Quick reference

Refrigeration Fundamentals and System Components

  • Sensible heat changes temperature without a phase change (Q = 1.08 × CFM × ΔT for air); latent heat changes state at constant temperature (about 1,055 Btu per lb of water vaporized at standard conditions).

  • Superheat = actual suction line temperature minus saturated suction temperature at the same pressure; subcooling = saturated condensing temperature minus liquid line temperature. Both are measured with pressure converted to saturation temperature.

  • The four required functions in any mechanical refrigeration circuit are compression, condensation, metering (expansion), and evaporation; removing any one stops the heat pump cycle from moving heat uphill.

  • TXV/EEV capacity rises as evaporator load rises because the valve modulates to hold superheat; a fixed orifice (piston) flow depends on pressure difference and does not modulate.

  • Pressure–enthalpy diagram: compression is roughly isentropic up to discharge, condensation is constant pressure desuperheat/condense/subcool, metering is near-isenthalpic, evaporation is constant pressure and temperature.

  • Compressor types and typical use: hermetic reciprocating for small/medium loads, scroll for light commercial rooftop and split systems, semi-hermetic for serviceable commercial work, rotary for small residential.

  • Evaporator airflow rule of thumb for comfort cooling: about 400 CFM per ton; low airflow drops suction pressure and superheat and can freeze the coil, high airflow raises both.

  • Accessory functions: filter-drier removes moisture and acid, accumulator protects the compressor from liquid floodback, receiver stores liquid, muffler reduces discharge pulsation, oil separator returns oil to the crankcase.

  • Refrigerant glide is the temperature difference between bubble and dew points of a zeotropic blend; charge zeotropic systems as liquid and use dew point for superheat, bubble point for subcooling.

Quick reference

Light Commercial System Installation and Piping

  • Nitrogen purge while brazing at roughly 1–3 psig flow; the purge prevents internal oxidation (copper oxide flakes) that later plug driers, TXV screens, and capillary tubes.

  • Use a heat-sink or wet rag on valves and service ports, and flow nitrogen through the tubing with the system open to atmosphere; never braze with refrigerant in the circuit.

  • Horizontal suction lines should slope about 1/4 inch per 10 feet toward the compressor; traps are used at the base of risers and every 15–20 feet of vertical riser for oil return.

  • Line sizing balances oil return and pressure drop: keep suction velocity high enough to carry oil, keep liquid-line pressure drop below about 2–3 psi, and size hot gas lines per manufacturer tables.

  • Evacuation target is typically 500 microns or below with a standing vacuum decay test; triple evacuation with nitrogen sweeps helps remove moisture from large or contaminated systems.

  • Rooftop/condensing unit clearances: follow nameplate minimums for service access and airflow, mount on a level curb or pad, and isolate vibration with properly torqued spring or neoprene isolators.

  • Tubing support spacing is roughly 6 feet for horizontal runs and every floor for vertical risers; use hangers that do not crush insulation and allow thermal expansion.

  • Brazing filler for copper-to-copper is typically BCuP (phosphorus) without flux; copper-to-brass or copper-to-steel requires silver-bearing filler with flux and post-braze flux removal.

Quick reference

Electrical and Controls

  • Ohm's law and power: E = I × R, P = I × E; single-phase P = V × A × PF, three-phase P = 1.732 × V × A × PF. Locked-rotor current is typically 5–7 times running current.

  • Motor winding diagnosis: measure winding resistance to common on hermetic compressors; an open winding reads infinite, a shorted winding reads near zero, and a grounded winding reads continuity to the shell.

  • Capacitor check: use a meter with capacitance function or the microfarad scale; a bulged or out-of-tolerance run capacitor (typically ±6% for motor run) causes high current and poor starting.

  • Contactors and relays: a pitted or welded contactor contact keeps the compressor running or prevents starting; check coil voltage and pull-in with the control circuit energized.

  • Defrost and safety controls: high-pressure cutout, low-pressure cutout, oil pressure switch (typically 120-second delay), and freeze stat protect the compressor and coil; bypassing them is a diagnostic shortcut, not a repair.

  • Thermostat/controller wiring: R to W calls heat, R to Y calls cooling, G runs the indoor fan, and O/B reverses the reversing valve on heat pumps; keep 24 V control wiring away from line-voltage runs.

  • Electrical troubleshooting sequence: verify supply voltage and phasing, check fuses/breakers, then control voltage, then the load circuit; a single-phase condition on a three-phase compressor will trip internal overloads.

  • NEC-relevant practice: size branch-circuit conductors and overcurrent protection to the nameplate minimum circuit ampacity and maximum overcurrent protection, and bond the cabinet to the equipment grounding conductor.

Quick reference

System Performance and Charging

  • Target superheat for a fixed-orifice system is set by indoor wet-bulb and outdoor dry-bulb from the manufacturer charging chart; TXV systems instead set subcooling per nameplate, commonly 8–12°F.

  • Weigh-in charging is the most accurate method: use the nameplate factory charge plus the additional charge per foot of line length specified for the installed liquid-line size.

  • Approach method for condensers: condensing temperature minus outdoor ambient; a high approach with clean coils and correct airflow points to overcharge or non-condensables.

  • Evaporator superheat too high with normal subcooling suggests a restricted metering device or low load; superheat too low with high subcooling suggests overcharge or a stuck-open TXV.

  • Superheat and subcooling must be read under steady-state conditions: run at least 15–20 minutes, with all doors/panels in place, correct airflow, and stabilized pressures and temperatures.

  • Airflow verification: static pressure with a manometer, temperature rise/split across the coil (about 18–22°F for comfort cooling), and blower speed taps matched to the required CFM per ton.

  • Refrigerant pressure corresponds to saturation temperature: R-410A at 118 psig is about 40°F evaporating; R-22 at 68 psig is about 40°F. Use a PT chart for the actual refrigerant, not a generic one.

  • Non-condensables show as high discharge pressure and high subcooling with a normal-to-high approach; recover, evacuate, and recharge by weight rather than adding refrigerant.

Quick reference

Diagnosis, Service, and Repair

  • Diagnostic order: gather complaint, verify airflow and filters, measure pressures and temperatures, compute superheat/subcooling, then compare against the manufacturer chart before touching the charge.

  • Frozen evaporator causes: low airflow (dirty filter/coil, bad blower), low charge, restricted metering device, or a stuck-open TXV; never add refrigerant to a frosted coil before finding the cause.

  • Compressor won't start: check supply voltage, control voltage at the contactor coil, overload/thermal protector, run capacitor, and winding resistance; a hum with high current suggests a stuck rotor or bad capacitor.

  • High head pressure: dirty condenser, recirculated air, failed condenser fan, overcharge, non-condensables, or high ambient; low head pressure: low load, low ambient, or undercharge.

  • Low suction pressure: restricted liquid line/drier, undercharge, iced coil, or a failing TXV bulb; high suction pressure: overcharge, excess load, or a stuck-open valve.

  • Leak detection: electronic leak detector, soap bubbles, and UV dye; nitrogen pressure test to the manufacturer's test pressure, then evacuate to 500 microns before recharging.

  • Electrical/mechanical repair verification: after replacing a compressor, confirm correct rotation on three-phase, check oil level, record amps versus nameplate RLA, and recheck superheat/subcooling.

  • Refrigerant recovery and handling: recover into DOT-approved cylinders, never exceed 80% fill by weight, follow EPA Section 608 rules, and label recovered refrigerant.