of refrigerant, so small appliances are exempt from those rules.
- Recycling versus reclaiming
- Recycling cleans refrigerant on site for reuse, often in the same appliance; reclaiming reprocesses refrigerant to AHRI 700 purity at a certified facility and is required before the refrigerant changes ownership.
- Line-piercing service valve
- Many small appliances are factory-sealed with no service ports, so technicians install a line-piercing valve to recover refrigerant, then leak-check the access point after service.
- Type II appliance examples
- Type II certification covers high-pressure and very-high-pressure equipment other than small appliances and motor vehicle air conditioners, for example R-22, R-134a, R-404A, and R-410A systems.
- Post-1993 evacuation level
- High-pressure appliances manufactured after November 15, 1993 must be evacuated to 10 inches of mercury vacuum before being opened for service or disposal.
- Pre-1993 R-22 evacuation
- For high-pressure appliances built before November 15, 1993 that contain HCFC-22, technicians must evacuate to 0 inches of mercury vacuum, meaning atmospheric pressure.
- Pre-1993 other refrigerant evacuation
- High-pressure appliances manufactured before November 15, 1993 that use refrigerants other than HCFC-22 must be evacuated to 4 inches of mercury vacuum before opening.
- R-410A pressure class
- R-410A is a near-azeotropic blend of R-32 and R-125 that operates at pressures roughly 50 to 70 percent higher than R-22, so only R-410A-rated gauges, hoses, and recovery equipment may be used.
- Eighty percent cylinder limit
- A recovery cylinder must never be filled beyond 80 percent of its capacity by weight, because liquid refrigerant expands as it warms and an overfilled cylinder can rupture.
- Nitrogen leak testing
- Dry nitrogen is the approved pressurizing gas for leak testing; oxygen, compressed air, and acetylene must never be used because they can cause fire, explosion, or oil breakdown.
- Fifty-pound leak repair rule
- Appliances holding 50 or more pounds of refrigerant must have leaks repaired within 30 days of discovery, followed by an initial verification test and a follow-up verification test.
- Micron gauge dehydration
- A vacuum pump and micron gauge dehydrate an opened high-pressure system; pulling to about 500 microns and holding a stable vacuum shows the system is dry and leak-free.
- Type III appliances
- Type III certification covers low-pressure appliances such as centrifugal chillers using CFC-11 or HCFC-123, refrigerants that boil below atmospheric pressure so the machine operates in a vacuum.
- Low-pressure evacuation level
- Low-pressure appliances must be evacuated to 25 millimeters of mercury absolute, about 29.6 inches of mercury vacuum, before opening; the same level applies to pre-1993 and post-1993 equipment.
- Air and moisture ingress
- Because low-pressure systems run below atmospheric pressure, any leak or open line pulls air and moisture in, which raises condensing pressure and forms acids that damage the system.
- Low-pressure rupture disc
- Low-pressure chillers are protected by a rupture disc, usually set near 15 psig, instead of a reseating relief valve; the system must never be pressurized above that setpoint.
- Purge unit function
- A purge unit removes air and other non-condensables that collect in a low-pressure chiller's condenser, restoring efficiency; excessive purging wastes refrigerant and signals a leak.
- Freeze-up from moisture
- Moisture carried into a low-pressure chiller can freeze at the evaporator and restrict refrigerant flow, so the system uses filter-driers and is never left open to the atmosphere.
- R-11 versus R-123
- CFC-11 has an ozone depletion potential of 1.0, while HCFC-123 is a lower-ODP replacement; both are low-pressure refrigerants that must be recovered and never vented.
- Low-pressure recovery sequence
- Recovering a low-pressure chiller usually means removing liquid first, then vapor with a recovery machine able to pull from a vacuum; cooling the recovery cylinder speeds the transfer.
- Venting prohibition
- Since July 1, 1992, knowingly venting ozone-depleting refrigerant to the atmosphere during service, maintenance, repair, or disposal has been prohibited; recovered refrigerant must be recycled, reclaimed, or destroyed.
- Ozone depletion potential values
- CFC-11 and CFC-12 have an ozone depletion potential of 1.0, HCFC-22 is about 0.05, and HFCs such as R-134a and R-410A have a value of zero.
- Final disposal responsibility
- Refrigerant must be recovered before an appliance is scrapped, and the last person in the disposal chain must verify that recovery and keep the documentation for three years.
- Section 609 versus 608
- Motor vehicle air conditioners are governed by Section 609 and require a separate certification; Section 608 covers stationary refrigeration and air-conditioning equipment only.
- Never braze charged lines
- Heating a line that still contains refrigerant can decompose halogenated refrigerant into toxic, corrosive gas; recover the charge and purge with dry nitrogen before brazing.
- No mixed refrigerants
- Never mix different refrigerants in one recovery cylinder; the mixture cannot be reclaimed to specification and must be destroyed, and each cylinder must be labeled with its refrigerant.
- Cylinder requalification
- DOT recovery cylinders must be pressure-tested and requalified on a set schedule, and cylinders that are damaged, corroded, or past their test date must not be filled.
- De minimis release
- Small releases that occur during good-faith attempts to recover refrigerant, such as residual vapor left in hoses, are de minimis and are not violations of the venting prohibition.