I.S. 10101 / ET101 Wiring Rules study materials
I.S. 10101 / ET101 Wiring Rules study resources

I.S. 10101 / ET101 Wiring Rules cheat sheet

I.S. 10101 / ET101 Wiring Rules · Keep the key ideas within reach.

Quick reference

Scope, Fundamental Principles and Definitions

  • The wiring rules apply to electrical installations in buildings and to fixed installations supplied at standard low voltage; they cover design, erection, inspection and testing.

  • Fundamental principles: protection against shock, thermal effects, overcurrent, fault current and surge; installations must be safe in normal use and under single-fault conditions.

  • Definitions: an installation is an assembly of associated electrical equipment with coordinated characteristics to fulfil a specific purpose.

  • A live part is any conductor or conductive part intended to be energised in normal use, including a neutral conductor but not a PEN conductor.

  • Basic protection prevents contact with live parts under normal conditions; fault protection protects against contact under single-fault conditions.

  • An exposed-conductive-part is a conductive part of equipment that can be touched and is not live in normal use but may become live under fault conditions.

  • An extraneous-conductive-part is a conductive part not forming part of the installation that may introduce a potential, typically earth potential.

  • Equipment must be selected to withstand the prospective fault current and the environmental conditions of its location.

Quick reference

General Characteristics and Assessment of General Characteristics

  • Assessment covers: maximum demand and diversity, earthing arrangement, prospective fault current, and the nature of supply and load.

  • Diversity may be applied to maximum demand only where the load pattern justifies it; the designer must document the assumed diversity factors.

  • Installations are classified by earthing arrangement: TN-S, TN-C-S, TT, and IT systems determine protective measures and disconnection times.

  • Protective device selection depends on the supply characteristics: prospective short-circuit current, earth fault loop impedance, and disconnection time limits.

  • Conductor cross-sectional area is selected for current-carrying capacity, voltage drop, thermal withstand, and mechanical strength.

  • Voltage drop from the origin to the load should not exceed the limits set for the installation; lighting and power circuits are assessed separately.

  • The rated current of the supply and the number of circuits determine the arrangement of distribution boards and protective devices.

  • Environmental conditions (ambient temperature, grouping, installation method) derate cable current-carrying capacity via correction factors.

Quick reference

Protection for Safety: Electric Shock

  • Basic protection by insulation, barriers or enclosures, or by placing live parts out of reach; fault protection by automatic disconnection, double insulation, or separation.

  • Automatic disconnection: the disconnection time depends on the system (TN or TT) and the nominal voltage; typical limits are 0.4 s for TN final circuits up to 32 A.

  • Earth fault loop impedance must satisfy Zs ≤ U0 / Ia, where Ia is the current that causes the protective device to operate within the required time.

  • In TT systems, an RCD is generally required because the loop impedance is too high for overcurrent devices to disconnect within the time limit.

  • For a TT system, the relationship Ra × IΔn ≤ 50 V applies, where Ra is the earth electrode resistance and IΔn the RCD residual current.

  • Supplementary protection by 30 mA RCDs is required for socket-outlets up to 32 A for general use and in certain special locations.

  • Protection by electrical separation uses an isolating transformer or equivalent source supplying one item of equipment only.

  • SELV and PELV systems limit voltage to a safe value; SELV has no earth connection, PELV may be earthed.

Quick reference

Protection for Safety: Thermal Effects, Overcurrent and Surge

  • Overcurrent protection requires Ib ≤ In ≤ Iz, where Ib is design current, In the device rating and Iz the cable capacity.

  • The device must also satisfy I2 ≤ 1.45 × Iz, where I2 is the current ensuring effective operation of the protective device.

  • Coordination between conductors and devices ensures the cable is protected against overload and short circuit.

  • Short-circuit protection: the device must interrupt the prospective fault current and the cable must withstand the let-through energy (k²S² ≥ I²t).

  • Thermal effects: equipment and cables must not exceed their temperature limits in normal use or under fault conditions.

  • Surge protective devices (SPDs) limit transient overvoltages; they are selected by voltage protection level, discharge current and location.

  • SPDs are installed at the origin and, where required, near sensitive equipment; coordination between SPDs uses their voltage/current characteristics.

  • Overload protection may be omitted where interruption of the circuit would create a hazard, provided the risk of overload is excluded.

Quick reference

Selection and Erection of Wiring Systems

  • Wiring system selection considers: environmental conditions, mechanical stress, current-carrying capacity, and ease of maintenance.

  • Cables must be supported at intervals appropriate to the cable type and protected against mechanical damage where exposed.

  • Cable installation methods (clipped direct, in conduit, in trunking, buried) determine the reference method and hence the current rating.

  • Grouping of cables and thermal insulation reduce current-carrying capacity and require correction factors.

  • Segregation is required between power and communication/telecommunication cables to limit interference and fault spread.

  • Fire safety: wiring systems in escape routes and fire compartments must maintain circuit integrity where required.

  • Joints and connections must be accessible unless they are of a type that is maintenance-free and suitable for the location.

  • Cable entries into equipment must maintain the degree of protection (IP rating) of the enclosure.

Quick reference

Cables and Conductors

  • Conductor material is copper or aluminium; cross-sectional areas are selected for current capacity, voltage drop, and thermal withstand.

  • Minimum cross-sectional areas apply for fixed wiring and for flexible cords depending on the circuit and protective conductor function.

  • The neutral conductor must have a cross-sectional area not less than that required for the load; it may be reduced only where harmonics are negligible.

  • The protective conductor size depends on the phase conductor size, using the standard table relationship (S ≤ 16 mm² → S; larger sizes use S/2 with a minimum).

  • The adiabatic equation S ≥ √(I²t)/k verifies the protective conductor withstands fault energy, with k depending on conductor and insulation material.

  • Cable insulation types (PVC, XLPE) determine the maximum conductor operating temperature and hence the current rating.

  • Voltage drop is calculated from the load current, cable resistance and reactance, and circuit length; it must remain within the installation limit.

  • Conductors must be identified throughout the installation by colour or marking consistent with their function.

Quick reference

Earthing Arrangements, Protective Conductors and Bonding

  • Earthing arrangements: TN-S uses a separate protective conductor; TN-C-S uses a combined PEN split at the origin; TT uses a local earth electrode; IT is unearthed or earthed through impedance.

  • The main earthing terminal (MET) connects protective conductors, main protective bonding conductors, and the earthing conductor.

  • Main protective bonding connects extraneous-conductive-parts (water, gas, structural steel) to the MET; the conductor size depends on the supply neutral size.

  • Supplementary bonding connects simultaneously accessible exposed and extraneous-conductive-parts locally where disconnection times cannot be met.

  • The earthing conductor size is selected from the phase conductor size and must withstand prospective fault current.

  • The earth electrode resistance in a TT system must satisfy Ra × IΔn ≤ 50 V for the RCD protecting the installation.

  • Protective conductors must be identified green/yellow and must not carry load current except in a PEN conductor.

  • Bonding conductors must be mechanically protected and connected by permanent, reliable means.

Quick reference

Switchgear, Controlgear, Isolation and Switching

  • Every installation must have a means of isolation and switching for maintenance, emergency, and functional control.

  • Isolation must be by a device that provides a visible or clearly indicated break and is lockable or otherwise secured against reconnection.

  • Switching devices must be selected for the rated voltage, current, frequency, and the prospective fault current at the point of installation.

  • Devices must be capable of making and breaking the load current and, where required, the short-circuit current.

  • Emergency switching must be provided where a hazard could arise and must be clearly identified and accessible.

  • Functional switching controls the load in normal use; it need not provide isolation.

  • Protective devices must be coordinated so that the device nearest the fault operates first (discrimination).

  • RCDs must be selected for the type of residual current (AC, pulsating DC, smooth DC) and the required sensitivity.

Quick reference

Special Installations and Locations

  • Bathrooms: equipment is zoned; socket-outlets are generally excluded from zones 0, 1 and 2, and supplementary bonding may be required.

  • Zone 0 is inside the bath or shower basin; zone 1 is above it; zone 2 extends beyond zone 1; equipment must suit the zone.

  • Construction sites: installations must resist mechanical damage and harsh conditions; 30 mA RCDs protect socket-outlets and reduced voltages are used where required.

  • Agricultural and horticultural premises: equipment must withstand dust, moisture and corrosive atmospheres; RCD protection is widely required.

  • In locations with fire risk, equipment must be selected and installed to limit ignition and fire spread.

  • In conductive locations (metallic enclosures, restricted movement), protection by SELV, PELV, or electrical separation may be required.

  • Equipment in special locations must have an appropriate IP rating for water and dust ingress.

  • Where a special location requires a measure not used elsewhere, the requirement is additional to the general rules.

Quick reference

Inspection, Testing, Verification and Certification

  • Verification comprises inspection, testing, and the issue of a certificate and schedule of test results.

  • Inspection before testing checks: correct selection and erection, protection measures, identification, and accessibility.

  • Continuity testing verifies protective conductors, ring final circuits, and main and supplementary bonding.

  • Insulation resistance is measured with the installation isolated; the result must meet the minimum value for the circuit voltage.

  • Earth fault loop impedance is measured to confirm that protective devices disconnect within the required time.

  • RCD testing verifies the tripping current and operating time at the rated residual current and at half and five times that value.

  • Polarity must be verified so that all switches and protective devices are in the phase conductor.

  • Test results are recorded on a schedule, and the certificate confirms the installation complies with the wiring rules.