CDCP key terms
CDCP · Get comfortable with the vocabulary.
- Tier Classification (I–IV)
- Related: Concurrently Maintainable, Fault Tolerance, Redundancy (N, N+1, 2N)
A four-level scheme describing data centre availability and fault tolerance, from Tier I (basic capacity, no redundancy) to Tier IV (fully fault tolerant with concurrently maintainable critical paths).
- Concurrently Maintainable
- Related: Tier Classification (I–IV), Fault Tolerance, Maintenance Window
A design property allowing any piece of critical equipment to be removed for maintenance or repair without shutting down the IT load, typically associated with Tier III and IV topologies.
- Fault Tolerance
- Related: Redundancy (N, N+1, 2N), Concurrently Maintainable, Single Point of Failure
The ability of a facility to sustain an unplanned failure of any single component in the critical path without interrupting the IT load, achieved through redundant capacity and automatic failover.
- Redundancy (N, N+1, 2N)
- Related: Fault Tolerance, Single Point of Failure, Load Bank
Spare capacity provided beyond the minimum needed to carry the load. N is the minimum, N+1 adds one spare unit, and 2N duplicates the entire capacity for full backup.
- Single Point of Failure
- Related: Redundancy (N, N+1, 2N), Fault Tolerance, Critical Path
Any component whose failure would interrupt the entire IT load because no alternate path or spare capacity exists to carry the load during its outage.
- Critical Path
- Related: Single Point of Failure, Concurrently Maintainable, UPS (Uninterruptible Power Supply)
The sequence of power, cooling, and control components that must function for IT equipment to remain powered and cooled, from utility entry through to the rack.
- TIA-942
- Related: Tier Classification (I–IV), Structured Cabling, Cross-Connect
A widely used data centre infrastructure standard covering topology, cabling, power, cooling, and security requirements, with an accompanying tier rating framework and annexes for related facilities.
- PUE (Power Usage Effectiveness)
- Related: DCiE (Data Centre Infrastructure Efficiency), Raised Floor Plenum, Free Cooling
The ratio of total facility power to IT equipment power. A value of 1.0 is ideal; higher values indicate more energy consumed by cooling, losses, and other support systems.
- DCiE (Data Centre Infrastructure Efficiency)
- Related: PUE (Power Usage Effectiveness), Free Cooling
The reciprocal of PUE, expressed as a percentage, representing the share of total facility power that actually reaches IT equipment; equal to 1 divided by PUE.
- ASHRAE Allowable Envelope
- Related: Supply Air Temperature, Relative Humidity Control, Hot Aisle / Cold Aisle
The range of inlet temperature and humidity conditions within which IT equipment is permitted to operate, defined by ASHRAE classes A1 through A4 and used in cooling design.
- Structured Cabling
- Related: Cross-Connect, TIA-942, Meet-Me Room
A standardized hierarchical cabling system using defined media, connectors, and pathways, organized into backbone and horizontal distribution to support reliable, manageable data centre connectivity.
- Cross-Connect
- Related: Structured Cabling, Meet-Me Room
A patching point where cables terminate and are interconnected, used in main distribution, horizontal distribution, or equipment areas to manage and reconfigure connections flexibly.
- Meet-Me Room
- Related: Cross-Connect, Structured Cabling
A controlled space where external carriers and service providers terminate their networks and interconnect with the data centre's internal cabling infrastructure.
- Utility Service Entrance
- Related: Automatic Transfer Switch (ATS), Generator (Genset), Critical Path
The point where electrical power from the utility grid enters the facility, including transformers, switchgear, and metering that define the site's available capacity and reliability.
- UPS (Uninterruptible Power Supply)
- Related: Double Conversion (Online) UPS, Battery String, Automatic Transfer Switch (ATS)
A system that provides conditioned, continuous power to IT loads during brief outages and transfers to generator or utility power, bridging the gap without interruption.
- Double Conversion (Online) UPS
- Related: UPS (Uninterruptible Power Supply), Battery String, Power Factor
A UPS topology that converts incoming AC to DC for the battery and back to clean AC for the load, isolating equipment from sags, surges, and frequency variations at all times.
- Battery String
- Related: UPS (Uninterruptible Power Supply), Automatic Transfer Switch (ATS), Load Bank
A series-connected group of batteries providing DC energy to a UPS during outages; its runtime, age, temperature, and maintenance determine the ride-through available before generator power is ready.
- Automatic Transfer Switch (ATS)
- Related: Generator (Genset), Utility Service Entrance, Battery String
A device that senses loss of the primary power source and automatically switches the load to an alternate source, such as a generator, within a defined transfer time.
- Generator (Genset)
- Related: Automatic Transfer Switch (ATS), Load Bank, Utility Service Entrance
An engine-driven alternator that supplies backup electrical power when utility power fails, characterized by its rated capacity, fuel supply, startup time, and load acceptance capability.
- Load Bank
- Related: Generator (Genset), Battery String, Redundancy (N, N+1, 2N)
A resistive or reactive device used to apply controlled electrical load to a generator or UPS for testing, commissioning, and verifying capacity without risking live IT equipment.
- PDU (Power Distribution Unit)
- Related: Busway, Branch Circuit, Power Density (kW per Rack)
Equipment that distributes electrical power to racks and IT devices; floor-mounted PDUs step down voltage and feed branch circuits, while rack PDUs provide outlet-level distribution.
- Busway (Busbar)
- Related: PDU (Power Distribution Unit), Power Density (kW per Rack)
A prefabricated, modular electrical distribution system using copper or aluminum conductors in a housing, allowing tap-off boxes to be added or moved above racks without recabling.
- Branch Circuit
- Related: PDU (Power Distribution Unit), Power Density (kW per Rack)
The final circuit from a panelboard or PDU to the load, protected by an overcurrent device sized to the conductor ampacity and the connected equipment requirements.
- Power Density (kW per Rack)
- Related: PDU (Power Distribution Unit), Hot Aisle / Cold Aisle, Liquid Cooling
The electrical load a rack position is designed to support, used to plan cooling, power distribution, and floor loading; high-density racks may exceed 15–20 kW each.
- Power Factor
- Related: Double Conversion (Online) UPS, Generator (Genset)
The ratio of real power (kW) to apparent power (kVA) in an AC circuit; low power factor increases current for the same useful work and affects UPS and generator sizing.
- Hot Aisle / Cold Aisle
- Related: Containment, Supply Air Temperature, CRAC / CRAH Unit
An arrangement where racks face each other in alternating rows so cold supply air enters rack fronts and hot exhaust air is collected from rack rears, reducing mixing and improving cooling efficiency.
- Containment
- Related: Hot Aisle / Cold Aisle, Raised Floor Plenum, Free Cooling
Physical barriers such as doors, panels, and roofs that enclose either the cold aisle or hot aisle to prevent air mixing between supply and return streams, improving cooling capacity and efficiency.
- CRAC / CRAH Unit
- Related: Chiller, Raised Floor Plenum, Supply Air Temperature
Computer room air conditioning (direct expansion) or air handling (chilled water) units that cool and circulate air in the data hall; CRAH units use chilled water coils and typically lack built-in compressors.
- Chiller
- Related: CRAC / CRAH Unit, Free Cooling, PUE (Power Usage Effectiveness)
A refrigeration machine that removes heat from water in a chilled water loop serving CRAH units or other cooling equipment; its efficiency and redundancy strongly affect overall facility PUE.
- Free Cooling (Economizer)
- Related: Chiller, PUE (Power Usage Effectiveness), Containment
A cooling strategy that uses cool outdoor air or water instead of mechanical refrigeration when ambient conditions allow, reducing compressor energy and lowering PUE.
- Raised Floor Plenum
- Related: Hot Aisle / Cold Aisle, CRAC / CRAH Unit, Containment
The space between a structural slab and a raised access floor, often used to deliver conditioned air to perforated tiles or to route cabling and piping beneath the data hall.
- Supply Air Temperature
- Related: ASHRAE Allowable Envelope, CRAC / CRAH Unit, Hot Aisle / Cold Aisle
The temperature of air delivered to IT equipment inlets, a key control setpoint balancing equipment reliability against cooling energy use and condensation risk.
- Relative Humidity Control
- Related: ASHRAE Allowable Envelope, Supply Air Temperature
Managing moisture in the data hall to avoid electrostatic discharge at low humidity and condensation or corrosion at high humidity, typically through humidification and dehumidification equipment.
- Liquid Cooling
- Related: Power Density (kW per Rack), CRAC / CRAH Unit
Cooling IT equipment by circulating liquid directly to or near heat sources, such as cold plates or immersion tanks, enabling higher rack power densities than air cooling alone.
- CFD (Computational Fluid Dynamics)
- Related: Hot Aisle / Cold Aisle, Containment, Supply Air Temperature
Numerical modeling of airflow, temperature, and pressure in a data hall, used to predict hot spots, evaluate containment options, and validate cooling designs before construction.
- Maintenance Window
- Related: Concurrently Maintainable, Change Management, Load Bank
A scheduled period during which equipment may be taken out of service for testing, repair, or upgrades, planned to avoid impact on IT loads in concurrently maintainable designs.
- Change Management
- Related: Maintenance Window, MOP (Method of Procedure), SOP (Standard Operating Procedure)
A controlled process for reviewing, approving, scheduling, and documenting changes to infrastructure or IT systems, reducing the risk of unplanned outages from undocumented modifications.
- MOP (Method of Procedure)
- Related: SOP (Standard Operating Procedure), Change Management, EOP (Emergency Operating Procedure)
A detailed, step-by-step document describing how to perform a specific task safely, including prerequisites, verification steps, rollback plans, and approvals required before execution.
- SOP (Standard Operating Procedure)
- Related: MOP (Method of Procedure), EOP (Emergency Operating Procedure), Change Management
A documented routine procedure for operating equipment consistently and safely, used for recurring activities such as transfers, startups, shutdowns, and inspections.
- EOP (Emergency Operating Procedure)
- Related: SOP (Standard Operating Procedure), MOP (Method of Procedure), Incident Management
A predefined response procedure for emergencies such as power loss, fire, or cooling failure, specifying actions, responsibilities, and escalation to protect people and IT loads.
- Incident Management
- Related: EOP (Emergency Operating Procedure), Change Management
The process of detecting, logging, responding to, and resolving service disruptions, including root cause analysis and corrective actions to prevent recurrence.