GA Well Driller study materials
GA Well Driller study resources

GA Well Driller cheat sheet

GA Well Driller · Keep the key ideas within reach.

Quick reference

Well Siting, Geology, and Hydrogeology

  • Georgia Piedmont: productive yield comes from fractures and faults in crystalline bedrock, not from intergranular porosity; a dry hole is common where no fracture is intersected.

  • Coastal Plain: sediments young seaward; the Floridan aquifer system is the principal supply, and the Upper Floridan is confined beneath the Dublin-Metter and other confining units.

  • Drawdown cone of influence radius in a confined aquifer: r = sqrt(2.25Tt/S) (Theis approximation), where T is transmissivity, S storativity, t pumping time.

  • Specific capacity = pumping rate / drawdown (gpm/ft); a falling specific capacity over time signals well inefficiency, not necessarily aquifer decline.

  • Georgia requires a 50-ft minimum separation between a well and a source of contamination such as a septic tank or animal lot; greater setbacks apply to land-application sites.

  • Topographic lows and drainageways concentrate recharge; siting on a ridge or steep slope reduces the catchment and increases the chance of a low-yield well.

  • Static water level is measured before pumping; pumping water level is measured during pumping. Difference = drawdown, used to compute specific capacity.

  • Confined aquifer potentiometric surface can stand above the top of the aquifer; an flowing (artesian) well results where it stands above land surface.

Quick reference

Well Design and Construction

  • Casing must extend at least 20 ft into competent, unweathered bedrock where bedrock is encountered, and the annular space above the seal must be grouted to land surface.

  • In unconsolidated Coastal Plain sediments, casing is set through the upper confining unit and the screen is placed in the target aquifer; the annular seal must extend from the bottom of the casing to land surface.

  • Screen slot size is selected to retain 90-100% of the formation sand; slot openings are typically 0.010-0.040 in for Coastal Plain sands and larger for gravel-pack wells.

  • Gravel pack envelope thickness is normally 3-5 in around the screen; the pack must extend above the screen and be topped with a bentonite seal before grouting.

  • Well diameter must accommodate the pump: allow at least 2 in of clearance between pump outside diameter and casing inside diameter for motor cooling and setting depth.

  • Conductor casing is used to seal off unconsolidated surface material and shallow water; it is set first and the inner casing is telescoped through it.

  • A wellhead must be at least 12 in above finished grade, with a watertight, vermin-proof cap and a sanitary seal around the pump drop pipe.

  • Pitless adapters allow the discharge line to exit below frost line through the casing wall while keeping the wellhead watertight.

Quick reference

Drilling Methods, Equipment, and Operations

  • Mud rotary: circulation of bentonite-based fluid removes cuttings and stabilizes the borehole wall; cuttings return velocity must exceed the slip velocity of the largest cuttings.

  • Air rotary with a hammer is preferred in hard crystalline bedrock; foam or water injection controls dust and stabilizes the hole in wet zones.

  • Cable tool drilling: a heavy bit is lifted and dropped; cuttings are removed with a bailer. Formation water is not contaminated by drilling fluid, so it is useful for water-quality sampling.

  • Reverse circulation uses a dual-wall pipe; cuttings travel up the inner pipe and the sample is less contaminated by wall caved material.

  • Annular velocity for direct circulation: v = 24.5*Q/(D_h^2 - D_p^2) in ft/min with Q in gpm and diameters in inches; keep above 100-120 ft/min in large holes.

  • Lost circulation in fractured bedrock is treated with lost-circulation material, cement, or by switching to air; continuing to pump fluid wastes water and can wash out the formation.

  • Hole deviation is checked with a plumb-bob or downhole survey; excessive deviation prevents casing from seating and makes pump setting difficult.

  • Drilling-fluid weight must be kept low enough to avoid fracturing the formation; hydrostatic pressure = 0.433 psi/ft times mud weight in lb/gal divided by 8.34.

Quick reference

Grouting, Sealing, and Annular Space Integrity

  • Neat cement grout is mixed at no more than 6 gal of water per 94-lb sack (about 15.6 lb/gal); extra water causes shrinkage, cracking, and loss of seal.

  • Bentonite may be added at up to 5% by weight of cement to reduce shrinkage and improve pumpability; more than that weakens the set grout.

  • Grout is placed from the bottom up through a tremie pipe; free-fall placement from the top causes bridging and voids.

  • The annular seal must be continuous from the bottom of the casing (or screen) to land surface; a shallow seal that stops below grade leaves a direct pathway for surface contamination.

  • Bentonite grout (high-solids sodium bentonite) is acceptable in some settings but is not a substitute for cement where the rule requires cement.

  • Grout volume for an annulus: V (ft^3) = 0.00545*(D_hole^2 - D_casing^2)*L, with diameters in inches and L in feet; add 10-20% for loss.

  • Casing centralizers keep the casing centered so the grout envelope is uniform; without them the casing can lie against the wall and leave an unsealed channel.

  • A grout seal must be allowed to set at least 24 hours before drilling out or pressure-testing, and the well should not be developed until the cement has reached initial set.

Quick reference

Well Development, Testing, and Disinfection

  • Development removes drilling fluid, fines, and filter cake; methods include surging, jetting, bailing, and air-lifting, continued until discharge is clear of sediment.

  • Specific capacity test: pump at a steady rate until drawdown stabilizes, record pumping and static levels, then compute gpm per foot of drawdown.

  • Constant-rate pumping test of 24 hours or more with recovery monitoring is used to estimate transmissivity and storativity for larger or public-supply wells.

  • Step-drawdown test (three or more steps) separates well loss from aquifer loss; well efficiency = aquifer loss / total drawdown.

  • Disinfection: a chlorine solution of 50-100 mg/L in the well, contact time of at least 12 hours (24 hours is common), then pump to waste until chlorine odor is gone.

  • Chlorine demand of the water and casing must be satisfied before a residual can be measured; test residual with a DPD kit and record the result.

  • Bacteriological sampling follows disinfection and a stabilization period; a total coliform-positive result requires investigation and re-disinfection, not automatic abandonment.

  • Water-level measurements are referenced to a marked measuring point on the casing top; record the height of that point above land surface so depths are reproducible.

Quick reference

Pumps, Water Systems, and Pressure Equipment

  • Submersible pump setting depth must leave the pump above the well bottom and below the pumping water level so the motor stays submerged and cooled.

  • Pump capacity curve and system head curve intersect at the operating point; a pump operating far to the right of its curve can overload the motor.

  • Pressure tank precharge is set 2 psi below the pump cut-in pressure; a waterlogged tank (precharge lost) causes rapid cycling and motor failure.

  • Pressure switch settings are typically 30/50 or 40/60 psi; the gap between cut-in and cut-out determines the drawdown volume the tank must supply.

  • Drawdown volume of a bladder tank is roughly 25% of nominal tank volume; size the tank so the pump runs at least one minute per cycle.

  • Jet pumps are limited to about 25 ft of suction lift; deeper settings require a two-pipe deep-well jet or a submersible.

  • Pump motor voltage drop should not exceed 3% on the feeder and 5% total; undersized wire causes overheating and shortened motor life.

  • Backflow prevention and a check valve on the discharge protect the pump and prevent contamination of the aquifer from the distribution system.

Quick reference

Abandonment and Decommissioning of Wells

  • Abandonment requires filling the entire borehole with an approved material, usually neat cement or bentonite grout, from bottom to land surface.

  • The uppermost 20 ft of a abandoned well must be sealed with cement grout and the casing cut off at least 12 in below grade or removed.

  • Bridge plugs or bentonite chips may be used to support grout in a cased or screened well, but the seal above them must still be continuous to land surface.

  • A well that is temporarily out of service must still be capped watertight and marked; it may not be left open or unmarked.

  • Abandonment records (location, depth, method, materials, and volume) must be filed with the Georgia EPD within the required reporting period.

  • Flowing artesian wells must be controlled during abandonment; grout is placed against the flow and the well is not left flowing between aquifers.

  • Abandoned well casings that are cut off must be capped or sealed so that surface water cannot enter the remaining borehole.

  • An abandoned well is a potential direct conduit between surface contamination and the aquifer; improper abandonment is a common cause of aquifer contamination.

Quick reference

Georgia Well Construction Rules and Regulatory Compliance

  • Georgia Water Well Standards are administered by the Georgia Department of Natural Resources, Environmental Protection Division; the rules are in Ga. Comp. R. & Regs. 391-3-2.

  • A water well contractor must be licensed by the Georgia EPD; the license is required before constructing, repairing, or abandoning a well.

  • A well permit or notification is required before drilling in most Georgia counties; the local health department or EPD issues the permit and inspects the well.

  • Well logs must be filed with the EPD within 30 days of completion and must include depth, casing, screen, grout, and water-level data.

  • Casing must be new pipe meeting specified standards; used pipe may not be used for water well casing in Georgia.

  • The minimum distance from a well to a septic tank or sewage disposal area is 50 ft; greater distances apply to land application systems and other sources.

  • Public-supply wells are subject to additional requirements under the Safe Drinking Water Act and Georgia's public water system rules, including monitoring and operator certification.

  • A variance from a specific rule may be requested from the EPD in writing; the well may not be constructed until the variance is granted.

Quick reference

Safety, Environmental Protection, and Site Management

  • Before drilling, call 811 to have underground utilities located; drilling into a gas or electric line is a leading cause of serious injury on well sites.

  • Confined-space entry into a pit or vault requires atmospheric testing for oxygen, hydrogen sulfide, and combustible gas, plus a rescue plan and attendant.

  • Hydrogen sulfide is lethal above about 100 ppm and deadens the sense of smell; never rely on odor to judge safety.

  • Drilling fluid and cuttings must be contained in a pit or tank and disposed of properly; do not discharge to streams or wetlands without a permit.

  • Fuel and oil storage on site must be bermed or double-contained; a spill kit must be on site and spills reported to the EPD.

  • Rotating shafts, belts, and augers must be guarded; loose clothing and jewelry are prohibited near the drill string.

  • Hearing protection and a hard hat are required on active drill sites; rig mast raising and lowering is done only with the area cleared.

  • Site restoration includes removing cuttings, grading, reseeding, and restoring drainage so that surface water does not pond around the wellhead.