I.S. 10101 / ET101 Wiring Rules · Put your knowledge to work in context.

All case studies

Agricultural Installation with Livestock

A farm building houses cattle and has a 230 V lighting circuit and a 400 V three-phase supply to a feed auger motor. The building is of steel-framed construction with metallic cladding, and the floor is concrete that is often wet. The lighting is provided by batten luminaires at 2.5 m height, and the wiring is surface-run in plastic conduit. The earthing is TN-C-S with a Ze of 0.4 Ω, and the main protective bonding is 10 mm² to the steel frame. The farmer wants to add a 230 V socket outlet at 1 m height for a pressure washer, and a 400 V outlet for a welder. The existing installation has no RCD protection on the lighting circuit.

1. Assess the risks and compliance issues for this agricultural installation, and state what protection is required for the new outlets.

Read the worked answer

Special location. Agricultural buildings are a special location because of the presence of livestock, wet floors, and metallic structures. The risks include electric shock to animals and humans, and fire. The installation must provide supplementary protection, typically 30 mA RCD protection for all circuits, and equipotential bonding of all exposed and extraneous-conductive-parts.

Earthing and bonding. The steel frame is bonded with 10 mm², which is appropriate for a TN-C-S system with a supply neutral up to 35 mm². However, the concrete floor and metallic cladding mean that touch voltages can be significant. All metallic parts, including the cladding, must be bonded, and the bonding must be verified. The Ze of 0.4 Ω must be checked against the maximum Zs for the protective devices; for the lighting circuit, the disconnection time must be met, and RCD protection is required.

Lighting circuit. The lack of RCD protection on the lighting circuit is a deficiency in an agricultural building; 30 mA RCD protection should be provided, or the circuit should be re-designed. The luminaires at 2.5 m are above the reach of livestock but may be accessible to humans; they must be suitable for the environment (IP rating) and protected against impact.

New outlets. The 230 V socket for the pressure washer must be 30 mA RCD-protected, have a suitable IP rating for wet conditions, and be positioned so the lead does not trail through water. The 400 V welder outlet must also be RCD-protected (30 mA), with a suitable isolator, and the welder's supply must be sized for its rating. Both outlets must be in a location where they are not accessible to livestock and are protected from mechanical damage.

Verification. The installation should be inspected and tested, with particular attention to bonding continuity, RCD operation, and earth fault loop impedance.

2. The farmer proposes to use a 100 mA RCD for the welder outlet to avoid nuisance tripping. Is this acceptable?

Read the worked answer

No. In an agricultural location, the requirement is for 30 mA RCD protection for socket outlets and circuits where the risk of electric shock is increased. A 100 mA device does not provide the same level of protection and is not acceptable as the sole means of additional protection for a socket outlet in this environment. Nuisance tripping should be addressed by using a suitable type of RCD (for example, type A or B where appropriate), by separating circuits, or by using a time-delayed device only where discrimination is required - not by increasing the rated residual current beyond 30 mA for shock protection. The welder outlet must be 30 mA RCD-protected, and the welder's earth connection and the bonding of the steel frame must be verified. If the welder causes tripping, the cause (e.g. high protective conductor current, or a fault) should be investigated rather than defeated by a larger RCD.