HI Fire Sprinkler flashcards
HI Fire Sprinkler · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- NFPA 13 scope
- Sets minimum requirements for design and installation of automatic sprinkler systems in commercial, industrial, and storage occupancies, excluding one- and two-family dwellings covered by NFPA 13D.
- NFPA 13R
- Covers automatic sprinkler systems in residential occupancies up to and including four stories, with reduced design criteria compared with full NFPA 13 systems.
- Listing versus approval
- Listing means a product has been tested by a recognized laboratory to a published standard; approval means the authority having jurisdiction has accepted the product or installation.
- Light hazard density
- Typically 0.10 gpm per square foot over the hydraulically most remote 1,500 square feet, applied to occupancies such as offices, schools, and churches.
- Ordinary Hazard Group 2
- Design density of about 0.20 gpm per square foot over 1,500 square feet for occupancies such as machine shops, repair garages, and post offices.
- Extra Hazard Group 1
- Design density of about 0.30 gpm per square foot over 2,500 square feet for occupancies with moderate quantities of flammable liquids or high heat release.
- Dry system area increase
- Dry pipe and double-interlock pre-action systems require the remote area to be increased, commonly by 30 percent, because water delivery is delayed after a sprinkler opens.
- Hose stream allowance
- The flow added to the sprinkler demand at the base of the riser to account for fire department hose use, varying with hazard and standpipe presence.
- Hazen-Williams formula
- Friction loss in psi per foot equals 4.52 times flow in gpm raised to 1.85, divided by roughness coefficient raised to 1.85 times inside diameter raised to 4.87.
- Elevation pressure conversion
- Each foot of elevation change converts to 0.433 psi; pressure decreases with rise and increases with drop in the piping system.
- Waterflow test data
- Static pressure, residual pressure, and flow rate recorded at a hydrant; results are plotted and extrapolated to estimate pressure at the required fire flow.
- Safety margin
- The required cushion between available supply pressure and system demand pressure, ensuring the demand point falls below the water supply curve.
- Backflow preventer loss
- A fixed pressure loss added to hydraulic calculations for each backflow prevention device, along with losses from check valves and dry pipe valves.
- Sprinkler temperature rating
- Ordinary ratings of 135 to 170 degrees Fahrenheit; intermediate 175 to 225 degrees; high 250 to 300 degrees. Rating must exceed maximum ceiling temperature.
- Standard spray deflector distance
- Deflectors of standard spray sprinklers are positioned 1 to 12 inches below the ceiling, with specific rules for concealed and recessed types.
- Light hazard spacing
- Maximum spacing generally 15 feet between sprinklers and 15 feet between branch lines, with coverage not exceeding 225 square feet per sprinkler.
- Sidewall sprinkler limits
- Sidewall sprinklers have reduced coverage areas and specific distance-from-wall and deflector rules compared with pendant and upright sprinklers.
- Quick-response reduction
- Quick-response sprinklers may allow a limited reduction in design area for some light and ordinary hazard applications, subject to conditional requirements.
- Riser check valve
- A valve in the riser that prevents water from flowing back into the supply, protecting the public water system from contamination.
- Dry pipe valve function
- Holds air pressure above and water below; when a sprinkler opens and air escapes, the valve trips and admits water into the piping.
- Pre-action valve
- Requires a detection signal before water enters the piping; single-interlock admits water on detection, double-interlock also requires a sprinkler to open.
- Inspector's test valve
- Located at the hydraulically most remote point, it simulates a single sprinkler flow to test alarms, waterflow switches, and dry pipe valve trip time.
- CPVC limitations
- CPVC piping is listed for specific light hazard and residential applications, with limitations on temperature, pressure, and exposure to sunlight.
- Hydrostatic test
- Piping is tested at 200 psi for two hours, or at 50 psi above working pressure when working pressure exceeds 150 psi, with no leakage allowed.
- Main drain test
- Records static and residual pressure at the riser; a significant drop compared with prior tests indicates a supply or valve problem.
- Dry pipe trip test
- Confirms the dry pipe valve trips at the manufacturer's specified air pressure and records the time required for water to reach the test connection.
- Underground flushing
- Underground mains are flushed before connection to the sprinkler system at a velocity sufficient to clear debris, preventing clogging of sprinklers and valves.
- Working plan contents
- Shows occupancy, hazard classification, sprinkler types and spacing, pipe sizes and materials, hanger locations, control valves, and test connections.
- Hydraulic calculation submittal
- Must identify the hydraulically most remote area, node-by-node pipe lengths, fittings, elevations, and the resulting demand at the supply point.
- As-built drawings
- Reflect field changes from approved plans; deviations require re-review and approval before installation proceeds.
- Impairment procedure
- When a system is taken out of service, notify the owner, insurer, and fire department, and provide a fire watch or temporary protection as required.
- Change order
- A written document authorizing a change to the contract scope, such as revised sprinkler design, requiring coordination with the owner, architect, and authority having jurisdiction.