Replacement Sizing After an Envelope Retrofit

GA HVAC · Put your knowledge to work in context.

All case studies

Replacement Sizing After an Envelope Retrofit

A 1978 ranch in Atlanta, 2,000 ft² with 8 ft ceilings. The owner has replaced the windows, air-sealed the attic floor, and blown R-38 over existing R-11; the duct system is still R-4 flex lying on the attic floor of a vented attic that reaches 135°F in August. A block Manual J (92°F DB/74°F WB outdoor, 75°F/50% RH indoor, duct gain included) returns 27,000 Btu/h total, 21,000 Btu/h sensible, and 6,000 Btu/h latent. Duct leakage to outdoors measures 180 CFM25. The existing 3-ton, 10 SEER split still keeps up on all but the hottest afternoons, but the house feels clammy. The owner wants a like-for-like replacement and asks whether a 2-ton unit would 'save money.'

1. What nominal capacity do you select, and what must you complete before you commit to a tonnage?

Read the worked answer

Start from the load, not from the old nameplate. The 3-ton unit was sized for a leaky 1978 envelope and is now roughly 33% oversized against a 27,000 Btu/h design load.

Check the latent side first. 6,000 Btu/h latent ÷ 1,070 Btu/lb ≈ 5.6 lb/h of condensate, about 0.67 gal/h. Required SHR = 21,000/27,000 = 0.78. A 2-ton match rated 24,000 Btu/h at ARI 80/67 entering delivers about 18,000 sensible / 6,000 latent. Our actual entering air is 75°F DB / 63°F WB, which derates capacity roughly 5–8%, so real sensible output lands near 16,500–17,000 - short of the 21,000 sensible load. A 2-ton is not automatically wrong; it is wrong as long as the ducts stay where they are.

Three steps before committing:

  1. Pull manufacturer expanded ratings at 75 DB/63 WB entering and 95°F outdoor for the specific condenser/coil/air-handler match (Manual S), not the ARI headline number.
  2. Run Manual T so the air handler is not undersized for the room-by-room airflow the new envelope still needs.
  3. Price the duct remediation as part of the job. Sealing and encapsulating (or relocating) the attic ducts removes duct gain and the 180 CFM25 of outdoor leakage - typically 3,000–5,000 Btu/h of sensible load here.

Decision: If the ducts are fixed, a 2-ton match, set at 350–400 CFM/ton with a variable-speed air handler and dehumidification control, covers the revised load. If the owner refuses the duct work, select 2.5 tons with a matched expanded rating that shows at least 21,000 Btu/h sensible at actual entering conditions. Do not install another 3-ton.

2. The current system 'keeps up' but the house is clammy. Explain the mechanism and why oversizing makes it worse.

Read the worked answer
  • A 36,000 Btu/h unit on a 27,000 Btu/h load is running near 75% of capacity at design, so it satisfies the thermostat quickly and cycles. In partial-load operation the coil's sensible heat ratio rises - it removes fewer Btu of moisture per Btu of sensible cooling - and the entering wet-bulb at the coil drops as indoor humidity climbs.
  • Meanwhile the attic ducts are pulling 135°F air in through 180 CFM25 of leakage and adding sensible gain, so the unit is working on dry-bulb load while the latent load (6,000 Btu/h, driven by the Atlanta design wet bulb) goes unaddressed.
  • Going to 2 tons without fixing the ducts would fix nothing: the coil would run longer but the load would still exceed capacity on design day.
  • Complaints of clamminess with short runtime are the classic signature of oversizing plus duct gain, not of a refrigerant problem. Confirm by logging runtime and indoor RH before condemning the equipment.

3. What measurements do you require at start-up to accept the job?

Read the worked answer
  • External static pressure versus the air handler's rated ESP; compare to the value used in the expanded rating table.
  • Airflow: verify within ±10% of design at 350–400 CFM/ton (a lower blower setting is a legitimate moisture-control lever in this climate - document whichever setting is used).
  • Temperature split across the coil, 18–22°F at steady state, with the filter clean and all registers open.
  • Superheat/subcooling per the manufacturer's charging chart for the actual indoor and outdoor conditions.
  • Duct leakage after remediation, targeted at 10% or less of fan flow (or the adopted energy code's CFM25 per 100 ft² threshold) rather than the 180 CFM25 found today.
  • Room-by-room temperature verification, plus indoor RH maintained near 50% at design - the metric the owner actually complained about.