gh-ec-electrical-wiring-domestic study materials
gh-ec-electrical-wiring-domestic study resources

gh-ec-electrical-wiring-domestic cheat sheet

gh-ec-electrical-wiring-domestic · Keep the key ideas within reach.

Quick reference

General Electrical Knowledge, Definitions, and Code Administration

  • Voltage is the potential difference driving current; Ohm's law: E = I × R, so I = E/R and R = E/I for DC and purely resistive AC loads.

  • Power formulas: P = E × I (watts); in resistive circuits P = I²R = E²/R. Single-phase apparent power VA = E × I; three-phase VA = √3 × E × I.

  • Series circuit: current is common, resistances add (R_total = R1 + R2...), voltage divides. Parallel circuit: voltage is common, conductances add (1/R_total = 1/R1 + 1/R2...).

  • NEC Article 100 definitions control enforcement: "outlet" is any point where current is taken to use; a receptacle is a specific type of outlet, so every receptacle is an outlet but not every outlet is a receptacle.

  • Continuous load is one expected to operate at maximum current for 3 hours or more; the NEC generally requires branch-circuit and feeder conductors/OCPDs sized at 125% of continuous load plus 100% of noncontinuous load.

  • Ampacity is the current a conductor can carry continuously under stated conditions without exceeding its temperature rating; it depends on material, size, insulation, ambient temperature, and number of current-carrying conductors.

  • The NEC is adopted and enforced locally; the AHJ (authority having jurisdiction) interprets the code and may require listed equipment and approved methods. Local amendments can be stricter than the model code.

  • Working clearances at equipment (NEC 110.26) are measured from the live parts or enclosure front: typically 3 ft at 0–150 V to ground, 3.5 ft at 151–300 V, 4 ft at 301–600 V, with 30 in. width and 6.5 ft headroom.

  • Terminations are sized by the 60°C column for conductors 14–1 AWG unless the terminals and conductor are listed for a higher temperature; ampacity is also limited by the 75°C or 90°C termination rating.

Quick reference

Wiring Methods and Materials (Cables, Raceways, Boxes, Fittings)

  • NM-B (Romex) is permitted in one- and two-family dwellings and their attached/detached garages, but is prohibited in damp or wet locations, in masonry or concrete, and where subject to physical damage.

  • Box fill (NEC 314.16): count each 14 AWG conductor as 2.0 cu in, 12 AWG as 2.25, 10 AWG as 2.5; add one conductor volume for each device yoke, each clamp, each grounding conductor set, and each cable's support fittings.

  • Minimum box size for a given conductor count is found by dividing total cubic-inch volume by the per-conductor volume; a box marked 18 cu in holds eight 12 AWG conductors before devices, clamps, and grounds are added.

  • Cable support: NM cable must be secured within 12 in. of boxes and every 4.5 ft; bored holes need support within 12 in. of the hole, and cables must be protected by nail plates where within 1.25 in. of the framing surface.

  • Raceway fill (Chapter 9): one conductor max 53% of interior cross-section, two conductors 31%, three or more 40%; conduit bodies and short nipples have separate allowances.

  • Bending radius and conduit support: EMT must be supported within 3 ft of boxes and every 10 ft; IMC/RMC within 3 ft and every 10 ft; PVC schedule 40 every 3 ft for smaller sizes and within 3 ft of boxes.

  • Boxes must be accessible; junction boxes cannot be buried in walls or ceilings. Box extensions and covers are required where a box is set back from combustible or noncombustible finishes beyond the permitted amount.

  • Type AC/MC cable requires an insulated equipment grounding conductor in MC; AC cable uses the armor plus a bonding strip as the ground path. Both require listed connectors and anti-short bushings where required by listing.

  • Conductors in wet locations must be listed for wet locations; UF cable is permitted direct burial and in wet locations, with burial depth per NEC Table 300.5 (typically 24 in. for direct-buried cable, 18 in. under a concrete slab).

Quick reference

Branch Circuits, Feeders, and Service Calculations

  • Standard OCPD sizes (NEC 240.6): 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400 A.

  • Small-appliance branch circuits: two or more 20 A circuits required for kitchen/dining countertop receptacles, no other outlets on them; each counts 1,500 VA in the load calculation.

  • Laundry: one 20 A laundry branch circuit required, counted at 1,500 VA. Bathroom receptacles require at least one 20 A circuit serving only bathroom outlets.

  • General lighting load: 3 VA per sq ft for dwellings; feeder/service demand factors apply per Table 220.42 (first 3,000 VA at 100%, 3,001–120,000 VA at 35%).

  • Range and dryer demand factors: a single electric range uses Table 220.55; a 12 kW range counts 8,000 VA. Clothes dryers use 5,000 VA minimum or nameplate, whichever is larger.

  • Fixed appliances: 100% of the largest plus 40% of the remainder if four or more are fastened in place (NEC 220.53). Motor loads use Article 430 rather than the general demand rules.

  • Service conductor sizing: compute total demand in VA, divide by voltage to get amperes, then select the next larger standard service rating per 230.42/240.4; the grounded conductor may be reduced but not below the minimum in 250.24(C).

  • Voltage drop is not a code requirement but is a common design rule: keep total drop under 3% on a branch circuit and 5% overall; VD = 2 × K × I × L / circular mils for single-phase two-wire.

  • Receptacle spacing: 6 ft maximum along walls in habitable rooms, and any wall space 2 ft or wider must have a receptacle; kitchen countertop receptacles are required so no point is more than 24 in. from one.

Quick reference

Grounding, Bonding, and Overcurrent Protection

  • The service grounded conductor must be bonded to the service equipment enclosure and grounding electrode conductor at the service; the main bonding jumper is the connection between the grounded conductor and equipment grounding bus.

  • Grounding electrode system (250.50) includes all available electrodes: metal water pipe (10 ft in contact with earth), metal building frame, concrete-encased electrode, ground ring, rod/pipe electrodes, and plate electrodes.

  • Grounding electrode conductor sizing follows Table 250.66 based on service conductor size; a concrete-encased electrode or ground ring requires only a 4 AWG copper GEC regardless of service size.

  • A single rod, pipe, or plate electrode must have 25 ohms or less resistance to earth, or be supplemented by one additional electrode of any permitted type (250.53).

  • Equipment grounding conductors are sized from Table 250.122 based on the rating of the OCPD protecting the circuit, not the conductor ampacity.

  • Bonding is required for metal water piping, metal gas piping, structural steel, and any metal parts likely to become energized; bonding jumpers around water meters and insulating sections are required.

  • Overcurrent devices protect conductors from overcurrent: overload, short circuit, and ground fault. The next-size-up rule (240.4(B)) allows rounding up only if the ampacity is 800 A or less and the next standard size does not exceed the conductor ampacity.

  • GFCI protection is required in bathrooms, kitchens (countertop), garages, outdoors, crawl spaces, unfinished basements, laundry areas, and within 6 ft of sinks; AFCI protection is required for most 120 V branch circuits in dwelling living areas.

  • Fuse and breaker interrupting rating must be at least the available fault current at the terminals; series-rated systems require listed series combination ratings marked on the equipment.

Quick reference

Devices, Switches, Receptacles, and Outlet/Lighting Installations

  • Receptacle ratings: a 15 A receptacle may be installed on a 20 A circuit only if it is not a single receptacle; a single receptacle on an individual branch circuit must match the circuit rating (30 A receptacle on a 30 A circuit).

  • Tamper-resistant receptacles are required in dwelling units; GFCI receptacles must be installed in a readily accessible location and are not permitted where the reset cannot be reached.

  • Switch control: habitable rooms require a wall switch-controlled lighting outlet; stairways require switches at each floor level; attached garages require at least one lighting outlet controlled by a switch at the entrance.

  • Receptacle grounding: grounding-type receptacles must be connected to an equipment grounding conductor. Replacing an ungrounded receptacle with a GFCI is permitted with marking "No Equipment Ground."

  • Boxes for receptacles and switches must be installed so the box is flush with or slightly recessed from the finished surface, and the yoke must be secured; gaps greater than 1/8 in. require a proper cover or extension ring.

  • Lighting outlet boxes in ceilings must be listed and supported independently of the fixture canopy; fan-rated boxes are required for paddle fans and must be marked for the load.

  • Switch loops and travelers: 3-way switches use two travelers plus a common; 4-way switches are inserted between travelers. Neutral must be present at switch locations in most habitable-room installations per 404.2(C).

  • Receptacles in damp/wet locations require weather-resistant (WR) types and in-use covers; outdoor receptacles require GFCI protection and a while-in-use cover.

  • Device boxes must be accessible and not supported by the raceway alone where the box supports a fixture; fixtures over 50 lb require independent support.

Quick reference

Special Occupancies and Residential-Specific Requirements

  • Bathrooms: at least one 20 A branch circuit supplying only bathroom receptacles; all bathroom receptacles require GFCI; no receptacles are permitted within a shower or bathtub space.

  • Kitchen countertop: at least two 20 A small-appliance circuits; GFCI required for all countertop receptacles; island and peninsular countertops require at least one receptacle, with GFCI protection.

  • Garages: at least one 20 A circuit for garage receptacles, GFCI-protected; the garage lighting outlet must be switch-controlled at the entrance; a garage is considered a separate area for receptacle spacing.

  • Pools and spas: receptacles must be at least 6 ft from the inside wall of the pool; underwater luminaires require GFCI and specific listed fittings; equipotential bonding of pool shells and metal parts is required by Article 680.

  • Unfinished basements and crawl spaces: receptacles require GFCI; crawl spaces need a lighting outlet and a receptacle, both GFCI-protected where required.

  • Outdoor outlets: all 15 A and 20 A outdoor receptacles in dwellings require GFCI and weather-resistant devices; a receptacle is required at the front and back of a one-family dwelling.

  • Laundry areas: receptacles require GFCI; the laundry branch circuit must be 20 A and supply only laundry outlets (plus associated equipment).

  • Smoke and CO alarms: interconnected smoke alarms required in each bedroom, outside each sleeping area, and on each level; CO alarms required where fuel-burning appliances or attached garages exist.

Quick reference

Motors, Appliances, HVAC Equipment, and Dedicated Circuits

  • Motor branch-circuit conductors are sized at 125% of the motor full-load current from Article 430 tables, not the nameplate current, unless the nameplate is used for a specific listed motor.

  • Motor overload protection protects the motor from overload; the branch-circuit short-circuit and ground-fault protective device protects the circuit. They are separate functions and are not interchangeable.

  • Motor disconnecting means must be within sight of the motor and controller, or capable of being locked open; the disconnect must be rated at least 115% of the motor FLC.

  • HVAC equipment: a central heating/AC unit requires a dedicated branch circuit; the nameplate minimum circuit ampacity (MCA) and maximum overcurrent protection (MOCP) govern conductor and breaker sizing.

  • Room air conditioners and central units may use a 25 A or 30 A circuit as marked; the breaker must not exceed the nameplate maximum fuse or HACR breaker rating.

  • Appliances fastened in place and rated over 1,380 VA require an individual branch circuit; a dedicated circuit is required for a range, dryer, water heater, and dishwasher/disposal where specified.

  • Motor conductor ampacity must be at least 125% of FLC, and the overload device is sized per the motor's service factor and temperature rise (typically 115–125% of nameplate current).

  • Hermetic refrigerant motor-compressors use Article 440: branch-circuit selection uses rated-load current and 125% of the largest motor plus the sum of other loads.

  • Motor control circuits and disconnects must be labeled with the source; a motor circuit must have a controller capable of starting and stopping the motor, and the disconnect must open all ungrounded conductors.

Quick reference

Low-Voltage, Communications, and Signaling Systems

  • Class 2 and Class 3 circuits are power-limited; Article 725 governs separation from power conductors, and Class 2 cables cannot be installed in the same raceway with power conductors unless the raceway is divided or the cable is listed for the purpose.

  • Communications circuits (Article 800) include telephone, data, and CATV; cables must be listed, and a primary protector is required where the cable enters the building.

  • Separation rules: communications and Class 2 cables must maintain at least 2 in. from power conductors unless separated by a permanent barrier, and must cross power lines at right angles where possible.

  • Low-voltage lighting systems operating at 30 V or less require listed equipment; the transformer or power supply must be listed and accessible, and secondary conductors are sized for the load.

  • Fire alarm systems (Article 760) require listed cable and equipment; Class A circuits survive a single open, Class B circuits do not; the initiating and notification circuits must be separated from power wiring.

  • Smoke detector interconnect wiring in dwellings is typically 3-wire NM with a signal conductor; the interconnect must be on the same circuit as the smoke alarms and must not be GFCI-protected on a shared circuit.

  • Bonding of communications systems: the communications grounding conductor must be bonded to the building grounding electrode system, and the bonding jumper must be at least 6 AWG copper.

  • Signaling circuits must be identified; a low-voltage cable installed in a raceway with power conductors must have a voltage rating at least equal to the power circuit, and Class 2 circuits cannot share a box with power unless listed.

Quick reference

Safety, Inspection, and Code-Compliance Practices

  • Lockout/tagout: de-energize, verify with a tester rated for the voltage, and lock the disconnect before working on equipment; treat all conductors as energized until tested.

  • PPE and approach boundaries: use insulated gloves and tools rated for the voltage; the limited approach boundary for 120/240 V is typically 10 ft for unqualified persons.

  • Inspection sequence: rough-in inspection after boxes and raceways are installed but before covers; final inspection after devices, fixtures, and covers are installed and the system is energized and tested.

  • Common red-tag items: missing box covers, unsupported cable, missing GFCI, improper bonding, overfilled boxes, unprotected cable in framing, and missing nail plates.

  • Test instruments: use a non-contact voltage tester plus a multimeter; verify continuity of the grounding path and check for reversed polarity and open grounds at receptacles.

  • Working clearance and access: equipment must be accessible, not blocked by stored items, and the working space must be kept clear; panels need a minimum 30 in. width and 36 in. depth.

  • Arc-flash and shock risk increase with available fault current; equipment must be labeled with its short-circuit current rating, and series-rated equipment must be marked.

  • Record keeping: keep inspection records, permit numbers, and test results; a permit is required for new services, additions, and alterations, and final approval is required before energizing.

Quick reference

Georgia State Licensing Laws, Rules, and Business/Regulatory Requirements

  • Electrical contracting in Georgia is licensed by the Georgia State Electrical Contractors Board under the Secretary of State's Professional Licensing Boards Division; a state license is required to contract for electrical work.

  • License classes include Class I (unlimited) and Class II (limited to work of 400 A or less and specific voltage limits); the class determines the scope of work a licensee may perform.

  • Continuing education: Georgia requires licensed electrical contractors to complete continuing education hours each renewal cycle (commonly 8 hours per two-year cycle, with code-update content).

  • Insurance and bonding: a licensed electrical contractor must maintain general liability insurance and, where required, a surety bond; proof must be filed with the board.

  • Qualifying agent: a business entity must have a designated qualifying agent who holds the license and is responsible for the work; the agent must be actively engaged in the business.

  • Permits and inspections: local jurisdictions issue permits and inspect; work must comply with the locally adopted code, which in Georgia is typically based on the NEC with state and local amendments.

  • Unlicensed practice and advertising violations are grounds for discipline; the board may fine, suspend, or revoke a license, and unlicensed contracting is a criminal offense.

  • Business requirements: written contracts, lien notices, and compliance with Georgia's contractor licensing and consumer protection statutes; change orders and warranties should be documented in writing.

Quick reference

General Electrical Knowledge, Definitions, and Code Administration (continued)

  • Ampacity correction factors apply for ambient temperature (Table 310.15(B)(2)(a)) and adjustment for more than three current-carrying conductors in a raceway or cable (Table 310.15(B)(3)(a)).

  • The neutral (grounded) conductor in a multiwire branch circuit carries the unbalanced current only; in a 120/240 V system the neutral may be reduced but not below the minimum required by 250.24(C).

  • A multiwire branch circuit must have a means to simultaneously disconnect all ungrounded conductors at the panelboard, and the two hot legs must be on different phases.

  • The NEC is not retroactive; existing installations that complied when installed may remain unless the AHJ determines a hazard exists or the occupancy changes.

  • Listing and labeling: equipment must be installed per its listing and instructions; using a device outside its listing (e.g., an indoor box outdoors) is a code violation even if it fits.

  • The 2020/2023 NEC expanded GFCI requirements to more dwelling locations; verify which code edition your jurisdiction has adopted before applying a specific requirement.

Quick reference

Wiring Methods and Materials (continued)

  • Conductor insulation types: THHN/THWN-2 rated 90°C dry and 75°C wet; NM-B uses 90°C conductors but must be used at the 60°C ampacity per 334.80.

  • Minimum conductor size for general wiring is 14 AWG copper (12 AWG for 20 A circuits); fixture wires and Class 2 circuits are exceptions.

  • Splices must be made with listed splicing devices and enclosed in a box; solder-only connections are not permitted without a listed connector.

  • Expansion fittings are required where raceways cross building expansion joints; flexible connections are required at vibrating equipment.

  • The equipment grounding conductor in NM cable is the bare conductor; in MC it is the green insulated conductor; the armor of AC cable is not a substitute for an EGC in all cases.

  • Cable trays, wireways, and gutters have fill and support rules separate from conduit; wireways allow 20% fill for power conductors and require support every 5 ft.

  • Boxes in ceilings supporting luminaires must be listed for the fixture weight; a fan box is required for ceiling fans, and the box must be marked with the maximum weight.

Quick reference

Branch Circuits, Feeders, and Service Calculations (continued)

  • Optional calculation for dwellings (Article 220 Part IV) uses 3 VA/sq ft general lighting plus small appliance and laundry at 1,500 VA each, then applies the 220.82 demand factors to the total.

  • A 200 A service is typical for a modern dwelling; verify by calculating the total demand load and comparing to the service rating, and account for the largest motor at 25%.

  • Feeder taps and transformer feeders follow Article 240; the tap rules allow reduced conductor sizing only under specific length and protection conditions.

  • The service disconnecting means must be rated at least the calculated load and located at a readily accessible point nearest the point of entry of the service conductors.

  • A grounding electrode conductor for a 200 A service with 2/0 copper is typically 4 AWG copper per Table 250.66; verify against the actual service conductor size.

  • Voltage drop calculation example: a 120 V, 20 A load 100 ft away on 12 AWG copper (6,530 cmil) gives VD = 2 × 12.9 × 20 × 100 / 6,530 ≈ 7.9 V, about 6.6%.

  • Receptacle load calculations: a dwelling general-use receptacle outlet is included in the 3 VA/sq ft lighting load; specific appliance receptacles are added separately.

Quick reference

Grounding, Bonding, and Overcurrent Protection (continued)

  • The main bonding jumper must be sized per 250.28(D) based on the service conductor size; it is typically a screw or strap in the service panel and must not be removed for subpanels.

  • Subpanels require a separate equipment grounding conductor and an isolated neutral bar; bonding the neutral at a subpanel creates parallel return paths and is a violation.

  • GFCI protection may be at the breaker, receptacle, or a combination; the device must be listed and the protected circuit must not be shared with unprotected loads on the load side.

  • AFCI protection is required for branch circuits supplying outlets in dwelling living rooms, bedrooms, closets, hallways, and similar areas; combination AFCI breakers protect against series and parallel arcs.

  • Overcurrent device sizing for motors uses the nameplate or Article 430 tables; the branch-circuit protective device may be sized up to the percentages in Table 430.52.

  • Ground-fault protection of equipment (GFPE) is required for some large services (over 1,000 A at 480Y/277 V) and is different from GFCI protection for personnel.

  • The equipment grounding conductor must be continuous and connected to every metal enclosure; a loose or missing EGC is a common cause of shock and is a frequent inspection failure.

Quick reference

Devices, Switches, Receptacles, and Outlet/Lighting Installations (continued)

  • A 20 A receptacle has a T-slot configuration; a 15 A receptacle has parallel slots; a 15 A receptacle cannot be used on a 30 A circuit.

  • Receptacle orientation and mounting height are not code-mandated in dwellings, but kitchen countertop receptacles must be installed so the cord does not cross a walkway or appliance.

  • Dimmer switches must be listed for the load type (LED, incandescent, fluorescent) and rated for the connected load; a neutral may be required for smart dimmers.

  • Ceiling fan boxes must be listed and marked for fan support; a standard octagon box is not permitted for a paddle fan unless listed for the purpose.

  • Receptacles in bathrooms must be GFCI-protected and located on the wall or counter, not within the shower or tub space; a receptacle is required within 3 ft of the outside edge of each basin.

  • Switches must be installed in a grounded metal or nonmetallic box; the switch yoke must be grounded where a metal faceplate is used, and plastic faceplates are permitted with nonmetallic boxes.

  • Lighting outlets in closets must maintain clearance from storage: typically 12 in. for surface-mounted fixtures and 6 in. for recessed fixtures, per 410.16.

Quick reference

Special Occupancies and Residential-Specific Requirements (continued)

  • A dwelling unit is a single unit providing complete independent living facilities, including permanent provisions for living, sleeping, cooking, and sanitation.

  • Accessory buildings and detached garages require a grounding electrode system if a feeder is installed; the feeder must include an equipment grounding conductor and a disconnecting means.

  • Swimming pool bonding: all metal parts of the pool structure, including the reinforcing steel, must be bonded with a solid copper conductor at least 8 AWG, and the bonding grid must be connected to the equipment grounding system.

  • Hot tubs and spas require a disconnecting means within sight and at least 5 ft away, GFCI protection, and a means to lock the disconnect.

  • Receptacles in laundry rooms and utility rooms require GFCI protection; a dedicated 20 A circuit is required for the laundry.

  • Attic and crawl space lighting: a lighting outlet is required in attics and crawl spaces where equipment requiring servicing is installed, with a switch at the access.

  • Guest rooms and dormitories have specific receptacle and GFCI requirements; verify the occupancy classification before applying dwelling rules.

Quick reference

Motors, Appliances, HVAC Equipment, and Dedicated Circuits (continued)

  • Motor full-load current tables (430.248 for single-phase, 430.250 for three-phase) are used for conductor and OCPD sizing; nameplate current is used for overload protection.

  • A motor circuit needs a disconnecting means, a controller, overload protection, and branch-circuit short-circuit and ground-fault protection; each has its own sizing rule.

  • The 125% multiplier applies to the motor FLC for conductor sizing and to the largest motor for feeder and service calculations (430.24).

  • Appliance branch circuits: a 20 A circuit may supply multiple appliance outlets if the total load does not exceed the circuit rating; a 30 A circuit is required for a range or dryer.

  • The nameplate on an HVAC unit lists minimum circuit ampacity and maximum fuse/breaker size; the conductor must be at least the MCA, and the breaker must not exceed the maximum.

  • A furnace requires a dedicated circuit and a disconnecting means within sight; the equipment grounding conductor must be installed and bonded to the unit.

  • Motor overload relays are set based on the motor's service factor: 115% of nameplate current for a 1.15 service factor, 125% for a 1.0 service factor motor.

Quick reference

Low-Voltage, Communications, and Signaling Systems (continued)

  • Class 2 circuits are limited to 100 VA and specific voltage/current combinations; Class 3 circuits allow higher energy but are still power-limited and must be separated from power conductors.

  • CATV and satellite cables require a grounding block bonded to the building grounding electrode system; the grounding conductor must be at least 14 AWG copper or equivalent.

  • Fiber optic cables are nonmetallic and do not require grounding, but they must be installed per the listing and separated from power conductors where required.

  • Fire alarm initiating devices must be installed per NFPA 72 and the manufacturer's instructions; spacing and mounting height are specified for smoke detectors.

  • Telephone and data cables must not be installed in the same raceway as power conductors unless the raceway is divided or the cable is listed for the purpose.

  • Low-voltage landscape lighting requires a listed transformer and cable; the cable must be buried at the required depth and protected where subject to damage.

  • Signaling system conductors must be identified at both ends and tagged; a wiring diagram must be available for inspection.

Quick reference

Safety, Inspection, and Code-Compliance Practices (continued)

  • Before energizing a new service, verify polarity, grounding, and breaker sizing; check that all connections are tight and that the panel is labeled with a directory.

  • A continuity test on the equipment grounding conductor verifies the path from the receptacle to the panel; a reading of more than a few ohms indicates a poor connection.

  • GFCI testers simulate a ground fault and should trip the device; if the tester does not trip it, the device or wiring is defective and must be corrected.

  • Arc-fault breakers have a test button; test at installation and periodically, and record the results for the inspection.

  • Working alone on energized equipment is discouraged; use a second person as a safety observer and have emergency contact information available.

  • A permit and inspection are required for new services, panel changes, and major alterations; working without a permit can result in fines and required removal of the work.

  • Keep a current copy of the adopted code and local amendments on site; the AHJ's interpretation controls when there is a conflict.

Quick reference

Georgia State Licensing Laws, Rules, and Business/Regulatory Requirements (continued)

  • The Georgia State Electrical Contractors Board requires applicants to pass a licensing exam and provide proof of experience; the exam covers code, theory, and Georgia law.

  • License renewal is typically every two years; late renewal may require a fee and continuing education, and an expired license cannot be used to contract.

  • A qualifying agent must be an owner, officer, or employee of the licensed business and must be responsible for the electrical work performed by the business.

  • Georgia law requires that advertisements include the license number; failure to do so is a violation and grounds for disciplinary action.

  • Contractors must provide written contracts for work over a threshold amount and must comply with lien and notice requirements under Georgia law.

  • The board may discipline a licensee for incompetence, code violations, fraud, or failure to obtain permits; penalties include fines, suspension, and revocation.

  • Local jurisdictions may require a separate business license and registration in addition to the state electrical license; verify requirements with the city or county.

Quick reference

General Electrical Knowledge, Definitions, and Code Administration (continued 2)

  • The NEC uses the term "shall" for mandatory requirements and "should" for recommendations; "shall" is enforceable, "should" is not.

  • A "dwelling unit" is a single unit with permanent provisions for living, sleeping, cooking, and sanitation; this definition drives many residential-specific rules.

  • The "service point" is where the serving utility's conductors connect to the premises wiring; the service equipment is the first disconnect after the service point.

  • The "grounded conductor" is the neutral; the "grounding conductor" is the equipment grounding conductor; the two are bonded only at the service.

  • The "ampacity" of a conductor is determined by the code tables and adjusted for ambient temperature and conductor count; it is not the same as the breaker rating.

  • The "AHJ" is the authority having jurisdiction, typically the local building official or electrical inspector, who interprets and enforces the code.

Quick reference

Wiring Methods and Materials (continued 2)

  • NM cable must be secured with staples or straps that do not damage the sheath; staples must be driven so they do not cut into the conductors.

  • Cable installed in a raceway must be listed for the purpose, and the raceway fill rules apply; NM cable is generally not permitted in conduit outdoors.

  • Boxes must be listed and marked with their cubic-inch capacity; a box without a marking cannot be used for conductor splices.

  • Conduit bodies must be supported and secured, and the number of conductors in a conduit body is limited by the marking and the fill rules.

  • Expansion and deflection fittings are required where raceways are subject to movement; rigid conduit must be supported and anchored at terminations.

  • The minimum burial depth for rigid metal conduit is 6 in.; for PVC it is 18 in.; for direct-buried cable it is 24 in.; verify with Table 300.5.

Quick reference

Branch Circuits, Feeders, and Service Calculations (continued 2)

  • A 20 A small-appliance circuit must supply only receptacles in the kitchen, dining, and similar areas; lighting and other loads cannot be connected to it.

  • The minimum number of small-appliance circuits is two; a kitchen with a large countertop area may require more to keep receptacle spacing within 24 in.

  • The service calculation must include the general lighting load, small appliance and laundry loads, fixed appliances, and the largest motor at 25%.

  • The optional method (220.82) allows a dwelling load calculation using 3 VA/sq ft plus 1,500 VA for each small appliance and laundry circuit, then applying demand factors.

  • A feeder to a detached garage must be sized for the load and must include a grounding conductor; a grounding electrode is required at the detached structure.

  • The service disconnect must be labeled with the service voltage and the available fault current; the panel directory must identify each circuit.

Quick reference

Grounding, Bonding, and Overcurrent Protection (continued 2)

  • The grounding electrode conductor must be continuous and not spliced except at an irreversible connection; it must be securely fastened and protected where exposed.

  • A concrete-encased electrode (Ufer) requires at least 20 ft of 1/2 in. reinforcing steel or 4 AWG bare copper in the footing; it is one of the preferred electrodes.

  • A ground ring requires at least 20 ft of 2 AWG bare copper buried at least 30 in. deep and is a permitted grounding electrode.

  • The equipment grounding conductor must be sized per Table 250.122 and increased proportionally if the circuit conductors are increased for voltage drop.

  • GFCI protection for personnel is required in specific locations; GFPE protection for equipment is a different requirement with different thresholds.

  • A breaker must be installed in a panelboard listed for that breaker type; using a breaker not listed for the panel voids the listing and is a violation.

Quick reference

Devices, Switches, Receptacles, and Outlet/Lighting Installations (continued 2)

  • Receptacles must be installed in a box and covered with a proper faceplate; gaps around the device are not permitted.

  • A switch controlling a lighting outlet must be installed in a location where it is readily accessible, typically at the entrance to the room.

  • A 3-way switch circuit requires two travelers and a common; the common terminal must be identified and connected to the ungrounded conductor or the load.

  • A 4-way switch is installed between the two 3-way switches and has two pairs of traveler terminals; it does not connect to the common.

  • Receptacles in kitchens must be GFCI-protected and installed so that no point along the countertop is more than 24 in. from a receptacle.

  • A receptacle is required within 3 ft of the outside edge of a bathroom basin; it must be GFCI-protected and not located within the shower or tub space.

Quick reference

Special Occupancies and Residential-Specific Requirements (continued 2)

  • A one-family dwelling requires at least one outdoor receptacle at the front and one at the back; both must be GFCI-protected and weather-resistant.

  • A garage requires at least one 20 A circuit for receptacles and a lighting outlet controlled by a switch at the entrance; the garage floor must be kept clear of cords.

  • A bathroom requires at least one 20 A circuit supplying only bathroom receptacles; the circuit may also supply a bathroom fan or lighting if the load is within the circuit rating.

  • A kitchen requires at least two 20 A small-appliance circuits; a separate circuit is required for the refrigerator if it is not on a general-purpose circuit.

  • A laundry area requires a 20 A circuit for the laundry receptacle; the circuit may supply only laundry outlets and associated equipment.

  • A pool or spa requires GFCI protection for all receptacles and lighting, equipotential bonding, and a disconnecting means within sight.

Quick reference

Motors, Appliances, HVAC Equipment, and Dedicated Circuits (continued 2)

  • A motor circuit's branch-circuit protective device may be sized up to 250% of the motor FLC for a standard breaker, or 175% for a non-time-delay fuse, per Table 430.52.

  • The motor overload device is sized to protect the motor from sustained overload; it is typically set at 115–125% of the motor nameplate current.

  • A motor disconnect must be within sight of the motor and controller, or capable of being locked open; it must open all ungrounded conductors.

  • HVAC equipment must be on a dedicated circuit; the conductor is sized to the nameplate MCA and the breaker to the MOCP.

  • A room air conditioner may be connected to a dedicated circuit sized per the nameplate; the breaker must not exceed the marked maximum.

  • A water heater requires a dedicated circuit and a disconnecting means within sight; the branch-circuit conductor is sized at 125% of the nameplate current for a continuous load.

Quick reference

Low-Voltage, Communications, and Signaling Systems (continued 2)

  • Class 2 cables must be separated from power conductors by at least 2 in. or a barrier; they must cross power conductors at right angles.

  • Communications cables entering a building must have a primary protector installed at the point of entry, and the protector must be bonded to the grounding electrode system.

  • Fire alarm circuits must be installed per NFPA 72 and Article 760; the cable must be listed for fire alarm use and separated from power wiring.

  • Low-voltage lighting transformers must be listed and accessible; the secondary conductors must be sized for the load and protected from damage.

  • Signaling circuits must be identified and labeled; a wiring diagram must be available for the inspector.

  • Fiber optic cables do not require grounding but must be installed per the listing and separated from power conductors where required.

Quick reference

Safety, Inspection, and Code-Compliance Practices (continued 2)

  • Before working on a circuit, de-energize it, lock the disconnect, and verify with a tester rated for the voltage; treat all conductors as energized until tested.

  • Use a non-contact voltage tester to verify the circuit is off, then confirm with a multimeter on the load side of the disconnect.

  • Inspection of a new service includes checking the grounding electrode conductor, the main bonding jumper, and the panel directory.

  • A GFCI tester should trip the device; if it does not, the device or wiring is defective and must be corrected before the inspection.

  • A permit and inspection are required for new services, panel changes, and major alterations; working without a permit can result in fines and required removal of the work.

  • Keep a current copy of the adopted code and local amendments on site; the AHJ's interpretation controls when there is a conflict.

Quick reference

Georgia State Licensing Laws, Rules, and Business/Regulatory Requirements (continued 2)

  • The Georgia State Electrical Contractors Board requires applicants to pass a licensing exam and provide proof of experience; the exam covers code, theory, and Georgia law.

  • License renewal is typically every two years; late renewal may require a fee and continuing education, and an expired license cannot be used to contract.

  • A qualifying agent must be an owner, officer, or employee of the licensed business and must be responsible for the electrical work performed by the business.

  • Georgia law requires that advertisements include the license number; failure to do so is a violation and grounds for disciplinary action.

  • Contractors must provide written contracts for work over a threshold amount and must comply with lien and notice requirements under Georgia law.

  • The board may discipline a licensee for incompetence, code violations, fraud, or failure to obtain permits; penalties include fines, suspension, and revocation.

Quick reference

General Electrical Knowledge, Definitions, and Code Administration (continued 3)

  • The NEC is published by NFPA and updated every three years; jurisdictions adopt specific editions, so verify the edition in force before applying a requirement.

  • The code uses "approved" to mean acceptable to the AHJ and "listed" to mean equipment evaluated by a nationally recognized testing laboratory such as UL.

  • A "branch circuit" is the circuit conductors between the final overcurrent device and the outlet(s); a "feeder" is between the service equipment and the final branch-circuit OCPD.

  • The "service" includes the conductors and equipment for delivering energy from the serving utility to the premises wiring system.

  • The "neutral" is the grounded conductor; it carries current in normal operation and must be white or gray, while the equipment grounding conductor must be green or bare.

  • The "hot" conductor is the ungrounded conductor; it must be black, red, blue, or another color other than white, gray, or green.

Quick reference

Wiring Methods and Materials (continued 3)

  • NM cable must be secured with staples or straps that do not damage the sheath; staples must be driven so they do not cut into the conductors.

  • Cable installed in a raceway must be listed for the purpose, and the raceway fill rules apply; NM cable is generally not permitted in conduit outdoors.

  • Boxes must be listed and marked with their cubic-inch capacity; a box without a marking cannot be used for conductor splices.

  • Conduit bodies must be supported and secured, and the number of conductors in a conduit body is limited by the marking and the fill rules.

  • Expansion and deflection fittings are required where raceways are subject to movement; rigid conduit must be supported and anchored at terminations.

  • The minimum burial depth for rigid metal conduit is 6 in.; for PVC it is 18 in.; for direct-buried cable it is 24 in.; verify with Table 300.5.

Quick reference

Branch Circuits, Feeders, and Service Calculations (continued 3)

  • A 20 A small-appliance circuit must supply only receptacles in the kitchen, dining, and similar areas; lighting and other loads cannot be connected to it.

  • The minimum number of small-appliance circuits is two; a kitchen with a large countertop area may require more to keep receptacle spacing within 24 in.

  • The service calculation must include the general lighting load, small appliance and laundry loads, fixed appliances, and the largest motor at 25%.

  • The optional method (220.82) allows a dwelling load calculation using 3 VA/sq ft plus 1,500 VA for each small appliance and laundry circuit, then applying demand factors.

  • A feeder to a detached garage must be sized for the load and must include a grounding conductor; a grounding electrode is required at the detached structure.

  • The service disconnect must be labeled with the service voltage and the available fault current; the panel directory must identify each circuit.

Quick reference

Grounding, Bonding, and Overcurrent Protection (continued 3)

  • The grounding electrode conductor must be continuous and not spliced except at an irreversible connection; it must be securely fastened and protected where exposed.

  • A concrete-encased electrode (Ufer) requires at least 20 ft of 1/2 in. reinforcing steel or 4 AWG bare copper in the footing; it is one of the preferred electrodes.

  • A ground ring requires at least 20 ft of 2 AWG bare copper buried at least 30 in. deep and is a permitted grounding electrode.

  • The equipment grounding conductor must be sized per Table 250.122 and increased proportionally if the circuit conductors are increased for voltage drop.

  • GFCI protection for personnel is required in specific locations; GFPE protection for equipment is a different requirement with different thresholds.

  • A breaker must be installed in a panelboard listed for that breaker type; using a breaker not listed for the panel voids the listing and is a violation.

Quick reference

Devices, Switches, Receptacles, and Outlet/Lighting Installations (continued 3)

  • Receptacles must be installed in a box and covered with a proper faceplate; gaps around the device are not permitted.

  • A switch controlling a lighting outlet must be installed in a location where it is readily accessible, typically at the entrance to the room.

  • A 3-way switch circuit requires two travelers and a common; the common terminal must be identified and connected to the ungrounded conductor or the load.

  • A 4-way switch is installed between the two 3-way switches and has two pairs of traveler terminals; it does not connect to the common.

  • Receptacles in kitchens must be GFCI-protected and installed so that no point along the countertop is more than 24 in. from a receptacle.

  • A receptacle is required within 3 ft of the outside edge of a bathroom basin; it must be GFCI-protected and not located within the shower or tub space.

Quick reference

Special Occupancies and Residential-Specific Requirements (continued 3)

  • A one-family dwelling requires at least one outdoor receptacle at the front and one at the back; both must be GFCI-protected and weather-resistant.

  • A garage requires at least one 20 A circuit for receptacles and a lighting outlet controlled by a switch at the entrance; the garage floor must be kept clear of cords.

  • A bathroom requires at least one 20 A circuit supplying only bathroom receptacles; the circuit may also supply a bathroom fan or lighting if the load is within the circuit rating.

  • A kitchen requires at least two 20 A small-appliance circuits; a separate circuit is required for the refrigerator if it is not on a general-purpose circuit.

  • A laundry area requires a 20 A circuit for the laundry receptacle; the circuit may supply only laundry outlets and associated equipment.

  • A pool or spa requires GFCI protection for all receptacles and lighting, equipotential bonding, and a disconnecting means within sight.

Quick reference

Motors, Appliances, HVAC Equipment, and Dedicated Circuits (continued 3)

  • A motor circuit's branch-circuit protective device may be sized up to 250% of the motor FLC for a standard breaker, or 175% for a non-time-delay fuse, per Table 430.52.

  • The motor overload device is sized to protect the motor from sustained overload; it is typically set at 115–125% of the motor nameplate current.

  • A motor disconnect must be within sight of the motor and controller, or capable of being locked open; it must open all ungrounded conductors.

  • HVAC equipment must be on a dedicated circuit; the conductor is sized to the nameplate MCA and the breaker to the MOCP.

  • A room air conditioner may be connected to a dedicated circuit sized per the nameplate; the breaker must not exceed the marked maximum.

  • A water heater requires a dedicated circuit and a disconnecting means within sight; the branch-circuit conductor is sized at 125% of the nameplate current for a continuous load.

Quick reference

Low-Voltage, Communications, and Signaling Systems (continued 3)

  • Class 2 cables must be separated from power conductors by at least 2 in. or a barrier; they must cross power conductors at right angles.

  • Communications cables entering a building must have a primary protector installed at the point of entry, and the protector must be bonded to the grounding electrode system.

  • Fire alarm circuits must be installed per NFPA 72 and Article 760; the cable must be listed for fire alarm use and separated from power wiring.

  • Low-voltage lighting transformers must be listed and accessible; the secondary conductors must be sized for the load and protected from damage.

  • Signaling circuits must be identified and labeled; a wiring diagram must be available for the inspector.

  • Fiber optic cables do not require grounding but must be installed per the listing and separated from power conductors where required.

Quick reference

Safety, Inspection, and Code-Compliance Practices (continued 3)

  • Before working on a circuit, de-energize it, lock the disconnect, and verify with a tester rated for the voltage; treat all conductors as energized until tested.

  • Use a non-contact voltage tester to verify the circuit is off, then confirm with a multimeter on the load side of the disconnect.

  • Inspection of a new service includes checking the grounding electrode conductor, the main bonding jumper, and the panel directory.

  • A GFCI tester should trip the device; if it does not, the device or wiring is defective and must be corrected before the inspection.

  • A permit and inspection are required for new services, panel changes, and major alterations; working without a permit can result in fines and required removal of the work.

  • Keep a current copy of the adopted code and local amendments on site; the AHJ's interpretation controls when there is a conflict.

Quick reference

Georgia State Licensing Laws, Rules, and Business/Regulatory Requirements (continued 3)

  • The Georgia State Electrical Contractors Board requires applicants to pass a licensing exam and provide proof of experience; the exam covers code, theory, and Georgia law.

  • License renewal is typically every two years; late renewal may require a fee and continuing education, and an expired license cannot be used to contract.

  • A qualifying agent must be an owner, officer, or employee of the licensed business and must be responsible for the electrical work performed by the business.

  • Georgia law requires that advertisements include the license number; failure to do so is a violation and grounds for disciplinary action.

  • Contractors must provide written contracts for work over a threshold amount and must comply with lien and notice requirements under Georgia law.

  • The board may discipline a licensee for incompetence, code violations, fraud, or failure to obtain permits; penalties include fines, suspension, and revocation.