gh-ec-electrical-wiring-domestic flashcards
gh-ec-electrical-wiring-domestic · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ohm's Law
- In a DC or purely resistive circuit, voltage equals current times resistance (E = I × R). Rearranged, current equals voltage divided by resistance, and resistance equals voltage divided by current.
- Continuous load definition
- A load expected to operate at maximum current for three hours or more. Conductors and overcurrent devices serving it are generally sized at 125% of the continuous load plus 100% of noncontinuous load.
- Box fill counting
- Count 14 AWG as 2.0 cubic inches, 12 AWG as 2.25, and 10 AWG as 2.5. Add one conductor volume for each device yoke, each clamp, and the grounding conductors.
- NM cable support intervals
- Nonmetallic-sheathed cable must be secured within 12 inches of each box and at intervals not exceeding 4.5 feet. Bored holes require support within 12 inches of the hole.
- Small-appliance branch circuits
- Dwellings require at least two 20-ampere circuits for kitchen and dining receptacles, with no other outlets connected. Each circuit counts 1,500 volt-amperes in the load calculation.
- General lighting load dwelling
- Dwelling general lighting is calculated at 3 volt-amperes per square foot. Demand factors in Table 220.42 then apply, with the first 3,000 volt-amperes at 100 percent.
- Grounding electrode conductor sizing
- Sized from Table 250.66 based on the largest service conductor. A concrete-encased electrode or ground ring needs only a 4 AWG copper conductor regardless of service size.
- Single electrode rule
- A single rod, pipe, or plate electrode must have 25 ohms or less resistance to earth, or it must be supplemented by one additional electrode of any permitted type.
- Receptacle spacing rule
- In habitable rooms, wall-space receptacles must be installed so no point along the floor line is more than 6 feet from a receptacle, and any wall space 2 feet or wider needs one.
- Ungrounded receptacle replacement
- A grounding-type receptacle may replace an ungrounded one only with GFCI protection and a marking reading "No Equipment Ground." The equipment grounding conductor is not connected.
- Bathroom circuit requirement
- At least one 20-ampere branch circuit must supply only bathroom receptacles. All bathroom receptacles require GFCI protection and none may be inside the shower or tub space.
- Kitchen countertop receptacle rule
- Countertop receptacles must be GFCI-protected and installed so no point along the countertop is more than 24 inches from a receptacle. Islands and peninsulas also require one.
- Motor conductor sizing
- Motor branch-circuit conductors are sized at 125% of the full-load current from Article 430 tables, not the nameplate current, unless a specific listed motor exception applies.
- HVAC nameplate sizing
- A central air conditioner or heat pump lists minimum circuit ampacity and maximum overcurrent protection. Conductors must be at least the MCA and the breaker must not exceed the MOCP.
- Class 2 separation rule
- Class 2 cables must be separated from power conductors by at least 2 inches or a permanent barrier, and must cross power conductors at right angles where practical.
- Communications primary protector
- Communications cables entering a building require a listed primary protector at the point of entry, bonded to the building grounding electrode system with a minimum 6 AWG copper conductor.
- Working clearance 120 volts
- For equipment operating at 0 to 150 volts to ground, the minimum working space depth is 3 feet, with 30 inches of width and 6.5 feet of headroom.
- GFCI tester result
- A GFCI tester simulates a ground fault and should trip the device. If it does not trip, the device or its wiring is defective and must be corrected before final inspection.
- Georgia license classes
- Georgia issues electrical contractor licenses in classes, including Class I for unlimited work and Class II limited to smaller services and specified voltage limits. The class defines the scope.
- Qualifying agent role
- A licensed business must designate a qualifying agent who holds the license, is an owner, officer, or employee, and is responsible for the electrical work the business performs.
- Series circuit characteristics
- Current is the same through every component, resistances add directly, and voltage divides across the loads in proportion to their resistance.
- Conduit fill percentages
- For raceway fill, one conductor may occupy up to 53 percent of the interior cross-section, two conductors 31 percent, and three or more conductors 40 percent.
- Voltage drop formula
- For a single-phase two-wire circuit, voltage drop equals 2 times K times current times length divided by circular mils, where K is about 12.9 for copper.
- Main bonding jumper location
- The main bonding jumper connects the grounded service conductor to the service equipment enclosure and grounding bus. It is installed only at the service, never at subpanels.
- Three-way switch travelers
- A three-way switch has two traveler terminals and one common terminal. The common connects to the ungrounded supply or the load, and travelers run between the two switches.
- Garage receptacle requirement
- A dwelling garage requires at least one 20-ampere branch circuit for receptacles, GFCI-protected, plus a lighting outlet controlled by a switch at the vehicle entrance.
- Motor overload protection setting
- Motor overload relays are set at 115 percent of nameplate current for a motor with a 1.15 service factor, and 125 percent for a motor with a 1.0 service factor.
- Fire alarm circuit classes
- Class A initiating circuits survive a single open or ground fault and continue to operate, while Class B circuits do not survive a single open and signal a trouble condition.
- Lockout tagout procedure
- De-energize the circuit, lock the disconnect, and verify with a tester rated for the voltage. Treat all conductors as energized until testing proves otherwise.
- Georgia continuing education
- Georgia electrical contractors must complete continuing education hours each renewal cycle, commonly 8 hours per two-year cycle, including code-update content.
- Ampacity adjustment factors
- Conductor ampacity is corrected for ambient temperature and adjusted when more than three current-carrying conductors share a raceway or cable, using the tables in 310.15.
- Equipment grounding conductor sizing
- The equipment grounding conductor is sized from Table 250.122 based on the rating of the overcurrent device protecting the circuit, not on the conductor ampacity.