HVAC Excellence Master LC-AC flashcards
HVAC Excellence Master LC-AC · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Sensible heat ratio
- Ratio of sensible heat removed to total heat removed by an evaporator coil. Typical comfort range is 0.70–0.80; lower values indicate more latent (moisture) removal.
- Superheat
- Difference between actual suction line temperature and saturated suction temperature at the same pressure. Indicates whether the evaporator is properly fed with refrigerant.
- Subcooling
- Difference between saturated condensing temperature and liquid line temperature. Confirms solid liquid refrigerant at the metering device; typical TXV target is 8–12°F.
- Evaporator TD
- Return air dry-bulb minus supply air dry-bulb across the evaporator. Typical 15–22°F; high TD suggests low airflow, low TD suggests overcharge or high airflow.
- Condenser TD
- Outdoor ambient temperature minus saturated condensing temperature. Typical 15–25°F; elevated TD indicates dirty coil, non-condensables, or overcharge.
- 400 cfm per ton
- Standard airflow rule for cooling: one ton (12,000 Btu/h) of capacity requires about 400 cfm. Range 350–450 cfm/ton; low airflow risks coil freeze.
- Refrigerant glide
- Temperature difference between bubble point and dew point of a zeotropic blend at a given pressure. R-410A glide is about 0.2°F; R-407C is about 10°F.
- Static pressure budget
- Total external static pressure (TESP) measured across the air handler. Residential target is 0.5–0.8 in. w.c.; values above 0.8 indicate duct restriction.
- Temperature rise
- Supply air temperature minus return air temperature across a furnace. Must fall within the nameplate range (typically 35–65°F); high rise means low airflow.
- Combustion air requirement
- About 10 ft³ of air per 1,000 Btu of gas input for complete combustion, plus 50 ft³ per 1,000 Btu for dilution and ventilation.
- Manifold pressure
- Gas pressure at the burner manifold with the appliance firing. Natural gas typically 3.5 in. w.c.; LP gas typically 10–11 in. w.c.
- Flue draft
- Negative pressure at the flue collar of a natural-draft appliance, typically −0.02 to −0.04 in. w.c. Positive pressure indicates blocked vent or spillage.
- AFUE
- Annual Fuel Utilization Efficiency: seasonal efficiency rating for furnaces and boilers. Minimum 80% for standard; 90%+ for condensing appliances.
- Condensing furnace condensate
- Acidic water (pH ~3–5) produced by condensing furnaces. Must be neutralized before drain disposal and vented with PVC, CPVC, or polypropylene.
- Electric heat output
- Resistance heat produces 3,412 Btu/h per kW. Output in Btu/h equals volts × amps × 3.412, or kW × 3,412.
- Sensible heat formula
- Btu/h = cfm × 1.08 × ΔT for standard air. Used to calculate heating or cooling sensible capacity from airflow and temperature difference.
- Combustion analysis targets
- For natural gas: O₂ 4–9%, CO₂ 8–10%, CO below 100 ppm air-free, excess air 25–50%. Values outside range indicate improper combustion.
- Compression ratio
- Absolute discharge pressure divided by absolute suction pressure. Ratios above about 10:1 cause high discharge temperature and reduced capacity.
- Evacuation standard
- Evacuate a refrigeration system to 500 microns or lower and perform a standing vacuum test: rise less than 500 microns in 10 minutes.
- Recovery cylinder limit
- Refrigerant recovery cylinders must not be filled above 80% of their volume by liquid. Use a scale to verify weight and prevent hydrostatic rupture.
- POE oil
- Polyolester lubricant used with HFC and HFO refrigerants such as R-410A and R-134a. It is hygroscopic, so keep containers sealed and evacuate thoroughly.
- Mineral oil
- Lubricant used with CFC and HCFC refrigerants such as R-12 and R-22. It is not miscible with HFC refrigerants and must not be mixed with POE.
- Superheat at compressor
- Suction line temperature at the compressor minus saturated suction temperature. Typical target 20–30°F; lower values risk liquid slugging.
- Nitrogen pressure test
- Leak test using dry nitrogen at 150–300 psig on refrigerant lines. Never use oxygen or compressed air with refrigerant; both can cause fire or explosion.
- PT chart
- Pressure–temperature chart that converts saturation pressure to saturation temperature for a specific refrigerant. Essential for superheat and subcooling calculations.
- Ohm's law
- V = I × R. Voltage equals current times resistance. Used to troubleshoot electrical circuits and verify motor windings and heater elements.
- Locked-rotor amps
- Current drawn by a motor at startup with the rotor stationary. Typically 5–6 times running-load amps for PSC compressors; verify against the nameplate.
- Capacitor tolerance
- Run and start capacitors are typically rated ±6% of nameplate microfarads. Measure with a meter; bulged or leaking capacitors must be replaced.
- Motor winding test
- Run-to-common plus start-to-common resistance should equal run-to-start. Open winding reads infinite ohms; shorted winding reads near zero.
- Thermostat wiring letters
- R = 24V power, C = common, W = heat, Y = cool, G = fan, O/B = reversing valve, AUX/E = auxiliary or emergency heat.
- Defrost control
- Heat pump control that initiates defrost on accumulated compressor run time and coil temperature, and terminates on coil temperature or a time limit.
- Three-phase motor current
- I = (HP × 746) / (√3 × V × efficiency × PF). Used to verify actual current draw against nameplate full-load amps.