F-Gas Category II (IE) study materials
F-Gas Category II (IE) study resources

F-Gas Category II (IE) cheat sheet

F-Gas Category II (IE) · Keep the key ideas within reach.

Quick reference

Legislation and obligations under F-Gas and ODS regulations

  • Regulation (EU) 2024/573 (F-Gas) controls fluorinated greenhouse gases including HFCs, PFCs and SF6; it replaced Regulation (EU) No 517/2014.

  • Regulation (EC) No 1005/2009 (ODS) controls ozone-depleting substances such as CFCs, HCFCs and halons; R-22 is an HCFC.

  • In Ireland, the Environmental Protection Agency (EPA) is the competent authority for F-Gas and ODS enforcement.

  • Operators must ensure that leak checking, servicing, recovery and charging are performed by personnel holding the appropriate F-Gas certification.

  • F-Gas certification is personal and activity-based; Category II holders may carry out the activities within their certified scope.

  • The EU HFC phase-down reduces the quantity of HFCs placed on the market, measured in CO2e, through a quota system.

  • Placing on the market of certain equipment is banned from specified dates based on refrigerant GWP and equipment type.

  • Records must be kept for at least five years and made available to the competent authority on request.

Quick reference

Environmental impact of fluorinated greenhouse gases and ozone-depleting substances

  • GWP is the 100-year global warming potential of a gas relative to CO2, whose GWP is 1.

  • CO2e in tonnes = refrigerant mass in kg × GWP ÷ 1000.

  • R-410A GWP = 2088; 1 kg released equals 2.088 tonnes CO2e.

  • R-404A GWP = 3922; 1 kg released equals 3.922 tonnes CO2e.

  • R-134a GWP = 1430; R-32 GWP = 675; R-407C GWP = 1774.

  • ODP is the ozone-depleting potential relative to CFC-11, set at ODP 1.0; HFCs have ODP = 0.

  • R-22 has ODP of about 0.055 and GWP of 1810; it is both ozone-depleting and a greenhouse gas.

  • TEWI combines direct refrigerant emissions with indirect CO2 emissions from energy use.

Quick reference

Leak checking, containment and record keeping

  • Leak checks: 5–50 tCO2e every 12 months; 50–500 tCO2e every 6 months; 500 tCO2e or more every 3 months.

  • A leak detection system halves the frequency: 24, 12 and 6 months respectively.

  • Leak detection systems are mandatory for equipment containing 500 tCO2e or more and must be checked annually.

  • Equipment below 5 tCO2e has no mandatory periodic leak-check interval; hermetically sealed equipment below 10 tCO2e is exempt.

  • After repairing a leak, the equipment must be leak-checked within 24 hours.

  • If a leak cannot be repaired, the equipment must be decommissioned.

  • Records include refrigerant type and charge, top-up amounts, leak-check dates and results, repairs and technician details.

  • Labels must state refrigerant type and CO2e charge; update the label after any charge change.

Quick reference

Recovery, recycling, reclamation and disposal of refrigerants

  • Recovery is the collection of refrigerant from equipment for reuse, recycling, reclamation or destruction.

  • Recycling is basic cleaning and reuse of recovered refrigerant; it does not restore virgin specification.

  • Reclamation is reprocessing to virgin specification, normally requiring laboratory analysis and certification.

  • Venting refrigerant to atmosphere is prohibited; recovery is required before servicing, decommissioning or disposal.

  • Recovered refrigerant is waste unless reclaimed or recycled to an appropriate standard; use an authorised waste contractor.

  • Never mix different refrigerants; mixed refrigerant cannot be reclaimed as a single product and is treated as waste.

  • Recovery cylinders must be dedicated, labelled and filled by weight; never exceed the cylinder's maximum filling ratio.

  • Destruction must be by an approved facility, with waste transfer records retained.

Quick reference

Safe handling, charging, commissioning and decommissioning of equipment

  • Wear gloves, goggles and protective clothing; liquid refrigerant can cause frostbite and vapour can displace oxygen.

  • Work in ventilated areas; refrigerant vapour is heavier than air and can accumulate in low spaces.

  • Charge refrigerant by weight using calibrated scales; charge zeotropic blends as liquid to prevent fractionation.

  • Never charge liquid refrigerant into the suction of a running compressor.

  • Pressure-test with dry nitrogen (OFN), never oxygen or compressed air; use a regulator.

  • Evacuate to 500 microns (about 67 Pa) and hold; a rising vacuum indicates moisture or a leak.

  • For A2L or A3 flammable refrigerants, remove ignition sources and use intrinsically safe leak detectors.

  • Before decommissioning, recover all refrigerant, isolate and purge with nitrogen, then label and remove equipment.