Quick reference

General Regulations

  • The International Plumbing Code (IPC) is the minimum plumbing standard adopted statewide in Georgia; local jurisdictions may amend it to be more restrictive but not less restrictive.

  • A permit is required before installing, altering, repairing, or replacing any plumbing system; routine maintenance of existing fixtures is generally exempt.

  • Plumbing work must be performed by a licensed master or journeyman plumber, or by an apprentice under direct supervision of a licensed plumber.

  • Only a licensed master plumber may contract for plumbing work and pull plumbing permits.

  • Referenced standards (ASTM, ASME, CSA, NSF, CISPI) are enforceable parts of the code; an unlisted material requires written approval of the authority having jurisdiction (AHJ).

  • When two code provisions conflict, the more restrictive requirement governs; where the code is silent, the manufacturer's listed installation instructions govern.

  • The AHJ may order any unsafe, insanitary, or defective plumbing system disconnected and its use prohibited until corrected.

Quick reference

Administration and Code Scope

  • The code governs the erection, installation, alteration, repair, relocation, replacement, addition to, use, and maintenance of plumbing systems.

  • Scope includes water supply and distribution, fixtures and fittings, sanitary and storm drainage, vents, traps, interceptors, water heaters, and special wastes.

  • Lawfully installed existing plumbing need not be upgraded unless it is unsafe, insanitary, or ordered corrected by the AHJ.

  • Alternate materials or methods may be used when the AHJ finds them equivalent in quality, strength, effectiveness, fire resistance, durability, and safety.

  • A permit application must be accompanied by plans and specifications showing size, location, and type of piping and fixtures; permits expire if work does not commence within the period stated by the jurisdiction.

  • Rough-in, building sewer, and final inspections must be requested and passed before the work is concealed or placed in service.

  • A board of appeals hears disputes over code interpretation and decisions of the AHJ.

Quick reference

Plumbing Terminology

  • Cross-connection: any actual or potential connection between the potable water supply and a source of contamination or pollution.

  • Backflow: the reversal of normal flow of water, liquids, or gases into the potable water system by backsiphonage or backpressure.

  • Fixture unit (FU): a measure of the probable hydraulic load of a fixture; 1 drainage fixture unit equals 1 cubic foot per minute of flow (about 7.5 gpm).

  • Developed length: the total length measured along the centerline of pipe and fittings, including valves and fittings converted to equivalent pipe length.

  • Trap seal: the vertical distance between the crown weir and the top of the dip of the trap, required to be 2 inches minimum and 4 inches maximum.

  • Air gap: the unobstructed vertical distance through free atmosphere between a water outlet and the flood-level rim of the receptor.

  • Flood-level rim: the top edge of a receptor from which water would overflow onto the floor.

  • Stack: a general term for any vertical line of piping; a branch is a horizontal run connecting fixtures to a stack or drain.

Quick reference

Symbols and Isometric Analysis

  • Isometric drawings are drawn on three axes: vertical lines are drawn vertical, and the two horizontal axes are drawn at 30 degrees above the horizontal.

  • Drainage lines are typically shown solid; vents are commonly drawn dashed or distinguished by leader labels such as 'V' or 'VENT'.

  • Common abbreviations: WC = water closet, LAV = lavatory, KS = kitchen sink, FD = floor drain, CO = cleanout, FCO = floor cleanout, HWR = hot water return.

  • Diameter callouts are written on or beside the pipe, e.g., '3 V' means a 3-inch vent and '4 D' means a 4-inch drain.

  • Slope is shown as inches per foot or percent; on an isometric the flow direction is indicated by an arrow pointing downhill toward the drain or sewer.

  • Horizontal-to-horizontal drainage changes use a wye or a combination wye-and-eighth bend; vertical to horizontal uses a sanitary tee or wye.

  • Isometrics must be read together with the plan and a north reference; risers are the vertical segments that reconnect separate floor plans.

Quick reference

Water Supply and Distribution

  • The pressure at a fixture inlet must be at least 8 psi flowing; where static pressure exceeds 80 psi, a pressure-reducing valve is required.

  • Where the street pressure is inadequate for the fixture demand, an approved booster pump or on-site pressure tank must be provided.

  • A closed water system (created by a check valve, backflow preventer, or pressure-reducing valve) requires thermal expansion control.

  • Minimum water service pipe size is 3/4 inch; fixture supply branches are minimum 1/2 inch, with 3/8 inch permitted only for certain small fixtures.

  • Flushometer valves require larger, dedicated branch sizing than flush-tank fixtures and cannot be installed where the available flowing pressure is insufficient.

  • Hot water distribution must be insulated where required by the energy code, and hot water piping is run above cold water where pipes are parallel.

  • Water hammer arrestors are required at quick-closing valves and at fixture groups with fast-acting flush valves.

  • Water piping must be protected from freezing and supported at intervals required by code for the pipe material.

Quick reference

Sizing and Materials

  • Water distribution sizing uses the total water-supply fixture units and the developed length from the meter to the most remote outlet.

  • Copper water tube: Type K is used underground and in heavy-duty service, Type L above ground for domestic water, Type M only where permitted.

  • PEX must be listed to ASTM F876/F877 with fittings to ASTM F1807 or F1960; PEX-A is expanded, PEX-B is crimped.

  • DWV materials: PVC to ASTM D2665, ABS to ASTM D2661, service-weight cast iron to CISPI 301, copper DWV tube to ASTM B306.

  • Hubless cast iron joints use couplings complying with CISPI 310 and stainless steel shields.

  • Galvanized steel pipe must comply with ASTM A53; threaded joints use at least Schedule 40 pipe.

  • Solder and flux must be lead-free; lead content in pipe, fittings, and solder is limited to not more than 0.25 percent by weight.

  • Drainage piping shall not be reduced in size in the direction of flow; water piping is sized so velocity stays within limits that prevent noise and erosion.

Quick reference

Fixtures

  • Maximum fixture flow rates: water closets 1.6 gpf, urinals 1.0 gpf, showerheads 2.5 gpm at 80 psi, kitchen and lavatory faucets 2.2 gpm, public lavatory faucets 0.5 gpm.

  • Water closet compartment: not less than 15 inches from the centerline of the fixture to a side wall and 21 inches of clear space in front.

  • Accessible fixtures require clear floor space of 30 inches by 48 inches and comply with the adopted accessibility standard.

  • Fixtures must be of an approved type, with a smooth, impervious, corrosion-resistant surface, and securely fastened to the floor or wall.

  • Floor drains are required in public toilet rooms and in locations where water or a fixture leak could cause damage.

  • Drinking fountains must be capable of delivering at least 0.25 gpm and provide a minimum number based on occupant load.

  • Shower compartments must have a minimum finished interior area of 900 square inches and be finished with a smooth, impervious surface.

  • Food service establishments require a sink with at least three compartments for washing, rinsing, and sanitizing.

Quick reference

Fixture Fittings and Trim

  • Hose bibbs and sill cocks require an approved backflow preventer such as a vacuum breaker.

  • Shower valves must be pressure-balancing, thermostatic, or combination type, and must limit the delivered water temperature to a maximum of 120 degrees F.

  • A bathtub filler spout must be located at least 2 inches above the overflow rim of the tub.

  • Faucets and supply stops must be listed and installed so that the fixture can be isolated for repair.

  • Escutcheons are required where supply or drain pipes pass through a wall or floor in a finished area.

  • Flushometer valves require a minimum flowing pressure stated by the manufacturer and code and are installed with a control stop and vacuum breaker.

  • Fittings with slip joints are limited to the trap and fixture connection and must be accessible.

Quick reference

Water Heaters

  • Every water heater requires a temperature and pressure relief valve that is third-party listed and rated for the heater's capacity.

  • T&P relief discharge must be full size, gravity-flow, terminate not more than 6 inches above the floor or outside the building, and must not be trapped or have a threaded end.

  • A drain pan at least 1.5 inches deep with a drain of not less than 3/4 inch is required where leakage may cause damage, such as in an attic or above a ceiling.

  • The relief valve discharge pipe must not be reduced in size and must not contain a valve between the heater and the valve or in the discharge.

  • A water heater installed in a closed system requires a thermal expansion tank or other approved expansion control.

  • Gas-fired water heaters require combustion air, a sediment trap ahead of the controls, and venting sized to the appliance input.

  • Water heaters must be accessible for service and inspection, and the T&P valve must be accessible for testing and replacement.

  • Heaters installed in areas subject to vehicle damage require protection such as bollards.

Quick reference

Temperature and Pressure Control

  • A pressure-reducing valve is required where static pressure exceeds 80 psi; typical settings reduce the downstream pressure to 50-75 psi.

  • A PRV creates a closed system, so thermal expansion control is required downstream of it.

  • Water delivered to public lavatories and showers must not exceed 120 degrees F unless a limiting device is provided.

  • Tempered water for public hand-washing is delivered at approximately 110 degrees F using a thermostatic or tempering valve.

  • A typical T&P relief valve is set to open at 150 psi and 210 degrees F.

  • Water hammer arrestors are sized to PDI WH-201 and installed at quick-closing valves and flushometer groups.

  • A strainer must be installed ahead of a pressure-reducing valve, and the valve must be accessible with a downstream pressure tap.

Quick reference

Sanitary Drainage

  • Horizontal drainage piping slopes at least 1/4 inch per foot for pipe 2 1/2 inches and smaller and 1/8 inch per foot for pipe 3 inches and larger.

  • The building drain is the lowest piping of the drainage system that receives waste from inside the building and conveys it to the building sewer.

  • Each horizontal drain requires a cleanout at its upper end, and cleanouts are required at the base of each stack and at changes of direction greater than 135 degrees.

  • Cleanouts are required at intervals not exceeding 100 feet in horizontal drainage piping and must be accessible.

  • A backwater valve is required where a fixture's flood-level rim is below the elevation of the next upstream manhole.

  • Drainage fittings must have smooth interior surfaces; a sanitary tee is used for vertical-to-horizontal transitions, and wyes for horizontal-to-horizontal.

  • Vertical drainage stacks must be supported at their base and at intervals required by code, with no reduction in size in the direction of flow.

  • Fixtures must be protected from sewer gas and backflow by traps and, where required, backwater valves.

Quick reference

Slope and Drainage Sizing

  • Drainage pipe is sized from the total drainage fixture units (dfu) on the line using the code's drainage sizing tables.

  • Minimum slope: 1/4 inch per foot up to 2 1/2 inch pipe; 1/8 inch per foot for 3 inch and larger pipe.

  • The building sewer and building drain must be not less than 3 inches in diameter.

  • Trap arm length limits: 1 1/4 inch trap = 5 feet, 1 1/2 inch trap = 6 feet, 2 inch trap = 8 feet from the trap weir to the vent.

  • A drainage line may slope steeper than the minimum, but an excessive slope on short runs can leave solids behind; vertical drops are connected with a wye and bends.

  • Pipe size is never reduced in the direction of flow, and the slope must be uniform between fittings.

  • Storm drainage is sized on roof area and rainfall rate and uses the same minimum slope rules as sanitary drainage.

  • Insufficient slope causes solids deposition; reverse slope (falling toward the fixture) is prohibited.

Quick reference

Venting Systems and Vent Sizing

  • Every trap must be protected from siphonage by a vent, except where the code specifically permits an unvented fixture or common vent arrangement.

  • The minimum size of an individual vent or vent stack is 1 1/4 inches; a vent may never be smaller than 1 1/2 inches where required for the drainage it serves.

  • A vent must be taken off at least 2 pipe diameters from the trap weir, which prohibits a crown vent.

  • A vent stack must extend at least 6 inches above the roof surface and be flashed to prevent leakage.

  • Vents must be sized by the number of fixture units served using the vent sizing tables, and a vent cannot serve as a drain.

  • Wet venting is permitted only where the wet-vented fixture is on the same floor and the vent is sized per the tables.

  • Air admittance valves are permitted only where approved by the AHJ, are installed above the fixture flood-level rim, and require access.

  • A vent must extend upward without offsets below the fixture, and horizontal vent runs must slope back toward the drain.

Quick reference

Traps

  • Each fixture must be separately trapped, except fixtures with integral traps and where a single trap is permitted by code.

  • A water closet has an integral trap and does not require an additional trap.

  • A trap seal must be between 2 inches and 4 inches deep, and the trap must be self-cleaning.

  • Trap sizes: minimum 1 1/4 inch for lavatories, 1 1/2 inch for sinks, and 2 inches for other fixtures such as floor drains.

  • A trap must be level (horizontal) after installation, and the trap arm length limits apply from the trap weir to the vent.

  • S-traps, crown vents, double traps, and traps that depend on moving parts for their seal are prohibited.

  • Traps must be accessible for cleaning, either by location or by a removable cleanout/fixture.

  • Trap seals can be lost by evaporation, siphonage, backpressure, or capillary action; venting and proper installation prevent most seal loss.

Quick reference

Interceptors

  • Grease interceptors are required for restaurants and other establishments that discharge grease-laden waste from food preparation or dishwashing.

  • Grease interceptors are sized by the fixture-capacity or flow-rate method; mass-produced units must be listed to PDI G101.

  • Interceptors must be installed with a vent, an accessible cover, and a cleanout for removal of accumulated grease.

  • The grease interceptor must be located so that accumulated grease can be removed and the unit inspected; it is commonly installed outside the building.

  • Sand and oil interceptors are required for garages, repair shops, and car washes where sand, oil, or similar materials enter the drainage system.

  • The discharge from an interceptor must connect to the sanitary drainage system through a vented line with a full-size cleanout.

  • Interceptors must retain a water seal and must not be double-trapped or installed where they can be siphoned.

Quick reference

Backflow Prevention and Cross-Connection Control

  • An air gap is the only method that protects against both backsiphonage and backpressure; it must be at least twice the pipe diameter and never less than 1 inch.

  • A reduced pressure zone (RPZ) assembly protects against both backpressure and backsiphonage and is required for high-hazard connections; it must be field tested.

  • A double check valve assembly (DCVA) is used for low-hazard connections and protects against backpressure and backsiphonage.

  • A pressure vacuum breaker (PVB) protects against backsiphonage only and must be installed at least 12 inches above the highest downstream outlet.

  • An atmospheric vacuum breaker must be installed at least 6 inches above the flood-level rim and must not have a shutoff valve downstream.

  • Backflow protection is required at boiler feed lines, irrigation systems, hose bibbs, carbonators, chemical dispensers, and lawn sprinklers.

  • Backflow assemblies must be installed in an accessible location for testing and must be tested by a certified backflow tester.

  • A bypass around a backflow assembly is prohibited unless the bypass is equipped with an approved backflow device.

Quick reference

Storm Drainage

  • Storm drainage must be kept separate from the sanitary drainage system and discharge to an approved point such as a storm sewer, dry well, or splash block.

  • Roof drains and leaders are sized from the roof area and the local design rainfall rate, not from fixture units.

  • Minimum roof drain size is 2 inches, and storm drainage uses the same minimum slopes as sanitary drainage.

  • Primary and secondary (overflow) roof drains are required on roofs with parapet walls so that water can escape if the primary drain clogs.

  • Roof drain strainers must be provided and the drain must be flashed to the roof to prevent leakage.

  • Storm drainage must not discharge into a sanitary sewer unless specifically allowed by the authority having jurisdiction.

  • Subsoil drains and sump pumps discharge to an approved location and may not connect to the sanitary system where prohibited.

Quick reference

Special and Indirect Waste

  • Indirect waste is waste that discharges into the drainage system through an air gap or air break into a properly sized and vented receptor.

  • An air gap must be at least twice the effective pipe diameter and never less than 1 inch; an air break requires the pipe to terminate above the flood-level rim of the receptor.

  • Indirect waste is required for food service sinks, dishwashing machines, ice machines, coffee brewers, sterilizers, and similar equipment.

  • Receptors must be individually trapped and vented and must be large enough to receive the discharge without splashing.

  • Special wastes include chemical wastes, which require acid-resistant piping, and condensate, which may discharge to an approved receptor.

  • Clear-water wastes such as condensate from air conditioning and relief valve discharge are discharged by indirect waste.

  • Food waste grinders and pot sinks must drain through an air gap or air break before entering the drainage system.

Quick reference

Fuel Gas Piping and Appliance Connections

  • Gas piping is sized using the longest-length method with the code's capacity tables for the specific pipe material and gas.

  • A sediment trap is required at each appliance inlet, installed upstream of the controls with a minimum 3-inch nipple.

  • A shutoff valve must be installed ahead of each appliance in the same room and must be accessible.

  • An appliance connector must not exceed 6 feet, must not be concealed, and must not pass through a wall, floor, or ceiling.

  • Gas piping must be supported at code intervals, protected against corrosion, and identified where it passes through concealed spaces.

  • Metallic gas piping must be bonded to the grounding electrode system; gas piping may not be used as a grounding conductor.

  • Combustion air for fuel-burning appliances is provided by indoor air (50 cubic feet per 1,000 Btu input) or by outdoor openings sized per the code.

  • New gas piping is pressure tested with air or nitrogen, and leaks are checked with soap solution, never with an open flame.

Quick reference

Safety

  • Trenches 5 feet deep or more require shoring, shielding, or sloping, and a ladder must be provided within 25 feet of lateral travel.

  • Spoil piles and equipment must be kept at least 2 feet from the edge of an excavation.

  • Confined spaces must be tested for oxygen, hydrogen sulfide, and combustible gas before entry, and ventilation must be provided.

  • Hydrogen sulfide in sewers is toxic and explosive at high concentrations; sewer gas must be controlled with ventilation and monitoring.

  • Ground-fault circuit interrupter protection is required for temporary power on construction sites.

  • Hot work with a torch requires a fire watch, removal of combustibles, and adequate ventilation of flux fumes.

  • Fall protection is required when working 6 feet or more above a lower level.

Quick reference

Tools

  • Copper tube must be reamed to full inside diameter after cutting to prevent turbulence and flow restriction.

  • A pipe wrench is operated by pulling the handle toward the user with the jaws facing the direction of rotation.

  • Cast iron soil pipe is cut with a soil pipe cutter or snap cutter, and the cut end is dressed before coupling.

  • Press fittings require a calibrated press tool with the correct jaw for the fitting size and material.

  • PEX-A is expanded with an expansion tool; PEX-B is joined with a crimp or clamp tool.

  • A hydrostatic test pump is used to pressure-test water distribution systems.

  • A closet auger is used for water closets; a drum or sectional cable machine is used for larger drain lines.

  • Drainage slope is set with a level, laser, or transit; a grade rule is used to check fall per foot.

Quick reference

Testing and Jobsite Practices

  • DWV systems may be tested with water, using a 10-foot head above the highest point of the system, held for at least 15 minutes without a drop.

  • DWV systems may alternatively be tested with compressed air at 5 psi for at least 15 minutes with the system isolated.

  • Water distribution systems are tested hydrostatically at working pressure or the code minimum, held for at least 15 minutes without leakage.

  • The building sewer is tested with water or air before being covered, and the test is witnessed by the AHJ.

  • Rough-in inspection must be approved before piping is concealed, and final inspection occurs after fixtures and trim are set.

  • Open pipe ends must be capped or plugged during construction to keep debris out of the drainage system.

  • Test results and inspections are recorded, and the AHJ may require a re-test whenever work is altered after approval.