ID HVAC flashcards
ID HVAC · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Sensible heat equation
- Qs = 1.08 × CFM × ΔT, where 1.08 derives from air density, specific heat, and 60 minutes. Used to size airflow for a required temperature difference at sea level.
- Latent heat equation
- QL = 0.68 × CFM × ΔW, with ΔW in grains of moisture per pound of dry air. It quantifies the moisture-removal load that does not change dry-bulb temperature.
- Total heat equation
- Qt = 4.5 × CFM × Δh, where Δh is the enthalpy difference in Btu per pound between entering and leaving air. It combines sensible and latent capacity in one calculation.
- Dew point temperature
- The temperature at which air reaches saturation at constant humidity ratio; further cooling produces condensation. Coil surface temperature must be below it for dehumidification.
- Relative humidity definition
- The ratio of actual water vapor pressure in the air to the saturation vapor pressure at the same dry-bulb temperature, expressed as a percentage. It changes with temperature even if moisture content is constant.
- Wet-bulb temperature
- The temperature reached by evaporative cooling of a wetted sensor in moving air. It equals dry-bulb at 100 percent relative humidity and indicates total heat content for evaporative equipment.
- Bypass factor
- BF = (leaving air DB − apparatus dew point) ÷ (entering air DB − apparatus dew point). A low bypass factor means more air contacts the coil and greater dehumidification.
- Sensible heat ratio
- SHR = sensible heat ÷ total heat for a space or coil. A low SHR signals a large latent load requiring more moisture removal and lower coil apparatus dew point.
- Apparatus dew point
- The effective coil surface temperature at which air would leave fully saturated, found where the entering-to-leaving air line intersects the saturation curve on a psychrometric chart.
- Duct velocity equation
- Q = V × A, where Q is cubic feet per minute, V is velocity in feet per minute, and A is cross-sectional area in square feet. Rearranged, A = Q ÷ V for sizing.
- Velocity pressure formula
- VP = (V ÷ 4,005)² in inches of water column, with V in feet per minute at standard air density. Total pressure equals static plus velocity pressure.
- Fan law for CFM
- Airflow varies directly with fan speed: CFM₂ = CFM₁ × (RPM₂ ÷ RPM₁). It assumes the same fan, air density, and system resistance curve.
- Fan law for horsepower
- Brake horsepower varies with the cube of fan speed: BHP₂ = BHP₁ × (RPM₂ ÷ RPM₁)³. Small speed increases can overload a motor.
- Superheat measurement
- Suction line temperature minus the saturation temperature corresponding to suction pressure. Measured at the evaporator outlet, it confirms the refrigerant is fully vapor before the compressor.
- Subcooling measurement
- Saturation temperature at the liquid-line pressure minus the actual liquid-line temperature. It verifies the condenser has fully condensed refrigerant and that the charge is adequate on a TXV system.
- External static pressure
- The total resistance a blower works against, measured as supply static plus return static, including filter, coil, and duct pressure drops. Blower performance tables are rated at this value.
- Air changes per hour
- ACH = (CFM × 60) ÷ room volume in cubic feet. It expresses how many times the full room air volume is replaced each hour for ventilation or filtration checks.
- Outdoor air ventilation rate
- Ventilation airflow needed for acceptable indoor air quality, set by occupancy and floor area per ASHRAE 62.1. It is separate from the airflow needed for heating and cooling loads.
- Manual J load calculation
- ACCA method that sums transmission, infiltration, internal, and duct gains or losses room by room. It determines equipment capacity before selecting the unit and duct system.
- Manual D duct design
- ACCA procedure that sizes ducts using friction rate, equivalent length, and available static pressure. It matches duct resistance to the selected blower's performance curve.
- Manual S equipment selection
- ACCA method for matching equipment capacity to the Manual J load, checking sensible and latent capacity at design conditions. Oversizing raises cycling and reduces latent removal.
- Refrigerant glide
- The temperature difference between bubble and dew points of a zeotropic blend at a given pressure. Charging and superheat calculations must use the correct point for the blend.
- TXV superheat control
- A thermostatic expansion valve modulates refrigerant flow to hold a set evaporator superheat. It responds to bulb temperature and pressure, adapting to load changes.
- Compressor short cycling
- Rapid on-off operation caused by oversized equipment, low charge, or control faults. It reduces latent removal, raises humidity, and shortens compressor life.
- Furnace temperature rise
- The difference between supply and return air temperatures across a furnace, checked against the data plate range. Excess rise indicates low airflow; low rise indicates high airflow or overfiring.
- Combustion air requirements
- Category I gas appliances need dedicated or mechanical combustion air sized by code, often 50 cubic feet per 1,000 Btu input for indoor air. Inadequate air causes incomplete combustion and carbon monoxide.
- Heat pump balance point
- The outdoor temperature at which heat pump capacity equals building heat loss. Below it, supplemental or auxiliary heat must make up the difference.
- Heat pump defrost cycle
- A timed or demand-initiated reversal that melts frost from the outdoor coil. During defrost the outdoor fan stops and auxiliary heat often energizes to temper supply air.
- Economizer operation
- A damper system that uses cool outdoor air for free cooling when outdoor enthalpy or temperature is below the return air condition. It reduces mechanical cooling energy.
- VAV terminal box
- A zone device with a damper and often a reheat coil that modulates airflow from a central air handler. Minimum airflow settings maintain ventilation and prevent coil frosting.
- Filter MERV rating
- ASHRAE 52.2 minimum efficiency reporting value from 1 to 16, based on particle capture by size. Higher MERV captures finer particles but adds static pressure.
- Duct leakage testing
- Pressurizing a duct system and measuring leakage airflow against total fan airflow, often to 6 percent or less for new construction. Sealing reduces energy loss and improves comfort.