Manual J
Manual J is the ACCA method for calculating residential heating and cooling loads from room-by-room envelope, infiltration, internal gain, and design-condition inputs.
Manual S
ACCA Manual S is the equipment selection procedure that matches manufacturer performance data to calculated Manual J loads and checks sensible and latent capacity at design conditions.
Sensible heat formula
For standard air near sea level, sensible heat in Btu/h equals 1.08 times airflow in cfm times the dry-bulb temperature difference in degrees Fahrenheit.
Ton of cooling
One ton of cooling equals 12,000 Btu per hour, the approximate heat removal rate of one ton of ice melting over 24 hours.
Superheat
Superheat is the difference between measured suction-line temperature and refrigerant saturation temperature at the same suction pressure; it indicates evaporator feed and protects the compressor.
Subcooling
Subcooling is the difference between refrigerant saturation temperature at liquid-line pressure and measured liquid-line temperature; it indicates liquid seal and charge in the condenser.
TXV function
A thermostatic expansion valve meters refrigerant into the evaporator and modulates flow to maintain a set superheat at the evaporator outlet under changing load.
A2L refrigerant
A2L refrigerants have lower flammability than A3 refrigerants but are mildly flammable; examples include R-32 and R-454B, and they require specific handling and charge limits.
AFUE
Annual fuel utilization efficiency is the ratio of annual heat output to annual fuel energy input for a furnace or boiler, expressed as a percentage on the rating plate.
Furnace temperature rise
Furnace temperature rise in degrees Fahrenheit equals output Btu/h divided by 1.08 times measured airflow in cfm; it must fall within the nameplate range.
Heat pump balance point
The balance point is the outdoor temperature at which heat pump capacity equals building heat loss; below it, supplementary heat is needed to maintain indoor temperature.
Condensing furnace condensate
A condensing furnace produces acidic water condensate from flue-gas water vapor; it must drain through a trap and often a neutralizer to a suitable location.
Equivalent length
Equivalent length converts duct fitting and component pressure losses into added straight-duct length so total effective length can be used with available static pressure.
ASHRAE 62.2
ASHRAE Standard 62.2 sets ventilation and acceptable indoor air quality requirements for low-rise residential buildings, including whole-house and local exhaust ventilation rates.
Duct leakage
Duct leakage is air escaping or entering a duct system through seams, joints, and penetrations; it reduces delivered airflow and efficiency and is measured by pressurization testing.
Sediment trap
A sediment trap, or drip leg, is a capped pipe section installed at a gas appliance connection to collect dirt and condensate before gas enters the controls.
Natural gas manifold pressure
Natural gas appliance manifold pressure is commonly about 3.5 inches water column, but the nameplate rating for the specific appliance always governs adjustment.
Dielectric union
A dielectric union separates dissimilar metals, such as copper and steel, to reduce galvanic corrosion at a piping connection while maintaining a pressure-tight joint.
MCA
Minimum circuit ampacity is the minimum conductor ampacity listed on HVAC equipment nameplate, calculated with code-required margins for the largest motor and continuous load.
Capacitor microfarad test
A capacitor is tested by measuring microfarads with a meter after discharging it; a reading outside the nameplate tolerance indicates a weak or failed capacitor.
C terminal
The C terminal is the common side of the 24-volt transformer secondary; it provides continuous power for thermostats and controls that require a common wire.
Nitrogen purge
Nitrogen purge means flowing dry nitrogen through refrigerant piping while brazing to displace oxygen and prevent internal oxidation scale that can damage compressors and valves.
500 microns
A vacuum of about 500 microns absolute indicates removal of moisture and noncondensables from a refrigerant system; a standing decay test confirms the vacuum holds.
Pitot tube traverse
A pitot tube traverse measures velocity pressure at multiple points across a duct; average velocity pressure is converted to airflow using duct area and air density.
Fan laws
Fan laws state that airflow varies with speed, static pressure with speed squared, and power with speed cubed for a fixed fan and system.
Delta T
Delta T is the temperature difference between return and supply air across equipment; it is compared with the expected range to assess airflow, charge, and capacity.
Frozen evaporator causes
A frozen evaporator can result from low airflow, low refrigerant charge, restricted metering, or low return-air temperature; each causes coil temperature below freezing.
Lockout/tagout
Lockout/tagout isolates hazardous energy, such as electrical or gas, with locks and tags before servicing equipment to prevent unexpected startup or release.
GFCI
A ground-fault circuit interrupter detects imbalance between hot and neutral conductors and opens the circuit to reduce shock hazard in wet or outdoor locations.
Permit
A permit is official authorization from the local authority to install or alter regulated equipment; work must follow approved plans and pass required inspections.
Manual D
ACCA Manual D is the residential duct design method that selects duct sizes and fittings based on available static pressure, total effective length, and room airflow.
Combustion analysis
Combustion analysis measures flue-gas oxygen, carbon dioxide, temperature, and carbon monoxide to calculate excess air and steady-state efficiency and verify safe burner operation.