HVAC Excellence Master LC Refrigeration flashcards
HVAC Excellence Master LC Refrigeration · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Sensible heat
- Heat that changes a substance's temperature without changing its state. In air it is estimated with Q = 1.08 x CFM x temperature difference, using dry-bulb readings.
- Latent heat
- Heat absorbed or released during a phase change at constant temperature, such as boiling or condensing refrigerant. It does not show on a thermometer but moves most of the system's capacity.
- Superheat definition
- The number of degrees a vapor is above its saturation temperature at the measured pressure. Suction superheat is measured at the evaporator outlet and indicates metering device performance.
- Subcooling definition
- The number of degrees a liquid is below its saturation temperature at the measured pressure. Liquid-line subcooling confirms the condenser has fully condensed refrigerant and is used for TXV charging.
- TXV operation
- A thermostatic expansion valve modulates refrigerant flow to hold a set evaporator superheat. Its bulb senses outlet temperature, and rising superheat opens the valve to admit more refrigerant.
- Accumulator purpose
- A vessel on the suction line that traps liquid refrigerant and oil and meters them back as vapor, protecting the compressor from liquid floodback in systems without a receiver or with long line sets.
- Zeotropic blend glide
- The temperature spread between bubble point and dew point for a blend such as R-407C. Charge as liquid, and use dew point for superheat and bubble point for subcooling calculations.
- Compressor locked rotor amps
- The current drawn when the rotor cannot turn, typically five to seven times running load amps. Compare measured inrush against the nameplate LRA to judge winding and start components.
- Nitrogen purge while brazing
- A low-pressure nitrogen flow through the tubing during brazing displaces oxygen and prevents copper oxide scale. Scale flakes later clog driers, screens, and capillary tubes and cause restrictions.
- Suction line oil return
- Horizontal suction runs slope about a quarter inch per ten feet toward the compressor, and traps at riser bases plus periodic riser traps keep oil moving back to the crankcase.
- Evacuation micron target
- Most manufacturers specify 500 microns or lower, verified by a standing vacuum decay test. A rising vacuum after isolation indicates moisture or a leak in the circuit.
- Triple evacuation
- Evacuate, break the vacuum with dry nitrogen, and repeat. The nitrogen sweeps absorb and carry out residual moisture, which is useful on large or contaminated systems.
- Phosphorus brazing filler
- BCuP filler is used for copper-to-copper joints without flux. Copper to brass or steel requires silver-bearing filler and flux, and flux residue must be cleaned after brazing.
- Liquid line pressure drop
- Excessive liquid-line drop causes flash gas ahead of the metering device and reduces capacity. Keep drop low, typically under two to three psi, by sizing lines per manufacturer tables.
- Equipment clearance and pad
- Rooftop and condensing units need level mounting, nameplate service clearances, unobstructed airflow, and vibration isolators torqued to specification to prevent noise and line fatigue.
- Line set support spacing
- Horizontal refrigerant tubing is typically supported about every six feet, with vertical risers supported at each floor. Hangers must not crush insulation or restrict thermal movement.
- Ohm's law and power
- E = I x R and P = I x E. For three-phase loads, P = 1.732 x V x A x power factor. These formulas size circuits and verify measured current against nameplate ratings.
- Hermetic winding check
- Measure resistance from each terminal to common and to the shell. Infinite resistance means an open winding, near zero means a short, and continuity to the shell means a grounded compressor.
- Run capacitor test
- Use the capacitance function or microfarad scale and compare with the nameplate rating, usually within about six percent. A weak or bulged capacitor causes high current and poor starting.
- Contactor failure signs
- Pitted, burned, or welded contacts cause intermittent operation or a compressor that will not shut off. Verify coil voltage and pull-in before replacing the contactor.
- Low pressure cutout
- A safety switch that stops the compressor when suction pressure falls below a setpoint, protecting against low charge and coil freeze-up. It should never be bypassed as a permanent repair.
- Oil pressure safety switch
- A control that trips the compressor if oil pressure does not rise within a timed interval, commonly 120 seconds, after startup. It protects against bearing damage from oil failure.
- Heat pump reversing valve
- The valve is energized or de-energized through the O or B terminal to swap evaporator and condenser roles. A valve stuck mid-travel causes poor heating and cooling performance.
- Nameplate MCA and MOP
- Minimum circuit ampacity sizes the branch-circuit conductors, and maximum overcurrent protection sizes the breaker or fuse. Both come from the equipment nameplate, not from rules of thumb.
- Weigh-in charging
- The most accurate charging method: nameplate factory charge plus additional charge per foot of installed liquid line, adjusted for line size. Use it whenever the total charge is known.
- TXV subcooling target
- For TXV systems, charge to the nameplate subcooling, commonly eight to twelve degrees Fahrenheit, measured at the condenser outlet with steady-state conditions and correct airflow.
- Fixed orifice superheat
- Superheat for a piston system is set from the manufacturer chart using indoor wet-bulb and outdoor dry-bulb. Target values commonly range from about five to fifteen degrees.
- Condenser approach method
- Condensing temperature minus outdoor ambient. A high approach with clean coils and correct airflow indicates overcharge or non-condensables rather than a load problem.
- Steady-state readings
- Pressures and temperatures are valid only after fifteen to twenty minutes of operation with panels in place, correct airflow, and stable readings. Charging before stabilization misleads diagnosis.
- Evaporator air temperature split
- For comfort cooling, the difference between return and supply air is commonly about eighteen to twenty-two degrees Fahrenheit. A low split suggests low load or excess airflow.
- Non-condensable symptoms
- High discharge pressure and high subcooling with a normal or high condenser approach, often after poor evacuation. Correct by recovering refrigerant, evacuating, and recharging by weight.
- Frozen evaporator diagnosis
- Frost indicates low airflow, low charge, a restricted metering device, or a stuck-open valve. Find and correct the cause before adding refrigerant or the coil will refreeze.