- NEC Purpose (Article 90)
- Article 90 states the Code is a minimum safety standard for practical safeguarding of persons and property from electrical hazards, not a design manual.
- Branch Circuit Definition
- Per Article 100, the circuit conductors between the final overcurrent device protecting the circuit and the outlet or outlets served.
- Mandatory vs Permissive Rules
- Mandatory rules use "shall" and must be followed; permissive rules use "shall be permitted" and allow optional methods.
- Informational Notes Status
- Informational notes in the NEC explain or reference material but are not enforceable requirements; they do not add mandatory rules.
- Working Clearance Table
- Table 110.26(A)(1) sets minimum depth of working space in front of electrical equipment based on voltage to ground and condition of surrounding surfaces.
- Plan Review Submittal Contents
- A reviewable electrical plan typically includes load calculations, service and feeder schedules, grounding details, and device/outlet layouts.
- Adopted Code Edition
- The edition of the NEC in force is the one adopted by the local jurisdiction, which may lag the most recently published edition.
- Dwelling General Lighting Load
- The general lighting load for dwellings is 3 VA per square foot of floor area, used as the base for the standard calculation.
- Small-Appliance Circuit Load
- Each 20 A small-appliance branch circuit in a dwelling is calculated at 1,500 VA; at least two such circuits are required.
- Laundry Branch Circuit
- A dwelling laundry branch circuit is calculated at 1,500 VA and must be a 20 A circuit supplying laundry receptacle outlets.
- Continuous Load 125% Rule
- Continuous loads are taken at 125% of their value for conductor and overcurrent device sizing; noncontinuous loads are taken at 100%.
- Standard OCPD Ratings
- Section 240.6 lists standard ampere ratings including 15, 20, 30, 40, 50, 60, 70, 100, 125, 150, 200, 400, and 600 amperes.
- Dwelling Receptacle Spacing
- In dwelling units, no point on a wall space is more than 6 feet from a receptacle, and wall spaces 2 feet or wider require one.
- Optional Dwelling Calculation
- The optional method applies 100% of the first 10 kVA of general load plus 40% of the remainder, then adds other loads.
- Service Disconnect Rating
- The service disconnecting means must have a rating not less than the calculated load and must be sized per the service conductors.
- Grounding Electrode Types
- Section 250.52 lists electrodes including underground metal water pipe, building steel, concrete-encased electrode, ground ring, rods, and plates.
- Ground Rod 25 Ohm Rule
- A single rod or pipe electrode must have 25 ohms or less resistance to earth, or a supplemental electrode must be added.
- Equipment Grounding Conductor Size
- Table 250.122 sizes equipment grounding conductors based on the rating of the overcurrent device protecting the circuit.
- Main Bonding Jumper
- The main bonding jumper connects the grounded service conductor to the service equipment enclosure and grounding electrode conductor at the service.
- GEC Sizing Basis
- Table 250.66 sizes the grounding electrode conductor based on the largest ungrounded service-entrance conductor.
- Next-Size-Up Rule
- Section 240.4(B) permits the next higher standard overcurrent rating if it does not exceed 800 A and load does not exceed conductor ampacity.
- GFCI Dwelling Locations
- Section 210.8(A) requires GFCI protection for dwelling bathroom, garage, outdoor, kitchen countertop, laundry, and unfinished basement receptacles.
- Hazardous Location Classes
- Class I covers flammable gases or vapors, Class II combustible dusts, and Class III ignitible fibers or flyings.
- Divisions and Zones
- Division 1/2 and Zone 0/1/2 designations describe the likelihood of hazardous atmosphere; equipment must be listed for the specific classification.
- Health Care Redundant Grounding
- Article 517 requires redundant grounding and, in critical-care areas, an insulated/isolated grounding conductor for patient care receptacles.
- Assembly Occupancy Rules
- Article 518 covers assembly occupancies and addresses emergency lighting, exit illumination, and wiring methods for large occupant loads.
- Theaters and Stage Wiring
- Article 520 addresses theaters, audience areas, and stages, including portable switchboards and stage set lighting requirements.
- Listed and Labeled Equipment
- Equipment must be listed by a recognized testing laboratory and installed per its listing; field modification may void the listing.
- Dedicated Equipment Space
- Section 110.26(E) requires dedicated space above and in front of electrical equipment for access and maintenance, shown on plans.
- Permit and Inspection Process
- Administrative provisions require a permit, approved plans, scheduled inspections, and final approval before the installation is energized.
- Revised Plan Approval
- Field changes or deviations from approved plans require revised drawings and re-approval by the authority having jurisdiction before proceeding.