HVAC Excellence Master LC-AC study materials
HVAC Excellence Master LC-AC study resources

HVAC Excellence Master LC-AC flashcards

HVAC Excellence Master LC-AC · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Sensible heat ratio
Ratio of sensible heat removed to total heat removed by an evaporator coil. Typical comfort range is 0.70–0.80; lower values indicate more latent (moisture) removal.
Superheat
Difference between actual suction line temperature and saturated suction temperature at the same pressure. Indicates whether the evaporator is properly fed with refrigerant.
Subcooling
Difference between saturated condensing temperature and liquid line temperature. Confirms solid liquid refrigerant at the metering device; typical TXV target is 8–12°F.
Evaporator TD
Return air dry-bulb minus supply air dry-bulb across the evaporator. Typical 15–22°F; high TD suggests low airflow, low TD suggests overcharge or high airflow.
Condenser TD
Outdoor ambient temperature minus saturated condensing temperature. Typical 15–25°F; elevated TD indicates dirty coil, non-condensables, or overcharge.
400 cfm per ton
Standard airflow rule for cooling: one ton (12,000 Btu/h) of capacity requires about 400 cfm. Range 350–450 cfm/ton; low airflow risks coil freeze.
Refrigerant glide
Temperature difference between bubble point and dew point of a zeotropic blend at a given pressure. R-410A glide is about 0.2°F; R-407C is about 10°F.
Static pressure budget
Total external static pressure (TESP) measured across the air handler. Residential target is 0.5–0.8 in. w.c.; values above 0.8 indicate duct restriction.
Temperature rise
Supply air temperature minus return air temperature across a furnace. Must fall within the nameplate range (typically 35–65°F); high rise means low airflow.
Combustion air requirement
About 10 ft³ of air per 1,000 Btu of gas input for complete combustion, plus 50 ft³ per 1,000 Btu for dilution and ventilation.
Manifold pressure
Gas pressure at the burner manifold with the appliance firing. Natural gas typically 3.5 in. w.c.; LP gas typically 10–11 in. w.c.
Flue draft
Negative pressure at the flue collar of a natural-draft appliance, typically −0.02 to −0.04 in. w.c. Positive pressure indicates blocked vent or spillage.
AFUE
Annual Fuel Utilization Efficiency: seasonal efficiency rating for furnaces and boilers. Minimum 80% for standard; 90%+ for condensing appliances.
Condensing furnace condensate
Acidic water (pH ~3–5) produced by condensing furnaces. Must be neutralized before drain disposal and vented with PVC, CPVC, or polypropylene.
Electric heat output
Resistance heat produces 3,412 Btu/h per kW. Output in Btu/h equals volts × amps × 3.412, or kW × 3,412.
Sensible heat formula
Btu/h = cfm × 1.08 × ΔT for standard air. Used to calculate heating or cooling sensible capacity from airflow and temperature difference.
Combustion analysis targets
For natural gas: O₂ 4–9%, CO₂ 8–10%, CO below 100 ppm air-free, excess air 25–50%. Values outside range indicate improper combustion.
Compression ratio
Absolute discharge pressure divided by absolute suction pressure. Ratios above about 10:1 cause high discharge temperature and reduced capacity.
Evacuation standard
Evacuate a refrigeration system to 500 microns or lower and perform a standing vacuum test: rise less than 500 microns in 10 minutes.
Recovery cylinder limit
Refrigerant recovery cylinders must not be filled above 80% of their volume by liquid. Use a scale to verify weight and prevent hydrostatic rupture.
POE oil
Polyolester lubricant used with HFC and HFO refrigerants such as R-410A and R-134a. It is hygroscopic, so keep containers sealed and evacuate thoroughly.
Mineral oil
Lubricant used with CFC and HCFC refrigerants such as R-12 and R-22. It is not miscible with HFC refrigerants and must not be mixed with POE.
Superheat at compressor
Suction line temperature at the compressor minus saturated suction temperature. Typical target 20–30°F; lower values risk liquid slugging.
Nitrogen pressure test
Leak test using dry nitrogen at 150–300 psig on refrigerant lines. Never use oxygen or compressed air with refrigerant; both can cause fire or explosion.
PT chart
Pressure–temperature chart that converts saturation pressure to saturation temperature for a specific refrigerant. Essential for superheat and subcooling calculations.
Ohm's law
V = I × R. Voltage equals current times resistance. Used to troubleshoot electrical circuits and verify motor windings and heater elements.
Locked-rotor amps
Current drawn by a motor at startup with the rotor stationary. Typically 5–6 times running-load amps for PSC compressors; verify against the nameplate.
Capacitor tolerance
Run and start capacitors are typically rated ±6% of nameplate microfarads. Measure with a meter; bulged or leaking capacitors must be replaced.
Motor winding test
Run-to-common plus start-to-common resistance should equal run-to-start. Open winding reads infinite ohms; shorted winding reads near zero.
Thermostat wiring letters
R = 24V power, C = common, W = heat, Y = cool, G = fan, O/B = reversing valve, AUX/E = auxiliary or emergency heat.
Defrost control
Heat pump control that initiates defrost on accumulated compressor run time and coil temperature, and terminates on coil temperature or a time limit.
Three-phase motor current
I = (HP × 746) / (√3 × V × efficiency × PF). Used to verify actual current draw against nameplate full-load amps.