General Regulations

  • A plumbing permit and inspections are required before work begins; piping must be tested and approved before concealment.

  • Materials must be approved and listed; used or defective materials may be installed only with approval of the authority having jurisdiction.

  • Drainage and vent systems are tested with a 10-foot water head or 5 psi of air for at least 15 minutes.

  • Water supply systems are hydrostatically tested at 100 psi, or at working pressure when that is higher, for 60 minutes.

  • Piping passing through foundation walls must be sleeved and sealed with a flexible, corrosion-resistant material.

  • Pipe must be protected from freezing, corrosion, and physical damage; water service is buried below the local frost line.

  • Pipe in trenches requires proper bedding and continuous support; support spacing follows the table for each pipe material.

  • Joints requiring maintenance must remain accessible; concealed mechanical joints and unions are limited to approved locations.

Quick reference

Administration and Definitions

  • The authority having jurisdiction (AHJ) enforces the code; 'approved' means accepted by the AHJ, usually through listing by a testing agency.

  • The building drain receives waste inside the building and extends 30 inches beyond the outside face of the wall; the building sewer continues from there.

  • A soil stack carries sewage, a waste stack carries non-fecal waste, and a vent stack serves the drainage system.

  • A drainage fixture unit (dfu) expresses the probable waste flow a fixture contributes to the drainage system.

  • Developed length is the pipe length measured along the centerline, including the allowance for fittings.

  • Trap seal is the vertical water depth in a trap, measured from the trap weir to the top of the dip.

  • Flood level rim is the edge of a receptacle from which water overflows when it is filled to capacity.

  • A cross-connection is any actual or potential connection between potable water and a nonpotable source.

Quick reference

Plumbing Math and Pipe Sizing Calculations

  • 1 psi equals 2.31 feet of water column; 1 foot of water column equals 0.433 psi, so pressure = 0.433 × height in feet.

  • Flow equation Q = A × V; 1 gallon per minute equals 0.002228 cubic feet per second, and 1 cfs equals 448.8 gpm.

  • Circle area = π d²/4 = 0.7854 d²; volume in gallons = cubic feet × 7.48.

  • Hazen-Williams head loss: h = 4.727 L Q^1.852 / (C^1.852 d^4.87), with h and d in feet, Q in cfs, and L in feet.

  • Offset multipliers: 45° travel = 1.414 × offset; 22.5° = 2.613; 60° = 1.155.

  • Slope conversions: 1/4 inch per foot = 2 percent; 1/8 inch per foot = 1 percent; fall = slope × length.

  • Drainage fixture units commonly used: water closet 3, lavatory 1, bathtub 2, shower 2, kitchen sink 2, washing machine 2.

  • Water supply fixture units commonly used: tank water closet 2.5, flushometer water closet 10, lavatory 1, bathtub 2, shower 2.

  • Pipe expansion: ΔL = L × α × ΔT; for steel, α is about 6.5 × 10⁻⁶ inch per inch per degree Fahrenheit.

Quick reference

Drainage Systems and Drainage Piping

  • Drainage pipe 2 inches and smaller slopes at 1/4 inch per foot; 3-inch and larger pipe may slope at 1/8 inch per foot where approved.

  • Cleanouts are required at the base of each stack, at changes of direction of 45 degrees or more, at intervals not exceeding 100 feet, and at the building sewer.

  • A horizontal drain turning to vertical must use long-radius fittings or an approved combination of 45-degree bends.

  • Sanitary tees are not permitted on horizontal drainage lines or on their backs; wyes and combination fittings are used instead.

  • The fall of a trap arm may not exceed one pipe diameter, and the trap arm must be vented within its permitted length.

  • The building sewer is sized from total drainage fixture units and slope, with a 3-inch minimum size typical.

  • A backwater valve is required where fixtures are below the elevation of the next upstream manhole or the street.

  • Vertical stacks must be supported at the base and restrained against lateral movement at each floor level.

Quick reference

Vents and Venting Systems

  • Every trap requires a vent except where a combination waste and vent system is specifically approved.

  • Vent pipe must be at least 1-1/4 inch in size and may not be smaller than required for the fixture units served.

  • A fixture vent must rise at least 6 inches above the flood level rim before any horizontal offset.

  • Vent terminals extend at least 6 inches above the roof, or 12 inches where snow is likely, and must be unobstructed.

  • Vent piping is graded so that moisture drains back to the drainage system, typically at 1/4 inch per foot.

  • A wet vent also serves as a drain and is generally limited to a bathroom group on the same floor.

  • A common vent may serve two fixture traps on the same floor when it is sized for the combined fixture units.

  • An island sink uses a loop vent installed below the floor with an accessible cleanout.

  • Air admittance valves are permitted only where approved, must be accessible, and require an air intake opening.

Quick reference

Traps, Interceptors and Special Wastes

  • A trap must maintain a water seal of at least 2 inches and not more than 4 inches.

  • Each fixture is separately trapped, except where a single trap is specifically permitted for a set of fixtures.

  • S-traps, double traps, and bell traps are prohibited; drum traps are allowed only for special wastes where approved.

  • A grease interceptor is required for commercial kitchens and is sized by fixture load and flow.

  • Sand and oil interceptors are required for garages, repair shops, and similar facilities.

  • Interceptors must be accessible for cleaning and have removable, gastight covers.

  • A floor drain trap subject to evaporation requires a trap primer to maintain the seal.

  • Fats, oils, grease, sand, oil, and harmful chemicals may not be discharged to the drainage system without treatment.

Quick reference

Water Supply and Water Distribution

  • Fixtures must receive at least 8 psi residual pressure under normal flow; flushometer valves typically require 15 to 25 psi.

  • A pressure-reducing valve is required when supply pressure exceeds 80 psi and is commonly set to 50 psi.

  • Design velocity is typically kept at 4 to 8 feet per second; higher velocities cause noise and erosion.

  • Water service pipe is buried below the frost line and protected from freezing and corrosion.

  • Water hammer arrestors are installed near quick-closing valves to absorb shock waves.

  • A closed system with a backflow preventer requires a thermal expansion tank.

  • Copper horizontal pipe is typically supported every 6 feet and vertical pipe every 10 feet, subject to the material table.

  • A corporation stop is installed at the main, a curb stop at the property line, and the meter downstream of the curb stop.

Quick reference

Plumbing Fixtures and Fixture Fittings

  • Federal maximums: water closet 1.6 gpf, urinal 1.0 gpf, showerhead 2.5 gpm at 80 psi, lavatory faucet 2.2 gpm at 60 psi.

  • A water closet must be at least 15 inches from its centerline to any side wall and have at least 21 inches of clearance in front.

  • Fixture tailpieces may not exceed 24 inches from the fixture outlet to the trap.

  • A fixture drain air gap must be at least 1 inch or twice the drain diameter, whichever is greater.

  • Floor drains require a trap seal and a primer where evaporation can occur.

  • Escutcheons are required where fixture supply or waste piping penetrates a wall or floor.

  • Accessible lavatories require knee clearance and insulated drain and supply piping.

  • Fixture fittings must be of approved type, and slip joints must be accessible.

Quick reference

Water Heaters and Temperature Control

  • A temperature and pressure relief valve is typically set to open at 210 degrees Fahrenheit or 150 psi, whichever occurs first.

  • The TPR valve must not be capped, and its discharge pipe must be full size, flow by gravity, and have an unthreaded end.

  • The relief discharge terminates 6 inches above the floor or outside the building where it cannot cause injury.

  • A drain pan is required where a leak would cause damage, with the pan drain routed to a safe location.

  • A water heater in a garage must be elevated so its ignition source is at least 18 inches above the floor.

  • A thermal expansion tank is required on closed systems where a backflow preventer or check valve is installed.

  • Seismic strapping uses two straps, one in the upper third and one in the lower third of the tank.

  • Delivered water temperature is typically limited to 120 degrees Fahrenheit, with higher storage temperatures using a mixing valve.

Quick reference

Fuel Gas Piping and Gas Appliances

  • Gas piping is sized by the longest-length method using gas specific gravity, available pressure, and allowable pressure drop.

  • A sediment trap or drip leg is installed downstream of the appliance shutoff valve and upstream of the controls.

  • A manual shutoff valve must be installed within 6 feet of the appliance and be readily accessible.

  • Appliance connectors may not exceed 6 feet and may not pass through walls, floors, or ceilings.

  • Low-pressure gas piping is commonly tested with air at 10 psi for 10 minutes with no pressure drop.

  • Gas piping must be bonded to the grounding electrode system; CSST is installed per the manufacturer's instructions.

  • Unions and mechanical joints are permitted only in accessible locations.

  • Appliances require venting and clearance to combustibles per their listing and the manufacturer's instructions.

  • A regulator vent must terminate outdoors in a location protected from water and debris.

Quick reference

Backflow Prevention and Cross-Connection Control

  • An air gap is the only absolute method of backflow prevention and is required for high-hazard connections.

  • A reduced-pressure principle assembly is used for high hazards; a double check valve assembly is used for low hazards.

  • A pressure vacuum breaker is commonly used for irrigation systems and must be installed above the highest downstream outlet.

  • Backflow assemblies must be tested at installation and annually by a certified tester.

  • Backsiphonage is caused by negative pressure in the supply; backpressure is caused by downstream pressure exceeding supply pressure.

  • Cross-connections between potable water and nonpotable sources are prohibited.

  • Hose bibbs require vacuum breakers to prevent contamination from hoses and attachments.

  • An atmospheric vacuum breaker may not be under continuous pressure for more than 12 hours.