Mistake 1

Reading a superheat or subcooling question and answering with the target value instead of calculating the measured value from the given suction/discharge pressures and line temperatures.

Candidates memorize '10°F superheat' or '10–12°F subcooling' as rules of thumb and skip the arithmetic, or they confuse superheat (suction line above saturation) with subcooling (liquid line below saturation).

What to do instead

On every charging question, write the four numbers before choosing: suction pressure converted to saturation temperature, measured suction line temp, discharge/liquid pressure converted to saturation temp, measured liquid line temp. Then compute both SH and SC and select the one the stem asks for. Practice converting R-410A and R-22 pressures with a PT chart until conversion is automatic.

Mistake 2

Treating a low-side pressure reading as a diagnosis by itself, then replacing the compressor or reversing valve when the actual fault is airflow, a restricted metering device, or an overcharge.

Low suction pressure has many causes and the exam deliberately offers several plausible component failures; candidates who jump to the component with the most dramatic symptom miss the diagnostic sequence.

What to do instead

Apply a fixed order on every diagnostic stem: verify airflow and filter first, then check superheat/subcooling together, then delta-T across the coil, then component-level electrical checks. Use the SH/SC combination as the discriminator - high SH with low SC points to undercharge or restriction; low SH with high SC points to overcharge or airflow.

Mistake 3

Mixing up the sequence and purpose of evacuation and leak detection - pulling a vacuum before confirming the system holds pressure, or relying on a standing vacuum decay alone to prove a leak is fixed.

Field shortcuts and time pressure teach techs to 'just pull it down,' and exam stems describe a system that 'held 500 microns' without stating a nitrogen pressure test.

What to do instead

Memorize the standing order: recover refrigerant, pressure-test with dry nitrogen (and trace gas for small leaks), repair, then evacuate to 500 microns or below with a decay test, then charge by weight or by superheat/subcooling. On the exam, any answer that skips the pressure test or the micron decay is wrong.

Mistake 4

Confusing the roles of the metering device, the accumulator, and the receiver - for example, stating that a TXV maintains superheat in a fixed-orifice system or that a receiver is used on a residential split system.

These components are taught together and the exam tests whether the candidate knows which system architecture uses which device and what each controls.

What to do instead

Build a one-page comparison: TXV/EEV modulates to hold superheat and is used on most residential and commercial splits; fixed orifice/piston meters a fixed flow and relies on charge for superheat; accumulator (suction side) protects the compressor from liquid in a heat pump or reverse-cycle system; receiver (liquid side) stores charge on systems with a receiver, typically commercial or larger equipment. Answer by identifying the system type first.

Mistake 5

Ignoring the difference between a heat pump's heating and cooling cycle when reading pressures, so the 'high side' and 'low side' are identified backwards in heating mode.

In heating mode the indoor coil becomes the condenser and the outdoor coil becomes the evaporator; candidates who learned cooling-only pressure logic misread the gauge readings and choose the wrong component as faulty.

What to do instead

Before answering any heat pump stem, state the mode out loud and map the coils: heating mode means hot gas goes to the indoor coil and the outdoor coil is the evaporator with a defrost cycle. Then interpret pressures against that map. Also confirm the reversing valve solenoid state and whether defrost is active.

Mistake 6

Calculating temperature rise or airflow without converting units, or accepting a furnace temperature rise outside the data plate range as normal.

Stems give CFM, Btu/h, and delta-T in mixed units, and candidates either skip the sensible heat equation or round so aggressively that a 70°F rise on a nameplate calling for 35–65°F looks acceptable.

What to do instead

Use the standard relation: Btu/h output = 1.08 × CFM × temperature rise (for standard air). Rearrange to solve for the missing variable, and always compare the result to the data plate rise range. A rise above range means low airflow; below range means high airflow or overfiring. Show the units in your scratch work so the exam's unit traps are visible.

Mistake 7

Diagnosing a no-heat call by replacing the ignitor first, without verifying the 24V call, the pressure switch proving, and the flame sensor signal in sequence.

Ignitors are a common real-world failure and the most memorable part, so candidates pattern-match to it and skip the safety chain that the exam is actually testing.

What to do instead

Walk the ignition sequence in order on every stem: thermostat call for heat, induced draft blower proving, pressure switch closure, ignition attempt, flame proving, gas valve stay-open, then blower on delay. Identify the last step that occurred successfully and answer at the next step. A failed flame sensor typically proves flame then drops out after a few seconds - that detail distinguishes it from a bad ignitor.

Mistake 8

Misapplying Ohm's law across a series circuit in a control circuit, or measuring voltage with the meter in the wrong configuration (amps in parallel, volts in series).

Control circuits combine switches, transformers, and loads in series, and candidates who only memorized E=IR for a single load misplace the meter or misread a voltage drop across an open switch.

What to do instead

Draw the circuit as a loop before answering. Volts are measured in parallel across a load; amps in series with the load. An open switch shows full source voltage across it and zero volts across the load. Verify transformer VA capacity against the connected load, and remember a 24V control circuit reading 0V at the load with 24V at the transformer points to an open in the loop, not a bad transformer.

Mistake 9

Selecting a capacitor, contactor, or motor replacement by physical size or 'close enough' microfarad rating rather than nameplate rating and tolerance.

Candidates treat capacitors as interchangeable and forget that a failed run capacitor can mimic a bad compressor or blower motor, and that the exam tests tolerance limits and correct ratings.

What to do instead

Always compare measured microfarads to the nameplate rating and accept only within the marked tolerance (commonly ±6% for run capacitors, wider for start capacitors). Know that a bulged or open capacitor causes high current and no-start symptoms that look like a seized motor. For motors, match voltage, phase, horsepower, RPM, frame, and rotation - not just physical dimensions.

Mistake 10

Guessing at code or safety requirements - clearance to combustibles, venting categories, condensate trapping, or refrigerant safety classification - instead of using the standard the exam names.

Candidates rely on what their local jurisdiction or their last job did, and the exam tests the referenced standard (for example, venting category by flue pressure, or A2L refrigerant handling rules).

What to do instead

For any code-flavored stem, identify which standard is being invoked and answer from that standard's logic: Category I vents with negative pressure and a chimney, Category III with positive pressure and a listed vent, Category IV condensing with positive pressure and PVC. For refrigerants, know the ASHRAE safety group letters and that A2L refrigerants are mildly flammable and require specific handling. If the stem does not name a standard, answer with the most conservative safety-compliant option.