CIC Grade A Electrical Trade Test study materials
CIC Grade A Electrical Trade Test study resources

CIC Grade A Electrical Trade Test cheat sheet

CIC Grade A Electrical Trade Test · Keep the key ideas within reach.

Quick reference

Construction-related E&M Trades

  • Japanese electrical installation practice separates 一般用電気工作物 (general-use, ≤600 V, ≤50 kW demand) from 事業用電気工作物 (business-use); business-use work requires a 電気工事士 or supervised 電気主任技術者.

  • Cable current-carrying capacity derating: apply ambient temperature correction factor and grouping (number of circuits in the same conduit or rack) factor multiplicatively to the base table value; never add them.

  • Voltage drop for a single-phase two-wire circuit: e = 2 × L × I × r (r in Ω/m); for three-phase three-wire use e = √3 × L × I × r. Keep drop within 2% for branch circuits and 5% total.

  • Conduit fill: for three or more conductors, total conductor cross-sectional area must not exceed 40% of the conduit internal area; two conductors 33%, one conductor 53%.

  • Grounding: 接地工事 types are A (400 V or less, 10 Ω or less in principle), C (200 V class, 100 Ω or less), and D (300 V or less low-current, 500 Ω or less); A-class applies to 400 V circuits and metal enclosures of high-voltage equipment.

  • Fire-resistant compartment penetration: seal with approved firestop rated to the same fire resistance as the wall or floor, and separate power and communication cables in dedicated raceways.

  • Protection coordination: an overcurrent device must clear a fault before conductor insulation is damaged, so the device rated current must not exceed the cable's allowable current after derating.

  • Cable tray and busway installation requires support spacing per manufacturer and seismic bracing in Japan per 建築設備耐震設計・施工指針 when the building requires it.

  • Insulation resistance acceptance: a 300 V or less circuit must read 0.1 MΩ or more with a 500 V insulation tester; 300 V to 750 V circuits require 0.2 MΩ or more.

Quick reference

Trade Test for Grade A Electrical Work

  • Grade A (第一種電気工事士) scope covers general-use electrical work up to 600 V plus special high-voltage (高圧) work up to 7,000 V for certain installations; Grade B (第二種) is limited to general-use work at 600 V or less.

  • Practical exam (技能試験) time is 40 minutes for the standard problem and 60 minutes for the composite problem; points are lost for missing parts, wrong wiring, and unfinished work.

  • Common practical failures: reversing the 100 V/200 V polarity, leaving a conductor unconnected, wrong ring-sleeve crimp, and insufficient strip length causing exposed copper.

  • Wiring methods in the practical test: VVF cable is stripped with a VVF stripper, ring sleeves are crimped with a dedicated tool, and connections are made with 差込コネクタ (push-in connectors) or terminal screws.

  • Illumination circuit switching: a 3-way switch (3路スイッチ) uses three wires between the two switches; a 4-way switch (4路スイッチ) has four terminals and is placed between two 3-way switches.

  • Pilot lamp and switch wiring: connect the pilot lamp in parallel with the load so it indicates whether the load is energized, not in series with the load.

  • Leakage breaker (漏電遮断器) rating: select a sensitivity current of 30 mA or less for human protection and 200 mA or less for fire protection of circuits.

  • Conductor color convention in Japan: black = hot (非接地側), white = neutral (接地側), green = ground; green must never be used as a live conductor.

Quick reference

Construction-related E&M Trades

  • Cable bending radius: for fixed installation of low-voltage cable, keep the inner radius at 6 times the cable diameter or more; for movable/flexible cable use 4 times or more.

  • Cable support spacing for VVF on insulators is about 2 m; for vertical runs on a wall, support at every floor and within 1 m of the top and bottom.

  • Switch and outlet height in Japanese residential practice: switches about 1,200 mm above floor, outlets about 300 mm, and kitchen counter outlets about 1,000 mm above the counter.

  • Conduit bending: the total bend between pull points must not exceed 360 degrees, and every bend must be made with a bender to avoid kinking and reduced cross-section.

  • Ground-fault protection: a 漏電遮断器 with 30 mA sensitivity must be installed on wet-location circuits, outdoor outlets, and temporary construction power circuits.

  • Load calculation for a dwelling: general lighting load is calculated at 30 VA per square meter for the floor area, plus specific appliance loads; apply demand factors per the 内線規程.

  • Insulation resistance test: use a 500 V megohmmeter for 300 V or less circuits; disconnect the main breaker and appliances before testing to avoid damage and false readings.

Quick reference

Trade Test for Grade A Electrical Work

  • The written exam has two parts: 筆記試験 with 一般問題 and 配線図問題; the practical exam (技能試験) is a separate pass/fail hurdle taken after passing the written exam.

  • General questions cover 電気理論, 配電理論, 配線設計, 電気機器, 発電・送電・変電, 電気応用, 電気工事用材料, and 施工方法.

  • 配線図問題: read the single-line diagram and answer questions on wire size, breaker rating, switch connections, and grounding; check the legend for cable symbols.

  • Common trap: a 3-way switch circuit requires the traveler wires between the two switches; the common terminal must connect to the load or the source, not to a traveler.

  • Load current calculation: for a single-phase 100 V load, I = P / (V × power factor); for a three-phase 200 V load, I = P / (√3 × V × power factor).

  • Breaker selection for a motor: use a breaker rated at 3 times the motor's rated current for direct-on-line starting, or per the manufacturer's recommended table.

  • Cable ampacity: VVF 2.0 mm² in conduit carries about 24 A (single-phase two-wire, 30 °C ambient), and 1.6 mm² carries about 17 A; always apply derating factors.

  • Practical exam scoring: each connection point is checked for correct wiring, correct parts, and correct finish; a single wrong connection can fail the whole problem.

Quick reference

Construction-related E&M Trades

  • Fire alarm and emergency lighting are separate low-voltage systems: emergency lighting must maintain 30 minutes of illumination at 1 lx or more on the floor of the evacuation route.

  • Cable separation: keep power and signal cables at least 300 mm apart, or use a metal barrier, to reduce electromagnetic interference in communication and control circuits.

  • Bus duct (busway) installation requires a torque check on joint bolts per the manufacturer's table and a phase-sequence check before energizing.

  • Grounding conductor sizing: the grounding conductor cross-section must be at least the phase conductor up to 16 mm², and at least half the phase conductor for larger sizes, per the 内線規程.

  • Panelboard labeling: every circuit breaker must be labeled with the circuit name and rating, and a single-line diagram must be posted near the panel.

  • Testing before energizing: perform insulation resistance, continuity, and polarity checks, and verify that all terminal screws are torqued to the specified value.

  • Cable derating for buried conduit: apply a soil thermal resistivity correction and a depth correction in addition to ambient temperature and grouping factors.

Quick reference

Trade Test for Grade A Electrical Work

  • Passing criteria: the written exam requires a score of 60% or more overall, and the practical exam is pass/fail based on completing the specified circuit correctly within the time limit.

  • Material identification: know the difference between VVF (vinyl insulated vinyl sheathed flat cable) and CV cable (cross-linked polyethylene insulated PVC sheathed), and where each is used.

  • Switch symbols in 配線図: a 3-way switch is drawn with three terminals, a 4-way switch with four; a 漏電遮断器 is drawn with a test button symbol.

  • Transformer and motor questions: for a single-phase transformer, V1/V2 = N1/N2; for a three-phase induction motor, synchronous speed Ns = 120 f / P.

  • Power factor correction: a capacitor bank connected in parallel raises the power factor; the required capacitor kvar = P × (tan θ1 − tan θ2).

  • Cable selection: use 1.6 mm² for lighting circuits, 2.0 mm² for general outlet circuits, and 2.0 mm² or larger for 200 V circuits, per the 内線規程.

  • Practical exam tools: bring wire strippers, crimping tool, screwdrivers, nippers, and a scale; the test site provides the cable, boxes, and parts.

  • Common mistake: using the wrong ring sleeve size for the conductor; the sleeve must match the conductor cross-section and the terminal screw size.

Quick reference

Construction-related E&M Trades

  • Conduit installation: use a 1/2-inch or 3/4-inch conduit for branch circuits; the conduit must be supported within 1 m of each box and at intervals of 2 m or less.

  • Cable tray fill: the total cable cross-section must not exceed 40% of the tray's usable cross-section for power cables, and 50% for control cables.

  • Switchboard clearance: maintain at least 1.2 m of working space in front of a switchboard, and 0.8 m at the sides and rear where access is required.

  • Grounding electrode: a copper-clad steel rod of 14 mm diameter and 1.5 m length is a standard 接地極; the resistance must be 10 Ω or less for A-class grounding.

  • Cable termination: strip the insulation to the correct length, crimp the terminal, and apply heat-shrink tubing; exposed copper strands are a defect.

  • Load balance: distribute single-phase loads evenly across the three phases to keep the neutral current low and avoid overload on one phase.

Quick reference

Trade Test for Grade A Electrical Work

  • Exam-day checklist: bring the admission ticket, ID, writing tools, and a watch; the practical exam does not allow sharing tools.

  • Time management: in the 40-minute practical problem, allocate about 10 minutes for layout and stripping, 25 minutes for wiring, and 5 minutes for final inspection.

  • Wiring sequence: connect the ground first, then the neutral, then the hot; this reduces the risk of accidental short circuits during assembly.

  • Inspection points: check that all screws are tight, no copper is exposed, the cable is not pinched, and the circuit operates as specified.

  • Written exam strategy: answer the 配線図 questions first if you are confident, then return to calculation questions; do not leave blanks because there is no penalty for guessing.

  • Regulation reference: the 電気設備技術基準 and 内線規程 are the primary sources for installation rules; the exam tests their application, not memorization of article numbers.

  • Motor control: a magnetic contactor with a thermal overload relay provides overload protection; the thermal relay setting is usually the motor's rated current.

  • Cable color code in a three-phase system: black, red, and blue for the three phases, white for neutral, and green for ground.

Quick reference

Construction-related E&M Trades

  • Lightning protection: a lightning rod must be connected to a grounding electrode with a resistance of 10 Ω or less, and the down conductor must be as straight as possible.

  • Cable in a wet location: use a cable with a moisture-resistant sheath such as CV or a cable in a sealed conduit; VVF is not suitable for direct burial.

  • Panelboard grounding: the neutral bar and ground bar must be separate in a subpanel, and bonded only at the main service panel.

  • Firestop and penetration: after installing cables through a fire-rated wall, seal the opening with a firestop material rated for the same fire resistance as the wall.

  • Voltage drop in a long run: if the drop exceeds 5%, increase the conductor size rather than adding a second circuit, because the drop is proportional to the conductor resistance.

  • Insulation resistance: a reading below 0.1 MΩ indicates a fault; locate it by disconnecting sections and testing each segment separately.

Quick reference

Trade Test for Grade A Electrical Work

  • Question types: 一般問題 are short-answer or multiple-choice; 配線図問題 are multiple-choice based on a diagram; the practical exam is a hands-on wiring task.

  • Common calculation: for a 100 V, 1 kW load, the current is 10 A; a 2.0 mm² VVF cable in conduit can carry this load with margin.

  • Transformer efficiency: η = output / input × 100%; losses are copper loss (proportional to current squared) plus iron loss (constant).

  • Illumination: the required illuminance for a living room is about 100 lx, for a kitchen about 300 lx, and for an office about 500 lx.

  • Cable derating example: a 2.0 mm² VVF cable rated 24 A at 30 °C, in a conduit with 4 circuits at 40 °C, applies a temperature factor of about 0.82 and a grouping factor of about 0.7, giving about 13.8 A.

  • Switch wiring: a single-pole switch is connected in the hot conductor, never in the neutral, so that the load is de-energized when the switch is off.

  • Practical exam parts: the test provides the cable, boxes, switches, outlets, and connectors; you must supply the tools and consumables such as tape and sleeves.

Quick reference

Construction-related E&M Trades

  • Cable support in a vertical shaft: support the cable at every floor and within 1 m of the top and bottom, and use a cable grip to relieve tension on the conductor.

  • Conduit expansion: install expansion fittings where the conduit run crosses a building expansion joint, and leave a gap of about 20 mm.

  • Grounding of metal enclosures: every metal box, panel, and conduit must be bonded to the grounding conductor with a listed bonding jumper or fitting.

  • Cable ampacity correction for ambient temperature: use the factor for the actual ambient, not the standard 30 °C, and apply the factor for the number of circuits in the same raceway.

  • Emergency power: a generator or battery must supply the emergency lighting and fire alarm circuits within 10 seconds of a power failure, per the 消防法.

  • Inspection before handover: verify the insulation resistance, grounding resistance, polarity, and breaker ratings, and record the results in the inspection report.

Quick reference

Trade Test for Grade A Electrical Work

  • Exam schedule: the written exam is usually held in spring and autumn; the practical exam is held after the written results are announced, typically in summer and winter.

  • Eligibility: Grade A requires no work experience, but the practical exam must be taken within a set period after passing the written exam.

  • Common practical problem: a two-way switch circuit with a pilot lamp, an outlet, and a leakage breaker; practice the layout and wiring sequence until it is automatic.

  • Cable stripping: use a VVF stripper set to the correct size; strip about 15 mm for a ring sleeve and 10 mm for a push-in connector.

  • Ring sleeve crimping: insert the conductor fully into the sleeve, crimp with the dedicated tool, and check that the sleeve is not cracked and the conductor cannot be pulled out.

  • Continuity test: use a tester to confirm each connection before energizing; a missing connection is the most common cause of failure.

  • Regulation: the 電気工事士法 requires a qualified person for the work; the exam tests the knowledge and skill required by that law.

  • Time limit: the practical exam ends exactly at the time limit; unfinished work is scored as incomplete, so leave time for the final inspection.

Quick reference

Construction-related E&M Trades

  • Cable tray grounding: bond each section of the tray to the grounding conductor, and use a bonding jumper across the joint if the tray is painted.

  • Switchboard ventilation: keep the ventilation openings clear and maintain the manufacturer's clearance to walls and other equipment.

  • Cable derating for high ambient: in a boiler room or attic, use the correction factor for the actual temperature, which may be 0.5 or lower at 50 °C.

  • Grounding resistance measurement: use the fall-of-potential method with two auxiliary electrodes, and space them at least 20 m apart for accurate results.

  • Insulation resistance test voltage: use 500 V for 300 V or less circuits and 1000 V for 300 V to 750 V circuits; never use a higher voltage than the circuit rating.

  • Panelboard circuit identification: label each breaker with the room and load, and update the label when a circuit is changed.

Quick reference

Trade Test for Grade A Electrical Work

  • Study focus: the 配線図 problem is often the deciding factor; practice reading single-line diagrams and identifying the correct wire size and breaker rating.

  • Common formula: for a three-phase load, I = P / (√3 × V × cos θ); for a single-phase load, I = P / (V × cos θ).

  • Cable size selection: use the 内線規程 table for the allowable current, then apply the temperature and grouping factors, and check the voltage drop.

  • Breaker coordination: the breaker rating must be less than or equal to the cable's allowable current after derating, and greater than the load current.

  • Practical exam layout: mark the positions of the boxes and switches on the board before wiring, and keep the cable runs straight and neat.

  • Common failure: reversed polarity at the outlet; check that the hot wire connects to the shorter slot and the neutral to the longer slot.

  • Exam tip: read the entire problem before starting, and identify the required parts and connections; a missed part is a lost point.

Quick reference

Construction-related E&M Trades

  • Cable in a hazardous location: use a cable with a flame-retardant sheath and seal the conduit at the boundary of the hazardous area.

  • Grounding of a transformer: the secondary neutral must be grounded at the transformer or at the first disconnect, and the grounding conductor must be sized per the 内線規程.

  • Cable support for a horizontal run: support at intervals of 2 m or less, and within 1 m of each box or fitting.

  • Insulation resistance of a motor: a reading below 1 MΩ indicates moisture or a fault; dry the motor before energizing.

  • Panelboard working space: maintain at least 1.2 m in front of the panel, and do not store materials in the working space.

  • Cable derating for a buried conduit: apply a soil thermal resistivity correction and a depth correction in addition to the ambient and grouping factors.

Quick reference

Trade Test for Grade A Electrical Work

  • Question type: the written exam includes true/false and multiple-choice questions; the practical exam is a hands-on task scored by inspectors.

  • Common topic: the 電気設備技術基準 requires that a circuit be protected against overload and short circuit, and that the grounding be appropriate for the circuit voltage.

  • Cable ampacity: a 1.6 mm² VVF cable carries about 17 A at 30 °C; apply derating for higher ambient and for multiple circuits in the same conduit.

  • Switch connection: a 3-way switch has a common terminal and two traveler terminals; the common terminal connects to the source or the load.

  • Practical exam: the test board has pre-marked positions; follow the drawing exactly and do not improvise the layout.

  • Common mistake: using a ring sleeve that is too large for the conductor, which causes a loose connection and a failed inspection.

  • Exam tip: bring a spare tester and spare sleeves; a failed tool can end the practical exam.

Quick reference

Construction-related E&M Trades

  • Cable tray fill: for power cables, the total cross-section must not exceed 40% of the tray's usable cross-section; for control cables, 50%.

  • Grounding electrode: a copper-clad steel rod of 14 mm diameter and 1.5 m length is standard; the resistance must be 10 Ω or less for A-class grounding.

  • Cable termination: strip the insulation to the correct length, crimp the terminal, and apply heat-shrink tubing; exposed copper strands are a defect.

  • Load balance: distribute single-phase loads evenly across the three phases to keep the neutral current low.

  • Firestop: seal every penetration of a fire-rated wall or floor with a material rated for the same fire resistance.

  • Insulation resistance: a reading below 0.1 MΩ indicates a fault; locate it by testing each segment separately.

Quick reference

Trade Test for Grade A Electrical Work

  • Exam structure: the written exam is 筆記試験 with 一般問題 and 配線図問題; the practical exam is 技能試験 with a 40-minute standard problem and a 60-minute composite problem.

  • Passing score: the written exam requires 60% or more overall; the practical exam is pass/fail based on completing the circuit correctly.

  • Common calculation: for a single-phase 100 V, 1 kW load, I = 10 A; for a three-phase 200 V, 5 kW load with power factor 0.8, I = 18 A.

  • Cable selection: use 1.6 mm² for lighting, 2.0 mm² for outlets, and 2.0 mm² or larger for 200 V circuits, per the 内線規程.

  • Practical exam: connect the ground first, then the neutral, then the hot; check all screws and connections before energizing.

  • Common trap: a 3-way switch circuit requires traveler wires between the switches; the common terminal must not connect to a traveler.

  • Regulation: the 電気工事士法 requires a qualified person for the work; the exam tests the knowledge and skill required by that law.

Quick reference

Construction-related E&M Trades

  • Cable in a wet location: use a cable with a moisture-resistant sheath such as CV or a cable in a sealed conduit; VVF is not suitable for direct burial.

  • Panelboard grounding: the neutral bar and ground bar must be separate in a subpanel, and bonded only at the main service panel.

  • Voltage drop: if the drop exceeds 5%, increase the conductor size rather than adding a second circuit.

  • Insulation resistance: use 500 V for 300 V or less circuits and 1000 V for 300 V to 750 V circuits.

  • Switchboard clearance: maintain at least 1.2 m of working space in front of a switchboard, and 0.8 m at the sides and rear where access is required.

  • Cable support: support at intervals of 2 m or less, and within 1 m of each box or fitting.

Quick reference

Trade Test for Grade A Electrical Work

  • Question types: 一般問題 are short-answer or multiple-choice; 配線図問題 are multiple-choice based on a diagram; the practical exam is a hands-on wiring task.

  • Common calculation: for a 100 V, 1 kW load, the current is 10 A; a 2.0 mm² VVF cable in conduit can carry this load with margin.

  • Transformer efficiency: η = output / input × 100%; losses are copper loss (proportional to current squared) plus iron loss (constant).

  • Illumination: the required illuminance for a living room is about 100 lx, for a kitchen about 300 lx, and for an office about 500 lx.

  • Cable derating example: a 2.0 mm² VVF cable rated 24 A at 30 °C, in a conduit with 4 circuits at 40 °C, applies a temperature factor of about 0.82 and a grouping factor of about 0.7, giving about 13.8 A.

  • Switch wiring: a single-pole switch is connected in the hot conductor, never in the neutral, so that the load is de-energized when the switch is off.

  • Practical exam parts: the test provides the cable, boxes, switches, outlets, and connectors; you must supply the tools and consumables such as tape and sleeves.

Quick reference

Construction-related E&M Trades

  • Cable support in a vertical shaft: support the cable at every floor and within 1 m of the top and bottom, and use a cable grip to relieve tension on the conductor.

  • Conduit expansion: install expansion fittings where the conduit run crosses a building expansion joint, and leave a gap of about 20 mm.

  • Grounding of metal enclosures: every metal box, panel, and conduit must be bonded to the grounding conductor with a listed bonding jumper or fitting.

  • Cable ampacity correction for ambient temperature: use the factor for the actual ambient, not the standard 30 °C, and apply the factor for the number of circuits in the same raceway.

  • Emergency power: a generator or battery must supply the emergency lighting and fire alarm circuits within 10 seconds of a power failure, per the 消防法.

  • Inspection before handover: verify the insulation resistance, grounding resistance, polarity, and breaker ratings, and record the results in the inspection report.

Quick reference

Trade Test for Grade A Electrical Work

  • Exam schedule: the written exam is usually held in spring and autumn; the practical exam is held after the written results are announced, typically in summer and winter.

  • Eligibility: Grade A requires no work experience, but the practical exam must be taken within a set period after passing the written exam.

  • Common practical problem: a two-way switch circuit with a pilot lamp, an outlet, and a leakage breaker; practice the layout and wiring sequence until it is automatic.

  • Cable stripping: use a VVF stripper set to the correct size; strip about 15 mm for a ring sleeve and 10 mm for a push-in connector.

  • Ring sleeve crimping: insert the conductor fully into the sleeve, crimp with the dedicated tool, and check that the sleeve is not cracked and the conductor cannot be pulled out.

  • Continuity test: use a tester to confirm each connection before energizing; a missing connection is the most common cause of failure.

  • Regulation: the 電気工事士法 requires a qualified person for the work; the exam tests the knowledge and skill required by that law.

  • Time limit: the practical exam ends exactly at the time limit; unfinished work is scored as incomplete, so leave time for the final inspection.

Quick reference

Construction-related E&M Trades

  • Cable tray grounding: bond each section of the tray to the grounding conductor, and use a bonding jumper across the joint if the tray is painted.

  • Switchboard ventilation: keep the ventilation openings clear and maintain the manufacturer's clearance to walls and other equipment.

  • Cable derating for high ambient: in a boiler room or attic, use the correction factor for the actual temperature, which may be 0.5 or lower at 50 °C.

  • Grounding resistance measurement: use the fall-of-potential method with two auxiliary electrodes, and space them at least 20 m apart for accurate results.

  • Insulation resistance test voltage: use 500 V for 300 V or less circuits and 1000 V for 300 V to 750 V circuits; never use a higher voltage than the circuit rating.

  • Panelboard circuit identification: label each breaker with the room and load, and update the label when a circuit is changed.

Quick reference

Trade Test for Grade A Electrical Work

  • Study focus: the 配線図 problem is often the deciding factor; practice reading single-line diagrams and identifying the correct wire size and breaker rating.

  • Common formula: for a three-phase load, I = P / (√3 × V × cos θ); for a single-phase load, I = P / (V × cos θ).

  • Cable size selection: use the 内線規程 table for the allowable current, then apply the temperature and grouping factors, and check the voltage drop.

  • Breaker coordination: the breaker rating must be less than or equal to the cable's allowable current after derating, and greater than the load current.

  • Practical exam layout: mark the positions of the boxes and switches on the board before wiring, and keep the cable runs straight and neat.

  • Common failure: reversed polarity at the outlet; check that the hot wire connects to the shorter slot and the neutral to the longer slot.

  • Exam tip: read the entire problem before starting, and identify the required parts and connections; a missed part is a lost point.

Quick reference

Construction-related E&M Trades

  • Cable in a hazardous location: use a cable with a flame-retardant sheath and seal the conduit at the boundary of the hazardous area.

  • Grounding of a transformer: the secondary neutral must be grounded at the transformer or at the first disconnect, and the grounding conductor must be sized per the 内線規程.

  • Cable support for a horizontal run: support at intervals of 2 m or less, and within 1 m of each box or fitting.

  • Insulation resistance of a motor: a reading below 1 MΩ indicates moisture or a fault; dry the motor before energizing.

  • Panelboard working space: maintain at least 1.2 m in front of the panel, and do not store materials in the working space.

  • Cable derating for a buried conduit: apply a soil thermal resistivity correction and a depth correction in addition to the ambient and grouping factors.

Quick reference

Trade Test for Grade A Electrical Work

  • Question type: the written exam includes true/false and multiple-choice questions; the practical exam is a hands-on task scored by inspectors.

  • Common topic: the 電気設備技術基準 requires that a circuit be protected against overload and short circuit, and that the grounding be appropriate for the circuit voltage.

  • Cable ampacity: a 1.6 mm² VVF cable carries about 17 A at 30 °C; apply derating for higher ambient and for multiple circuits in the same conduit.

  • Switch connection: a 3-way switch has a common terminal and two traveler terminals; the common terminal connects to the source or the load.

  • Practical exam: the test board has pre-marked positions; follow the drawing exactly and do not improvise the layout.

  • Common mistake: using a ring sleeve that is too large for the conductor, which causes a loose connection and a failed inspection.

  • Exam tip: bring a spare tester and spare sleeves; a failed tool can end the practical exam.