GA HVAC: Heating Equipment and Systems (Furnaces, Boilers, Heat Pumps)

GA HVAC · Work through your exam, one topic at a time.

All guide sections

Heating Equipment and Systems (Furnaces, Boilers, Heat Pumps)

Efficiency, venting, and delivered heat

Gas furnaces are rated by AFUE, which accounts for cycling and jacket losses, not just steady-state combustion efficiency. Condensing units recover latent heat (category IV venting, plastic flue, acidic condensate with a trap and neutralizer); non-condensing units (category I) need a properly sized chimney with draft and cannot be sidewall vented without a listed kit. Verify the temperature rise at every start-up: high rise means low airflow; low rise means excess airflow or overfiring. Manifold gas pressure and combustion analysis confirm the fuel side.

Hot water boilers require an expansion tank, air elimination, a relief valve piped to a safe drain, a low-water cut-off where required, and correct circulator sizing. Outdoor reset and primary/secondary piping improve performance but must respect minimum return temperatures to prevent condensing damage in non-condensing boilers.

Heat pumps are rated at 47°F and 17°F; capacity falls with outdoor temperature while building load rises. The balance point is where the two curves cross. Below it, supplementary resistance heat carries the difference, with a lockout to prevent unnecessary auxiliary use and a defrost cycle that temporarily reverses the cycle.

Traps: comparing AFUE to steady-state efficiency; sizing a heat pump from the cooling load without checking heating capacity at design temperature; ignoring aux-heat lockout settings; forgetting the condensate drain freeze risk on condensing furnaces.

Worked example: 80,000 Btu/h output at 1,200 CFM → ΔT = 80,000 ÷ (1.08 × 1,200) ≈ 62°F rise.