I.S. 10101 / ET101 Wiring Rules: Switchgear, Controlgear, Isolation and Switching

I.S. 10101 / ET101 Wiring Rules ยท Work through your exam, one topic at a time.

All guide sections

Switchgear, Controlgear, Isolation and Switching

The four functions

Switching devices serve distinct purposes and questions test whether you can tell them apart:

  • Isolation: to cut off for maintenance/safety, with a visible or reliably indicated gap and lockable.
  • Emergency switching: to remove danger quickly (e.g. a stop button).
  • Functional switching: normal on/off control.
  • Emergency stopping: to bring dangerous motion to rest.

A device may perform more than one function, but isolation must always be capable of being secured (lockable) and must isolate all live conductors of the relevant circuit.

Isolation requirements

Isolation must break all live conductors (not the neutral necessarily, depending on the system and whether the neutral is switched), be clearly identified, and prevent inadvertent reconnection. A common trap: assuming a functional switch is suitable for isolation - it may not have the required contact separation or lockability.

Protective devices and coordination

Switchgear includes MCBs, RCCBs, RCBOs, fuses and main switches. Discrimination (selectivity) ensures the device nearest the fault operates first, limiting the outage. Check breaking capacity, discrimination, and that RCDs are not defeated by incorrect neutral/earth arrangements.

Controlgear

Contactors, relays and starters control loads. Consider duty, utilisation category (AC-1, AC-3 etc.), and that control circuits may need their own protection and isolation.

Worked rule of thumb

For any switching question, ask: (1) What is it for - isolation, emergency, functional? (2) Does it break all live conductors required? (3) Can it be locked off? (4) Is it correctly rated for the load and fault level? If any answer is no, the device is unsuitable for that function.

Special Installations and Locations

Why special locations differ

Special locations present increased risk - water, wetness, restricted movement, corrosive or explosive atmospheres, or inexperienced users. The rules impose zones, reduced disconnection times, mandatory RCDs, and restrictions on equipment. The exam loves zone boundaries and which measures apply in each zone.

Bathrooms and shower rooms

Zones 0, 1 and 2 surround the bath/shower, with a zone beyond. Zone 0 is inside the bath/shower basin; Zone 1 is above it; Zone 2 extends outward. Requirements include:

  • Supplementary bonding where required (or RCD protection as an alternative in some editions).
  • 30 mA RCD protection for circuits in the zones.
  • Socket outlets generally prohibited in zones 0โ€“2 (except shaver units to a standard in some positions).
  • Equipment must suit the zone (IP rating, SELV in Zone 0).

Construction sites

Harsh, temporary, and often damp. Requirements typically include 30 mA RCDs on socket outlets, robust cables, IP-rated equipment, and reduced disconnection times. Traps: assuming permanent-installation rules apply unchanged.

Agricultural and horticultural

Dust, damp, livestock, and corrosive atmospheres. Bonding of metallic structures and 30 mA RCD protection are commonly required; equipment must resist dust and water.

Other special locations

Swimming pools, saunas, caravan parks, marinas, medical locations, explosive atmospheres - each has its own zone and equipment rules. Learn the principle: the more vulnerable the user or the harsher the environment, the more protective measures are layered.

Worked rule of thumb

For any special location, draw the zones first, then ask: what equipment is permitted here, what IP rating, is an RCD required, and is supplementary bonding needed? Answer all four before choosing a device.

Inspection, Testing, Verification and Certification

The sequence

The verification process has three parts, in order: inspection (visual), testing, and certification. Inspection comes first because it identifies defects that testing may not reveal and ensures testing is safe. Testing follows a defined sequence - continuity of protective conductors, continuity of ring final circuit conductors, insulation resistance, polarity, earth electrode resistance (where applicable), earth fault loop impedance, RCD operation, and functional testing. Getting the order wrong is a classic exam trap.

Key tests and what they prove

  • Continuity of CPCs: proves the protective conductor is connected and has acceptable resistance (used to derive R1+R2).
  • Ring continuity: proves the ring is complete and not accidentally a figure-of-eight.
  • Insulation resistance: proves insulation integrity (test between live conductors and earth, and between live conductors).
  • Polarity: proves live/neutral/earth are correctly connected.
  • Earth fault loop impedance (Zs): proves disconnection times can be met.
  • RCD operation: proves trip time and current are within limits.

Certification and reporting

Certificates record the design, installation, inspection and test results. Condition reports record the condition of an existing installation. The person signing must be competent. Traps: confusing an Electrical Installation Certificate (new work) with a Minor Works Certificate (small alterations) and with a Condition Report (existing installation assessment).

Worked rule of thumb

Before energising, confirm: insulation resistance acceptable, polarity correct, CPC continuity proven, and Zs within limits. If Zs fails, do not energise - remedy first. Record every result; a missing test result is a defect in the verification.