I.S. 10101 / ET101 Wiring Rules study materials
I.S. 10101 / ET101 Wiring Rules study resources

I.S. 10101 / ET101 Wiring Rules flashcards

I.S. 10101 / ET101 Wiring Rules · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Exposed-conductive-part
A conductive part of equipment that can be touched, is not live in normal use, but may become live under fault conditions; it requires protective earthing.
Extraneous-conductive-part
A conductive part not forming part of the installation that may introduce earth potential, such as metallic water or gas pipes and structural steel.
Basic protection
Protection against electric shock under normal conditions, achieved by insulation, barriers or enclosures, or by placing live parts out of reach.
Fault protection
Protection against electric shock under single-fault conditions, achieved by automatic disconnection, double insulation, or electrical separation.
Diversity factor
An assumed fraction applied to the sum of connected loads to estimate maximum demand, valid only where the load pattern justifies the reduction.
Prospective fault current
The current that would flow at a point if a short circuit of negligible impedance occurred there; used to select protective devices and cables.
TN-C-S system
An earthing arrangement where the supply neutral also serves as the protective conductor and is split into separate neutral and protective conductors at the origin.
Voltage drop limit
The maximum permitted reduction in voltage between the origin and the load, assessed separately for lighting and power circuits to ensure equipment operates correctly.
Earth fault loop impedance
The total impedance of the path from the origin through the phase conductor, fault, and protective conductor back to the source, denoted Zs.
Disconnection time
The maximum time permitted for a protective device to clear a fault; for TN final circuits up to 32 A it is typically 0.4 seconds.
TT system disconnection rule
In a TT system the earth electrode resistance times the RCD residual current must not exceed 50 volts, expressed as Ra × IΔn ≤ 50 V.
SELV system
A system operating at a safe extra-low voltage with no connection to earth, so that contact with live parts cannot cause a dangerous shock.
Overload coordination rule
The design current must not exceed the device rating, which must not exceed the cable capacity, and the device must operate before the cable overheats.
Adiabatic withstand
The cable or protective conductor must withstand fault energy, verified by k²S² being at least the let-through energy I²t of the protective device.
Surge protective device
A device that limits transient overvoltages by diverting surge current to earth, selected by voltage protection level and discharge current rating.
Grouping correction factor
A factor less than one applied to cable current rating when cables are bunched, because mutual heating reduces the ability to dissipate heat.
Reference installation method
A classification of how a cable is mounted (clipped, in conduit, buried) that determines its tabulated current-carrying capacity.
Circuit integrity
The ability of a wiring system to continue functioning during a fire, required for circuits supplying safety services and escape routes.
Protective conductor sizing
The protective conductor cross-section is related to the phase conductor size, with larger phase conductors allowing a reduced ratio subject to a minimum.
Maximum conductor temperature
The highest temperature a cable insulation may safely reach in normal or fault operation, determined by the insulation material such as PVC or XLPE.
Neutral conductor reduction
The neutral cross-section may be smaller than the phase conductor only where load and harmonic conditions permit, otherwise it must be adequate for the load.
Main earthing terminal
The terminal that connects the earthing conductor, protective conductors, and main protective bonding conductors together in an installation.
Main protective bonding
Connection of extraneous-conductive-parts to the main earthing terminal to prevent dangerous potential differences within the installation.
Supplementary bonding
Local connection of simultaneously accessible exposed and extraneous-conductive-parts where automatic disconnection alone cannot ensure safety.
PEN conductor
A combined protective and neutral conductor that carries both functions; it may only be used in fixed wiring where the supply arrangement permits.
Isolation
Cutting off supply from all live conductors for maintenance or repair, using a device with a clear break that can be secured against reconnection.
Functional switching
Control of equipment in normal use without providing isolation; it does not necessarily disconnect all live conductors.
Discrimination
Coordination of protective devices so that the device nearest a fault operates first, limiting the extent of supply interruption.
Bathroom zones
Defined regions around a bath or shower (0, 1 and 2) that restrict the type and location of electrical equipment according to water exposure.
Construction site protection
Harsh and wet conditions require robust equipment, reduced voltages where appropriate, and 30 mA RCD protection for socket-outlets.
Insulation resistance test
A test performed with the installation isolated to confirm insulation is sound, with results compared against the minimum value for the circuit voltage.
Polarity verification
A check that all switches and protective devices are connected in the phase conductor and that socket-outlet connections are correct.