ICC Masonry Inspector S2 study materials
ICC Masonry Inspector S2 study resources

ICC Masonry Inspector S2 cheat sheet

ICC Masonry Inspector S2 · Keep the key ideas within reach.

Quick reference

Masonry Materials and Construction Practices

  • Mortar Types (ASTM C270): M = highest compressive strength, used for below-grade and severe exposure; S = moderate-high, typical for structural and lateral-load walls; N = general-purpose above-grade veneer; O = low-strength, non-load-bearing interior; K = lowest, rarely permitted.

  • Mortar cement (ASTM C1329) Types M, S, N must not be confused with portland cement Types I-V (ASTM C150); mortar cement may contain limestone and has air-content limits different from masonry cement.

  • Masonry cement (ASTM C91) Types M, S, N are preblended with plasticizers; field mixing with portland cement produces 'mortar cement blends' whose proportions must follow the mortar cement manufacturer's instructions, not Table 1 of C270.

  • Mortar proportion specification (C270 Table 1) is by volume of portland cement : lime : sand; property specification requires testing of compressive strength, water retention, and air content instead.

  • Grout (ASTM C476) fine grout requires all sand passing a 3/8 in. sieve; coarse grout permits up to 50% of aggregate passing 1/2 in. Grout slump for fine grout is typically 8-11 in. and coarse 8-11 in. when pumped.

  • CMU ASTM C90 load-bearing units have minimum net-area compressive strength 1,900 psi (average of 3 units); C129 non-load-bearing units require 1,000 psi minimum. Absorption and dimensional tolerances differ.

  • Clay brick ASTM C216 (facing) and C652 (hollow brick) grade SW for severe weathering, MW for moderate, NW for negligible. Grade SW requires 24-hour cold water absorption ≤ 6% and saturation coefficient ≤ 0.78.

  • Anchor bolts: TMS 402/602 requires 1/2 in. minimum diameter, embedment of at least 4 in. into grout, and a minimum edge distance of 1-3/4 in. from the face of the wall for bolts in the center of a grouted cell.

  • Wall ties and anchors: joint reinforcement must be lapped at least 6 in. or per manufacturer; ties in veneer must have at least 1 in. embedment into mortar and 5/8 in. clearance from the exterior face for corrosion protection.

Quick reference

Plan Review and Permits

  • Plan review must verify the construction documents show: foundation and wall sizes, reinforcement size and spacing, grout placement sequence, mortar type, unit compressive strength, and lateral support details.

  • Special inspection requirements: TMS 402/602 Chapter 6 (or IBC Chapter 17) requires special inspection for masonry when f'm > 1,500 psi, when the structure is in Seismic Design Category C or higher, or when required by the building official.

  • Permit application submittals typically include a sealed drawing set, structural calculations, geotechnical report for foundation design, and a statement of special inspections (IBC 107.1 and 1704).

  • Code path: IBC 2021 Section 2101 adopts TMS 402/602-16 by reference; the designer must state whether the design uses allowable stress (ASD) or strength design (SD).

  • Deferred submittals for masonry (e.g., engineered truss lintels, post-installed anchors) must be listed on the construction documents with the responsible design professional identified.

  • Fire-resistance ratings for masonry walls are determined per IBC Table 721.1(2) or by listing; plan review must verify the required rating matches the assembly's equivalent thickness and grout fill.

  • Energy code (IECC) compliance for masonry walls is typically shown via U-factor tables (IECC Table C402.1.4) or COMcheck; verify continuous insulation and thermal bridging details on the plans.

  • Plan review checklist items: wall height-to-thickness ratio (h/t) limits per TMS 402 Section 5.5.3, allowable stresses for the specified f'm, and reinforcement details for shear walls including boundary elements.

  • When a plan lacks required information, the building official may issue a permit with conditions or return the plan; IBC 107.3.4 permits the official to require additional data for unusual design.

Quick reference

Inspection Procedures and Testing

  • Pre-construction meeting and verification: confirm approved submittals, mix designs, unit test reports, and the special inspection schedule before masonry begins.

  • Mortar and grout sampling: ASTM C780 covers sampling and testing of mortar for compressive strength (2 in. cubes) and consistency; grout is tested per ASTM C1019 using prisms of the masonry units it will fill.

  • Prism testing: ASTM C1314 masonry prisms determine f'm for the as-built assembly; a minimum of three prisms per set, and the compressive strength is the average with no individual below 75% of the average.

  • Unit verification: sample CMU per ASTM C140 for compressive strength, absorption, and dimensions; brick per ASTM C67 for absorption and saturation coefficient.

  • Grout placement inspection: verify grout lift heights (typically 5 ft or 8 ft maximum depending on method), consolidation by puddling or vibration, and that cleanouts are installed at the bottom of grouted cells.

  • Reinforcement inspection: verify bar size, spacing, lap lengths (Class A = 30 db, Class B = 48 db for tension laps), and cover before grouting; bars must be held in position with ties or positioners.

  • Flashing and weepholes: verify flashing laps (minimum 6 in. for sheet metal), end dams, and weepholes at 24 in. on center maximum in the head joint above the flashing.

  • Grout pour inspection: verify the grout slump (8-11 in.), pour height, and that the grout is not dropped more than 5 ft without a tremie; verify that cold joints are properly prepared.

  • Post-tensioned masonry: verify tendon placement, anchorage, stressing records, and elongation measurements; stressing must be witnessed and recorded by the special inspector.

Quick reference

Code Administration and Enforcement

  • Authority: the building official enforces the adopted code; the special inspector reports to the building official and the registered design professional, not to the contractor.

  • Special inspection reports must be filed within 24 hours of the inspection and must state whether the work is in conformance; discrepancies require immediate notification.

  • Stop-work authority: the building official may issue a stop-work order (IBC 115) for work that is unsafe or not in accordance with the approved plans; the order must be in writing.

  • Certificate of occupancy (IBC 111) requires that all special inspection final reports, testing reports, and final inspections be complete and accepted by the building official.

  • Violations and penalties: IBC 113 allows the building official to serve notice of violation and assess penalties; the notice must specify the code section and required corrective action.

  • Appeals: a decision of the building official may be appealed to the board of appeals within the time specified by the local ordinance, typically 30 days; the appeal must be in writing and state the specific code interpretation at issue.

  • Contractor licensing: masonry contractors must hold a state or local license; the inspector verifies license and insurance before work begins and documents it in the inspection file.

  • Record retention: inspection records, test reports, and approved plans must be retained for the period specified by the jurisdiction, commonly the life of the building or a set number of years.

  • Conflicts of interest: the special inspector must be independent of the contractor and may not inspect work they installed; independence is a code requirement, not just an ethical guideline.