HI Fire Sprinkler case studies
HI Fire Sprinkler · Put your knowledge to work in context.
NICET Automatic Sprinkler System Layout is a work-element certification for people who design and lay out automatic sprinkler systems - typically layout technicians, designers, and fire protection engineering technologists working for contractors, design firms, or engineering departments. It is offered at Levels I through IV, and each level pairs a multiple-choice exam with documented work experience; the upper levels also involve a technical report or project review. The HI Fire Sprinkler case studies are 5 cases and about 3,112 words.
1Four-Storey Mixed-Use Building - Which Sprinkler Standard?
A four-storey mixed-use building is proposed with a 17.5 m eave height. The ground floor is an 800 m² clothing and furniture store; the upper three floors are open-plan offices, each 800 m².
622 words, about 3 min2Town Main Capacity and Fire Pump Suction
A proposed eight-storey office building has a wet-pipe sprinkler system with a design demand of 2,600 L/min at 4.2 bar at the base of the riser. The only supply is a 150 mm town main.
610 words, about 3 min3Rack Storage of Group A Plastics - Contractor's OH2 Proposal
A 60 m x 40 m single-storey warehouse has a 10 m ceiling and double-row racks 6.5 m high. The commodity is cartoned unexpanded Group A plastic toys.
603 words, about 3 min4Beam Pockets in a Parking Garage
A 3.4 m high parking garage has precast concrete beams 350 mm deep at 2.2 m centres, forming 2.2 m x 5.0 m bays. The occupancy is ordinary hazard Group 1.
634 words, about 3 min5Main Drain Test Trend After Five Years
A wet-pipe system serving an eight-storey office building has a 150 mm riser and a 100 mm main drain. At acceptance five years ago, the main drain test recorded 6.4 bar static and 4.9 bar residual.
643 words, about 3 min