GA HVAC study materials
GA HVAC study resources

GA HVAC cheat sheet

GA HVAC · Keep the key ideas within reach.

Quick reference

HVAC System Design, Load Calculation, and Equipment Selection

  • ACCA Manual J calculates room-by-room heating and cooling loads; Manual S selects equipment; Manual D sizes ducts; Manual T addresses air distribution.

  • Sensible Btu/h = 1.08 × cfm × ΔT; latent Btu/h = 0.68 × cfm × Δgrains; total Btu/h = 4.5 × cfm × Δh for standard air near sea level.

  • 1 ton of cooling = 12,000 Btu/h; 1 kW = 3,412 Btu/h.

  • Sensible heat ratio (SHR) = sensible load ÷ total load; selected equipment should meet the design sensible and latent loads, not merely nominal tonnage.

  • Typical design conditions use 1% cooling design dry-bulb and 99% heating design temperature; indoor design is commonly 75°F cooling and 70°F heating unless specified.

  • Equipment capacity must be checked at design entering wet-bulb, outdoor temperature, and airflow using manufacturer performance data.

  • Oversized cooling equipment short-cycles, dehumidifies poorly, and can reduce equipment life.

  • Available static pressure for duct design = fan rated external static pressure minus pressure drops of filters, coils, humidifiers, and accessories.

Quick reference

Refrigeration Cycle, Components, and Refrigerants

  • Superheat = suction-line temperature minus saturation temperature at suction pressure; target value depends on metering type and manufacturer data.

  • Subcooling = saturation temperature at liquid-line pressure minus liquid-line temperature; TXV systems are commonly charged by subcooling.

  • The four basic components are compressor, condenser, metering device, and evaporator; the cycle moves heat from a low-temperature source to a higher-temperature sink.

  • A TXV modulates refrigerant flow to maintain evaporator outlet superheat; a fixed orifice relies on charge and operating conditions.

  • Low superheat indicates overfeed or floodback risk; high superheat indicates a starved evaporator, undercharge, or restriction.

  • Zeotropic refrigerant blends have temperature glide; they must be charged as liquid to avoid fractionation.

  • EPA Section 608 prohibits venting regulated refrigerants and requires certified technicians for recovery.

  • R-410A operates at roughly 50–70% higher pressure than R-22 and uses POE lubricant, which readily absorbs moisture.

  • A2L refrigerants such as R-32 and R-454B are mildly flammable and subject to charge, ventilation, and ignition-source rules.

Quick reference

Heating Equipment and Systems (Furnaces, Boilers, Heat Pumps)

  • AFUE = annual heat output ÷ annual fuel energy input × 100; condensing appliances typically exceed 90% AFUE.

  • Furnace temperature rise in °F = output Btu/h ÷ (1.08 × measured cfm); measured rise must fall within the nameplate range.

  • Natural gas manifold pressure is commonly about 3.5 in. w.c.; LP manifold pressure is commonly 10–11 in. w.c.; the appliance nameplate governs.

  • A condensing furnace recovers latent heat, produces acidic condensate, and requires a trapped drain and approved vent material.

  • Heat pump balance point is the outdoor temperature where heat pump capacity equals building heat loss; below it, auxiliary heat supplements capacity.

  • Defrost cycles remove outdoor-coil frost by reversing refrigerant flow or using hot gas; auxiliary heat may temper supply air during defrost.

  • A boiler relief valve setting must not exceed the boiler maximum allowable working pressure; the expansion tank absorbs thermal expansion.

  • Heat pump COP = heating output ÷ electrical input; COP varies with outdoor temperature and refrigerant lift.

  • Category I natural-draft appliances require proper flue draft and cannot share venting unless listed and approved for common venting.

Quick reference

Air Distribution, Ductwork, and Ventilation

  • Friction rate in in. w.c. per 100 ft = available static pressure ÷ total effective length.

  • Total effective length = straight duct length plus equivalent lengths of fittings, transitions, and components.

  • Airflow: cfm = 4005 × √VP for standard air, where VP is velocity pressure in in. w.c.

  • ASHRAE 62.2 governs residential whole-building and local exhaust ventilation; ASHRAE 62.1 governs most commercial buildings.

  • Return air must have a path from each room; undersized returns raise static pressure and reduce supply airflow.

  • Flex duct should be fully extended, properly supported, and kept with gradual bends; sharp bends add pressure loss.

  • Balancing dampers belong in branch ducts and at terminals; volume dampers should not be used to compensate for undersized ducts.

  • Duct leakage testing pressurizes the duct system and measures leakage airflow; sealed ducts reduce delivered-air losses.

Quick reference

Piping, Fittings, and Fuel Gas Systems

  • Gas pipe sizing uses the longest run, total connected load, allowable pressure drop, gas specific gravity, and pipe material tables.

  • A sediment trap or drip leg is installed at the appliance connection before controls; it is capped and accessible.

  • Natural gas service pressure is typically about 7 in. w.c.; appliance manifold pressure is set according to the nameplate.

  • CSST must be bonded according to manufacturer instructions and code; bonding reduces lightning-related arc damage risk.

  • Dielectric unions separate copper and steel to limit galvanic corrosion at piping connections.

  • Condensate drains require a trap to prevent flue gas or air bypass; trap depth must exceed the pressure difference.

  • Refrigerant line sizing must provide oil return at minimum capacity and acceptable pressure drop at design capacity.

  • Flue connectors require upward slope and clearance from combustibles according to listing and code.

Quick reference

Electrical Power, Motors, and HVAC Controls

  • Ohm's law: E = I × R; power: P = E × I for resistive loads; single-phase P = V × A × power factor.

  • MCA is the minimum circuit ampacity listed on the nameplate; MOP is the maximum overcurrent protective device size.

  • A capacitor stores charge; discharge it before testing microfarads, and replace it if the reading is outside nameplate tolerance.

  • Low-voltage thermostat terminals: R = 24V power, W = heat, Y = cooling, G = fan, C = common.

  • PSC motors use a run capacitor; ECM motors are electronically commutated and often operate in constant-torque or constant-airflow modes.

  • VFDs change motor speed and frequency; they require proper grounding and shielded cable to limit electrical noise.

  • A disconnect must be within sight of and readily accessible from the equipment it serves.

  • Motor current above nameplate FLA can indicate overload, bad bearings, low voltage, or restricted airflow.

Quick reference

Installation, Start-up, and Commissioning

  • Braze with dry nitrogen flowing through the piping to prevent internal oxidation scale.

  • Evacuate to 500 microns or lower and perform a standing vacuum decay test before charging.

  • Weigh in refrigerant when the system is empty or when manufacturer instructions require total charge.

  • Verify supply voltage and phase balance against nameplate; incorrect phase rotation reverses three-phase compressors.

  • Record airflow, temperature rise or drop, superheat, subcooling, static pressure, and amp draw at start-up.

  • Perform combustion analysis on fuel-burning equipment by measuring O2, CO2, CO, flue temperature, and draft.

  • Confirm condensate drainage, trap operation, and absence of water leaks before completing commissioning.

  • Functional testing verifies economizer sequences, safeties, and lockout functions.

Quick reference

Testing, Adjusting, and Balancing (TAB)

  • Pitot traverse: average velocity pressure across a duct; cfm = 4005 × √VP × duct area in ft².

  • Fan laws: cfm varies with rpm; static pressure with rpm squared; brake horsepower with rpm cubed.

  • Proportional balancing adjusts branch dampers so each terminal receives its design percentage before final readout.

  • Static pressure profile readings locate restrictions and excessive losses across filters, coils, and ducts.

  • Temperature difference across coils and equipment verifies airflow and capacity within expected ranges.

  • Instruments must be calibrated; record model, serial number, and calibration date in the TAB report.

  • The final TAB report includes design versus actual airflow, pressures, temperatures, and adjustments made.

Quick reference

Maintenance, Troubleshooting, and Repair

  • An air temperature difference outside the expected range can indicate low airflow, incorrect charge, or a dirty coil.

  • High superheat with low subcooling suggests undercharge or a liquid-line restriction; low superheat suggests overcharge or overfeed.

  • A failed run capacitor causes motor humming, low torque, and overheating; test microfarads against the rating.

  • A dirty filter reduces airflow, lowers evaporator temperature, and can freeze the coil.

  • Frozen evaporator causes include low airflow, low charge, restricted metering device, and low return-air temperature.

  • Electronic leak detectors and UV dye locate refrigerant leaks; after repair, evacuate and recharge.

  • Compressor winding checks use ohms among terminals and to ground; open or grounded windings indicate failure.

  • Heat pump defrost problems can involve the defrost board, sensors, reversing valve, or outdoor fan.

Quick reference

Codes, Standards, Permits, and Jobsite Safety

  • EPA Section 608 certification is required to service refrigerant-containing equipment; venting refrigerant is prohibited.

  • ASHRAE 34 classifies refrigerants by toxicity and flammability; ASHRAE 15 addresses refrigeration system safety.

  • OSHA construction fall protection is generally required at 6 feet; general industry fall protection at 4 feet.

  • Lockout/tagout isolates electrical, gas, and other hazardous energy before maintenance.

  • NEC rules govern disconnects, grounding, bonding, GFCI protection, and conductor sizing for HVAC equipment.

  • NFPA 54/IFGC governs fuel gas piping, combustion air, venting, and appliance connections.

  • The International Mechanical Code governs HVAC installation, ventilation, and appliance clearances where adopted.

  • Permits and inspections are required for regulated installations; final inspection confirms code compliance.