Business, Financial Management, and Contracting Practices

  • Gross profit = sales − direct job costs; net profit = gross profit − overhead expenses.

  • Selling price for a target margin = cost ÷ (1 − target margin %); markup % is calculated on cost, margin % on selling price.

  • Break-even sales = annual overhead ÷ gross margin percentage.

  • In Florida, a Notice to Owner must be served before first furnishing or within 45 days after first furnishing to preserve lien rights.

  • A claim of lien in Florida must be recorded within 90 days after final furnishing of labor, services, or materials.

  • Labor burden = base wage + payroll taxes + workers' compensation + insurance + benefits; it must be added to the base labor rate before pricing.

  • Written, signed change orders before extra work is performed protect the contractor's right to payment for changes.

Quick reference

Florida Building Code, Statutes, and Contractor Licensing Regulations

  • The Florida Building Code is enforced by local building departments; a permit is required before HVAC installation and a final inspection is required before occupancy.

  • A state-certified contractor may work anywhere in Florida; a state-registered contractor may work only in the jurisdictions where registered.

  • The Florida Construction Industry Licensing Board (CILB) under DBPR licenses HVAC contractors and investigates complaints.

  • The Florida Energy Code sets minimum SEER2, EER2, and HSPF2 efficiencies by equipment type and climate zone.

  • HVAC equipment in the wind-borne debris region requires Florida Product Approval or a Miami-Dade County Notice of Acceptance.

  • A Notice of Commencement is recorded by the owner before work begins and preserves the owner's and lender's lien defenses.

  • Section 489.113, Florida Statutes, defines the scope of work licensed contractors may perform; unlicensed contracting is a criminal offense.

Quick reference

Load Calculations and System Sizing

  • Manual J is the ACCA room-by-room load calculation procedure; square-foot rules of thumb are not acceptable for sizing.

  • Total cooling load = envelope conduction + infiltration + internal gains + latent load.

  • Sensible airflow: CFM = sensible BTU/h ÷ (1.08 × temperature difference °F).

  • Latent airflow: CFM = latent BTU/h ÷ (0.68 × humidity ratio difference in grains).

  • One ton of refrigeration = 12,000 BTU/h; nominal cooling airflow is 400 CFM per ton.

  • Sensible heat ratio (SHR) = sensible load ÷ total load; it determines the required apparatus dew point.

  • Florida summer design conditions are roughly 92–95°F dry bulb and 75–77°F wet bulb with indoor design of 75°F and 50% RH.

  • The duct load factor and ventilation load must be added to the room load before equipment selection.

Quick reference

Equipment Selection, Installation, and Start-Up

  • Manual S is used to select equipment whose capacity meets the Manual J load at design conditions, not at nominal rating conditions.

  • Match indoor and outdoor units per the AHRI directory; mismatched coils void rated capacity and efficiency.

  • Charge a TXV system by subcooling and a fixed-orifice system by superheat, following the manufacturer's chart.

  • Evacuate refrigerant lines to 500 microns and hold the vacuum to confirm no moisture or leaks remain.

  • Purge with dry nitrogen while brazing and never braze with refrigerant in the lines.

  • A condensate trap must offset the fan static pressure; a secondary drain pan with a float switch is required where damage may occur.

  • Steady-state temperature split is typically 16–22°F between return and supply air at 350–450 CFM per ton.

  • Start-up checks include electrical voltage and amp draw, refrigerant charge, airflow, condensate drainage, and control operation.

Quick reference

Ductwork Design, Air Distribution, and Ventilation

  • Manual D sizes ducts using the available static pressure and total effective length to establish the friction rate.

  • Typical duct velocities are 600–900 FPM in supply trunks, 500–700 FPM in returns, and 400–700 FPM in branches.

  • Flex duct must be fully extended, supported every 4–5 feet, and bent no tighter than 1.5 times its diameter.

  • Seal all duct joints and seams with mastic or approved tape; the Florida Energy Code requires duct leakage testing.

  • Duct insulation in Florida is typically R-6 minimum, with R-8 used in attics and exposed locations.

  • Each room needs a return path via a transfer grille or jumper duct; closed doors otherwise pressurize the room.

  • ASHRAE 62.2 requires mechanical ventilation; intermittent bath exhaust is 50 CFM and kitchen exhaust is 100 CFM.

  • A typical residential blower static pressure budget is 0.5 in. w.c. total external static.

Quick reference

Refrigeration Principles and Refrigerant Handling

  • Superheat = suction line temperature − evaporating saturation temperature.

  • Subcooling = condensing saturation temperature − liquid line temperature.

  • Compression ratio = discharge pressure (psia) ÷ suction pressure (psia).

  • R-410A is a near-azeotropic blend and must be charged as a liquid to avoid fractionation.

  • EPA Section 608 certification is required to handle refrigerants; intentional venting is prohibited.

  • Pressure-test with dry nitrogen, then evacuate to 500 microns; never use refrigerant to leak-test.

  • High superheat indicates undercharge or a restriction; high subcooling indicates overcharge or a liquid-line restriction.

  • POE oil is hygroscopic and absorbs moisture quickly, so lines must remain sealed until evacuation.

Quick reference

Electrical Systems, Controls, and Motors

  • Ohm's law: V = I × R; power: P = V × I for resistive loads.

  • Discharge capacitors before testing and use a meter rated for the voltage present.

  • RLA is running load amps and LRA is locked rotor amps; LRA is the starting current surge.

  • Standard 24V thermostat terminals: R = power, W = heat, Y = cool, G = fan, C = common.

  • A disconnect must be within sight of the equipment and lockout/tagout must be applied before service.

  • Size conductors per ampacity and the breaker per the nameplate MCA and MOP.

  • To reverse a three-phase motor, swap any two of the three supply leads.

  • GFCI protection is required in wet and outdoor locations.

Quick reference

Safety, Jobsite Practices, and Environmental Compliance

  • Fall protection is required at 6 feet or more; ladders are set at a 4:1 slope.

  • Recovery cylinders must not be filled beyond 80% of their water capacity by weight.

  • Never vent refrigerant; recover, recycle, or reclaim it per EPA Section 608.

  • Wear gloves and goggles when handling liquid refrigerant; it causes frostbite at −50°F or below.

  • Combustion appliances require CO testing and proper flue draft to prevent carbon monoxide poisoning.

  • Lockout/tagout isolates electrical energy before service or repair.

  • Heat stress prevention includes hydration, shade, and scheduled rest breaks.

  • Used oil, filters, and refrigerant cylinders are regulated wastes and must be disposed of properly.